HVAC plant operating mode, for heat pump (HvacPltMod17)

Overview

The application function "HVAC plant operating mode 17, for fan coil unit, heat pump, radiant ceiling, radiator " (HvacPltMod17) selects the HVAC plant operating mode and considers the room operating mode, presence detection, HVAC presence mode and window contact. Warm-up and cool down request signals are received via the central operating mode AF.

Function

 

Next room operating mode (NxROpMod)

To enhance energy efficiency, NxROpMod can be set to match the room operating mode expected to follow warm-up or cool down. A typical use case is a seldom used conference room that normally goes into Pre-Comfort after warm-up or cool down. Setting NxROpMod to Pre-Comfort would prevent the over-cooling or over-heating of the space by allowing Pre-Comfort setpoints to be used instead of Comfort setpoints during the warm-up or cool down phase.

The table shows the standard plant mode selection. No configurable selections are available.

IF

Then

Room operating mode

Psc Det 1)

Hvac Psc Mod

Window contact

Vnt signal

NgtC signal

Cool down signal

Warmup signal

FreeC signal

Plant mode

--

--

--

Open

--

--

--

--

--

Protection

--

Closed

True

--

--

--

--

Ventila­tion 2)

Protec­tion

--

--

Closed

False

--

--

--

--

Protec­tion

Economy

--

--

False

False

False

False

Economy

True

False

False

False

Night cooling

--

True

False

False

Cool down

--

--

True

False

Warm-up

--

--

--

True

Free Cooling 3)

Pre-Comfort

--

No Psc Fnct

--

False

--

False

Pre-Comfort

--

True

--

False

Cool down

--

--

--

True

Free Cooling 3)

Present

Cons. present & absent

--

--

--

--

Comfort

Absent

Cons. present & absent

--

False

--

False

Pre-Comfort

--

True

--

False

Cool down

--

--

--

True

Free Cooling 3)

Comfort

--

No Psc Fnct

--

--

--

--

Comfort

Present

Cons. present & absent

--

--

--

--

Comfort

Absent

Cons. present & absent

--

False

--

False

Pre-Comfort

--

True

--

False

Cool down

--

--

--

True

Free Cooling 3)

1) Presence detection with switch-on/off delay functionality, see Configuration.

2) Not supported by HvacPltMod17.

3) Only if in addition heating not active.

Configuration

Parameters

Description

Parameter

Default value

Switch delay when present

SwiDlyPrst

5 [min]

Switch delay when absent

SwiDlyAbst

5 [min]

Interface

Interface

Description

Type

Ref.

Owned by

PltOpMod

Plant operating mode

1:Off
2:Protection
3:Economy
4:Pre-Comfort
5:Comfort
6:Warm-up
7:Cool down
8:Room low temperature protection
9:Condensation overflow protection
10:Free cooling
11:Night cooling
12:Ventilation
13:Equipment temperature protection
14:Air volume flow off
15:Not used
16:Not used
17:Not used

MPrcVal

-

CoolDwnReq

Cool down request

0:Inactive
1:Active

BCalcVal

1)

WarmUpReq

Warm-up request

0:Inactive
1:Active

BCalcVal

1)

NgtCReq

Night cooling request

0:Inactive
1:Active

BCalcVal

1)

FreeCReq

FreeCReq

0:Inactive
1:Active

BCalcVal

1)

NxROpMod

Next room operating mode

▶ Can be set to match the room operating mode expected to follow warm-up or cool down, when that mode is not Comfort.

1:Protection
2:Economy
3:Pre-Comfort
4:Comfort

MPrcVal

1)

CenEmgHvac

Central emergency for HVAC

GrpMbr

-

RCtl

Room control

GrpMaster

Room

1) Received from central AFs, provided here for monitoring.