Fume hood sash positioner (FhSashPsnr11)

Overview

The application function "Fume hood sash positioner 11" (FhSashPsnr11) applies to a Fume Hood Sash Positioner that automatically closes a vertical fume hood sash when triggered by specific conditions. Safeties, to avoid closing on an obstruction, must be supplied by others.

The output device is a sash closer provided by a third party. There is no function to drive the vertical sash to any other position. Regardless of the number of sashes on the hood, there is only one sash closer AF in the application and only one sash closer BO (FhSashPsnrCls). In a complex installation, the BO may be wired to more than one closer.

Main features:

Function

The application supports several closing criteria. When any closing criterion is true, the sash closure object (FhSashPsnrCls) is pulsed on for the time set in PulseLngtCls, closing the sash. It repeats the pulse regularly while the sash closing criteria remains true.

The duration of FhSashPsnrCls pulse and the repeat interval command for closing DlyRptCls are configurable.

 

Command or request (or related)

Notification of condition or status, or availability

Device mode

Interlock (internal signal, not a BACnet object; see Interlocks section for additional information)

Criteria to close sash

The application can be configured to close the sash in response to these criteria:

Configuration

Parameters

Description

Parameter

Default value

Pulse length for close
▶ The length of time the signal to the sash closing device will be turned on.

PulseLngtCls

1 [s]

Delay before repeat close
▶ The signal to the sash closing device will be repeated every DlyRptCls whne FhOcc = Ucd or when FhOpMod = Off, Fire, or Emergency.

DlyRptCls

120 [min]

Enable close with reset of energy efficiency
▶ If set to Yes, the signal to the sash closing device will be turned on when the green leaf button on the ODP is pressed.

0:No
1:Yes

EnClsEeiRst

0:No

Interface

Interface

Description

Type

Ref.

Owned by

FhSashPsnrCls

Fume hood sash positioner close

0:Normal
1:Close

BO

Room segment / Field device

FhSashPsnrCmd

Fume hood sash positioner command

0:Ready
1:Close

MTrigVal

-

FhSashClsInCol

Collection of fume hood sash close input

ColView

-

 

FhSashClsInRs

Result of fume hood sash close input

0:Off
1:On

BCalcVal

-

FhSashClsIn

Fume hood sash close input

0:Off
1:On

BCalcVal

Room segment / Field device

Engineering and commissioning

Optional.