Fume hood sash, external only (FhSash14)

Note to reader
Optional.

Overview

The application function "Fume hood sash 14, external only" (FhSash14) is used to assign the face area from a Sash Open Area Module (SOAM) to a BACnet object and report the status of the sash sensors connected to the SOAM to other AFs.

The binary output represents the valid state of FhFaceArea. The output is monitored by other modules to indicate a failure on the Operator Display Panel, activate alarms, and to set the valid state of other objects.

Main features:

Function

 

Command or request (or related)

Notification of condition or status, or availability

Device mode

Interlock (internal signal, not a BACnet object; see Interlocks section for additional information)

Face area calculation

The Sash Open Area Module (SOAM) is an external device that has additional sash inputs and calculates an open area based on a separate configuration. The SOAM is connected to the fume hood controller via the sensor bus (SCOM).

Face area is determined by the following:

Face area valid signal

The FaceAreaVld output is used by other modules to determine if the general fume hood failure alarm should be active and to set other objects to valid.

The FaceAreaVld signal is a combination of valid signals from the sash 1 position sensor and external face area. ExtFaceArea is used to determine if there is an active external face area device.

The output will only be ON and FhFaceArea will only be set valid when the external face area is valid

 

Feature configuration

Feature selections for "Room HVAC coordination" are accessed via the Application configuration task in the Configuration component.

Feature (AF)

Feature description

Ref.

Trend for fume hood face area

None/Active

Configuration

Parameters

Description

Parameter

Default value

Area on sensor failure
▶Set AreaSenFail to the value that should be used as the fume hood face area in the event of communication error with the SOAM.

AreaSenFail

0.5 [m2]
5.38 [ft2]

Area unit
▶ Defined by selected engineering unit – do not change.

AreaUnit

[m2]
[ft2]

Interface

Interface

Description

Type

Ref.

Owned by

FhExtFaceArea

Fume hood external face area

AI

Room segment / Field device

FhFaceArea

Fume hood face area

ACalcVal

-

TrndFhFaceArea

Trend for fume hood face area

FtrSel

-

 

TrndFhFaceArea

Trend for fume hood face area

TrndLogS

-

Engineering and commissioning

Optional.