Modbus Integration (AI - subsystem-specific extension)
The Analog Input (AI) object supports following properties of the subsystem-specific extension Integration.
✳ Indicates a Siemens proprietary property.
Index, BACnet objects editor > Properties > Configuration
Data type ✳ |
|
| |||
|---|---|---|---|---|---|
Data type defines the data type for encoding the subsystem-specific data type. | |||||
8 bit and 16 bit integer data formats with Registers: | |||||
Encoding format | Description | Byte order | |||
U8 | unsigned 8-bit | 00 aa | |||
U16-B | unsigned 16-bit; big-endian | bb aa | |||
In case of U8, S8: the most significant byte is 0. | |||||
32 / 64 bit integer data formats with Registers: | |||||
Encoding format | Description | Byte order | |||
U32-B | unsigned 32-bit; big-endian | dd cc bb aa | |||
S32-B | signed 32-bit; big-endian | dd cc bb aa | |||
U48-B | unsigned 48, big-endian | ff ee dd cc bb aa | |||
S48-B | signed 48, big-endian | ff ee dd cc bb aa | |||
U64-B | unsigned 64, big-endian | hh gg ff ee dd cc bb aa | |||
S64-B | signed 64, big-endian | hh gg ff ee dd cc bb aa | |||
Example: | |||||
16 / 32 / 64 bit float data formats with Registers: | |||||
Encoding format | Description | Byte order | |||
F16-B | float 16, big-endian | bb aa | |||
F32-B | float 32, big-endian | dd cc bb aa | |||
F64-B | float 64, big-endian | hh gg ff ee dd cc bb aa | |||
Example:
| |||||
Polling times ✳ |
|
| |
|---|---|---|---|
"Polling times" defines the polling timer to be used to poll the subsystem-specific data point. The interval values for T1, T2, T3 can be configured in the Fieldbus-Management-Object. | |||
T1 | Highest priority. Typical interval value: 0.5s...5s. | ||
T2 | Medium priority (default). Typical interval value: 5s…60s. | ||
T3 | Low priority. Typical interval value: minutes ... hours. | ||
Process value 1 and Process value 2Input value 1 and Input value 2 ✳ |
|
|
|---|---|---|
"Process value 1" (X1), "Process value 2" (X2), "Input value 1" (Y1) and "Input value 2" (Y2) are used to calculate the linear function (f). The linear function is needed to calculate the input value out of the process value. Range: -3.402822E+38...3.402822E+38 | ||