Calendar (Calendar)
The BACnet object "Calendar" contains exception days, defined as single date, date range and/or weekday entries. The BACnet object "Scheduler" (Schedule) can reference such a calendar and interprets these date entries as exception days.
"Calendar" is a Siemens proprietary BACnet object.
✳ Indicates a Siemens proprietary property.
Present value |
|
|
|---|---|---|
'Present value' indicates the present value of the virtual variable. | ||
Property ID: 85 | ||
State flag ✳ |
|
|
|---|---|---|
"State flag" represents four boolean flags ("Out of service", "Overridden", "Fault", "In-Alarm") that indicate the general status of an object. | ||
Reliability |
|
|
|---|---|---|
'Reliability' indicates whether the property value 'Present value' is reliable. If the 'Present value' is not reliable, the property 'Reliability' indicates the cause of the fault and the bit "Fault" of the state indication is set to 'True'. In a normal case, the property 'Reliability' is set to "No fault". | ||
Property ID: 103 | ||
Date list |
|
| ||
|---|---|---|---|---|
"Date list" is a List of calendar entries. | ||||
Name | Value | Description | ||
| 0..30 | Up tp 30 calendar entries, consisting of a single date and/or date ranges. | ||
| ||||
| Single date | The calendar entry is active on a specific date. | ||
*-*-*-1 | Every Monday | |||
| Date range | The calendar entry is active during a date range. | ||
2017-04-02 | The present day is an exception day if the present date is within the specified start and end date range. | |||
| Weekday | The calendar entry is active on a specific weekday. | ||
July, Third, Tuesday | Tuesday, the third week of July. | |||
Date and time formats are not based on the Windows regional settings. On the automation station, date entries are always limited to the value range of 01.01.1970 to 31.12.2037. | ||||
Object access level ✳ |
|
| ||
|---|---|---|---|---|
"Object access level" defines the instance-specific object access level. "Object access level" is used for generic filtering and processing an object by a client application.
| ||||
Access level | Name | Description | ||
7 | Basic operation | Access to BACnet objects and properties for a room user e.g. data points visible on a room unit. | ||
6 | Standard operation | Access to BACnet objects and properties for standard operation and monitoring (daily business), .e.g. room and plant information on a management station. | ||
5 | Extended operation | Access to BACnet objects and properties for extended operation and monitoring such as network and device objects. All I/Os are visible | ||
4 | Administrator | Not used by HQ solutions yet. | ||
3 | Basic service | Access to BACnet objects and properties used for commissioning, e.g. configuration value extensions, I/O extensions, etc. | ||
2 | Extended service | Not used by HQ solutions yet. | ||
1 | Internal | Access to all BACnet objects and properties for very specialized actions e.g. during development. | ||
Object usage ✳ |
|
|
|---|---|---|
"Object usage" indicates whether the object is used or unused. The "Object usage" property can hide or display respective objects and their functionality in a client. For example, room functionality can be marked for flexible room arrangements as used/unused. An object that is marked as unused behaves as if the object does not exist. | ||
Property ID: 4930 | ||
Object identifier |
|
|
|---|---|---|
"Object identifier" is a numeric code that is used to identify the object. It must be unique internetwork-wide. | ||
Object name |
|
|
|---|---|---|
"Object name" represents a name for the object that is unique internetwork-wide. The minimum length of the string is one character. The set of characters used in the "Object name" are restricted to printable characters. | ||
Description |
|
|
|---|---|---|
"Description" is a string of printable characters whose content is not restricted. | ||
Object type |
|
|
|---|---|---|
"Object type " indicates membership in a particular object type class. E.g. "Analog input", "Binary output", "Event enrollment", "Trend log", etc. | ||
Building automation profile ✳ |
|
|
|---|---|---|
"Building automation profile" is an enumeration that indicates a particular type of Siemens proprietary object. Siemens objects are based on standard BACnet objects. For example, Siemens Analog Input, Analog Output, Analog Calculated Value, and Analog Configuration Value are based on standard Analog Input, Analog Output, and Analog Value BACnet objects. | ||
Profile name |
|
|
|---|---|---|
"Profile name" indicates the name of an object profile to which this object conforms. To ensure uniqueness, a profile name must begin with a vendor identifier code followed by a dash. All subsequent characters are administered by the organization registered with that vendor identifier code. The vendor identifier code that prefixes the profile name indicates the organization that publishes and maintains the profile document named by the remainder of the profile name. | ||
Comment |
|---|
A string of printable characters whose content is not restricted. (property is only used in ABT Pro) |
Version |
|---|
Version of a copied object (copied from a library). (property is only used in ABT Pro) |
Library reference |
|---|
Source of a copied object (copied from a library). (property is only used in ABT Pro) |
BACnetListOfBACnetCalendarEntry
BACnetCalendarEntry
BACnetCalendarEntry
SingleDate