Network port for IP (NwkPortIP)
Visible only Online
Network number ✳ |
|
| |
|---|---|---|---|
"Network number" indicates the BACnet network number associated with this network. | |||
0 | The number is not known or cannot be determined. Default value | ||
0..65534 | Value range | ||
UDP port ✳ |
|
|
|---|---|---|
"UDP port" indicates the UDP port number used for IP-subnet-local group communication. Local-Group-Communication-UDP-Port will be used to limit the group communication broadcast domain to an IP-subnet if BA-Group-Manager and all BA-Group-Member-Objects are connected on the same IP-Subnet and include the same Local-Group-Communication-UDP-Port. This optimization typically allows supersedeing global broadcasts for room segment grouping. If this property is modified, the property Changes-Pending will be set to true. The new value of Local-Group-Communication-UDP-Port will be activated when a value of activate is written to the property Command. | ||
IP address ✳ |
|
|
|---|---|---|
"IP address" indicates the IP address of this network port. If BACnet-DHCP-Enable is true, BACnet-IP-Address may not be online modified If this property is modified, the property Changes-Pending will be set to true. The new value of BACnet-IP-Address will be activated when a value of activate is written to the property Command. | ||
IP subnet mask ✳ |
|
|
|---|---|---|
"IP subnet mask" indicates the subnet mask for this network. If BACnet-DHCP-Enable is true, BACnet-IP-Subnet-Mask may not be online modified. If this property is modified, the property Changes-Pending will be set to true. The new value of BACnet-IP-Subnet-Mask will be activated when a value of activate is written to the property Command. | ||
IP default gateway ✳ |
|
|
|---|---|---|
"IP default gateway" indicates the default IP gateway. If BACnet-DHCP-Enable is true, BACnet-IP-Default-Gateway may not be online modified. If this property is modified, the property Changes-Pending will be set to true. The new value of BACnet-IP-Default-Gateway will be activated when a value of activate is written to the property Command. | ||
Enable (IP) DHCP ✳ |
|
|
|---|---|---|
"Enable (IP) DHCP" property indicates whether or not this network is configured via DHCP. If this property is modified, the property Changes-Pending will be set to true. The new value of BACnet-IP-DHCP-Enable will be activated when a value of activate is written to the property Command. | ||
Device instance number ✳ |
|
|
|---|---|---|
"Device instance number" indicates the Instance Number of the Object-Identifier of the BA-Device-Object. If this property is modified, the property Changes-Pending will be set to true. The new value of Instance-Number will be used as object instance number of the Object-Identifier of the BA-Device-Object when a value of activate is written to the property Command. | ||
Device name ✳ |
|
|
|---|---|---|
"Device name" indicates the Object-Name of the BA-Device-Object. If this property is modified, the property Changes-Pending will be set to true. The new value of Device-Name will be used as Object-Name of the BA-Device-Object when a value of activate is written to the property Command. | ||
Command ✳ |
|
| |
|---|---|---|---|
"Command" property allows triggering various actions to be performed by the network port object. A new command may only be written if the value of property Command is idle. | |||
Command | Function | ||
idle | Default value. An error will be returned. | ||
activate | The current configuration property settings will be activated. A new Command activate may only be written if the value of property Command is idle. The property value remains active until the activation is finished or fails. If the property Changes-Pending is false, the property Command will be set to idle. If activation of the settings succeeds, the property Changes-Pending will be set to false and the property Command will be set to idle. If activation of the settings fails, the property Reliability will be set to ACTIVATE-FAILURE. The property Changes-Pending will remain true, and the property Command will be set to idle. If the device cannot perform the activation without a reinitialization of the entire device, then it will reinitialize itself when running the command activate. | ||
discard-changes | The modified configuration property settings will be discarded. A new Command discard-changes may only be written if the value of property Command is idle. The modified properties will revert to the set of property values that were contained when Changes-Pending was first set to true. The property Changes-Pending will be set to false, and the property Command will be set to idle. | ||
restart-port | The device will be reinitialized to restart and reconnect to the network. A new Command restart may only be written if the value of property Command is idle. The property Changes-Pending will be set to false, and the property Command will be set to idle. | ||
State flag ✳ |
|
|
|---|---|---|
"State flag" represents four boolean flags ("Out of service", "Overridden", "Fault", "In-Alarm") that indicate the general status of an object. | ||
Reliability |
|
|
|---|---|---|
'Reliability' indicates whether the property value 'Present value' is reliable. If the 'Present value' is not reliable, the property 'Reliability' indicates the cause of the fault and the bit "Fault" of the state indication is set to 'True'. In a normal case, the property 'Reliability' is set to "No fault". | ||
Property ID: 103 | ||
Object access level ✳ |
|
| ||
|---|---|---|---|---|
"Object access level" defines the instance-specific object access level. "Object access level" is used for generic filtering and processing an object by a client application.
| ||||
Access level | Name | Description | ||
7 | Basic operation | Access to BACnet objects and properties for a room user e.g. data points visible on a room unit. | ||
6 | Standard operation | Access to BACnet objects and properties for standard operation and monitoring (daily business), .e.g. room and plant information on a management station. | ||
5 | Extended operation | Access to BACnet objects and properties for extended operation and monitoring such as network and device objects. All I/Os are visible | ||
4 | Administrator | Not used by HQ solutions yet. | ||
3 | Basic service | Access to BACnet objects and properties used for commissioning, e.g. configuration value extensions, I/O extensions, etc. | ||
2 | Extended service | Not used by HQ solutions yet. | ||
1 | Internal | Access to all BACnet objects and properties for very specialized actions e.g. during development. | ||
Object usage ✳ |
|
|
|---|---|---|
"Object usage" indicates whether the object is used or unused. The "Object usage" property can hide or display respective objects and their functionality in a client. For example, room functionality can be marked for flexible room arrangements as used/unused. An object that is marked as unused behaves as if the object does not exist. | ||
Property ID: 4930 | ||
Description |
|
|
|---|---|---|
"Description" is a string of printable characters whose content is not restricted. | ||
Object name |
|
|
|---|---|---|
"Object name" represents a name for the object that is unique internetwork-wide. The minimum length of the string is one character. The set of characters used in the "Object name" are restricted to printable characters. | ||
Comment |
|
|
|---|---|---|
A string of printable characters whose content is not restricted. | ||