Heating / Cooling coil 4-pipe, 6-way valve, two analog outputs via PL-Link (HCcl4Pipe15)

This application function operates over KNX PL-Link a 6-way control valve that is supplied with hot or chilled water from separate heating and cooling systems.

The valve position is calculated based on request signals (from the room controllers) received for heating and cooling.

 

Required elements and how to configure them:

Element

I/O

Signal type

HCclVlvPos "Heating/cooling coil valve position"

KNX PL-Link device, Heating/cooling coil valve position

GDB111.9E/KN

Function

The figure below shows BACnet objects associated with this application function. Primary signal flow is summarized as follows:

H/C coil heating or cooling request (HCclHReq / HCclCReq) is received and processed into the output signals for the H/C coil valve positions for heating and cooling (HCclVlvPosH / HCclVlvPosC).

Basic function: Accept request signal from associated room controller and pass it through a device mode logic switch; Output the result as a command to the BACnet object that controls the device.

Command or request (or related)

Notification of condition or status, or availability

Device mode

Interlock (internal signal, not a BACnet object; see Interlocks section for additional information)

Interlocks

Room automation interlocks are internal signals that coordinate interaction between HVAC devices. They are not visible in ABT Site or web interface, but parameters associated with them are. See comment column for hints on parameters that affect interlock functionality.

Signal

Type

Direction

Description

Comment

AirFlCReq

Boolean

Out

Air flow cooling request
▶ Initiates air flow (fan turns on or VAV damper provides air flow) to satisfy air flow support request for cooling. Signal is sent to fan or VAV supply damper depending on application.

See Configuration section for parameters named "...AirFlCReq".

AirFlHReq

Boolean

Out

Air flow heating request
▶ Initiates air flow (fan turns on or VAV damper provides air flow) to satisfy air flow support request for heating. Signal is sent to fan or VAV supply damper depending on application.

See Configuration section for parameters named "...AirFlHReq".

AirFlSta

Boolean

In

Air flow status
▶ Interlock signal, from a fan or a supply damper, that keeps the coil locked at equipment protection priority (PrPrio = 5) unless that same fan or supply damper provides air flow. (not active unless EnMonAirFlSta = Yes)

Parameter EnMonAirFlSta must = Yes. See Configuration section for additional information.

Sequence

Hot/Chilled water valve modulation: In response to heating or cooling demand, this application function modulates the control valve(s) to control the room temperature at setpoint. In response to external triggers for special modes such as warm-up, cool down, or safety conditions, the control valve(s) may be set to off or fully open.

Note
This AF does not perform loop control; its main purpose is to run commands. Loop control processes (for this AF) are managed in the "room" AF(s) that collaborate with this AF to command the end device.

Device mode: The input signal for device mode is a multistate value.

HCclDevMod supports the following states:

Heating available status: When the H/C coil is available for heating, the binary output signal for "Heating/cooling coil available for heating " (HCclAvlH) will be "Yes" (available). HCclAvlH is used by the system to regulate heating resources. For example, if there is a call for heating but the H/C coil is not available because it is already at maximum capacity (because device mode is fully open), then HCclAvlH will signal "No" and the next available heating resource in the temperature control sequence will be activated.

For heating available status to be "Yes", device mode must equal "Control mode" (modulation).

Cooling available status: When the H/C coil is available for cooling, the binary output signal for "Heating/cooling coil available for cooling" (HCclAvlC) will be "Yes" (available). HCclAvlC is used by the system to regulate cooling resources. For example, if there is a call for cooling but the H/C coil is not available because it is already at maximum capacity (because device mode is fully open), then HCclAvlC will signal "No" and the next available cooling resource in the temperature control sequence will be activated.

For cooling available status to be "Yes", device mode must equal "Control mode" (modulation).

 

Supply chain interface outputs

HCclHwDmd supports the following states:

HCclChwDmd supports the following states:

Free cooling can be initiated by the central plant when surplus cooling capacity is available. Under certain conditions, the room can take advantage of surplus cooling capacity in the absence of an explicit cooling demand; the room temperature must be below the setpoint associated with the current room climate mode (Comfort, Pre-Comfort etc.). This type of free cooling is different from "economizer" free cooling, which uses an outside air damper.

 

Supply chain interface inputs

The input signals for hot water availability / chilled water availability are binary values [No|Yes] determined by central command. They are commanded via supply chain group communication for the purpose of TOa-dependent device lockout. The relinquish default value for each is Yes.

HCclHwAvl: If the outside air temperature is above the hi limit value, HCclHwAvl is set to No and the heating valve is closed. (see Central AF SplyHwxx for additional information)

HCclChwAvl: If the outside air temperature is below the low limit value, HCclChwAvl is set to No and the cooling valve is closed. (see Central AF SplyChwxx for additional information)

If for some reason HCclHwAvl and HCclChwAvl are both "No", then device mode (HCclDevMod) is set to Off at priority 9.

 

The following figure(s) illustrates control modulation and related functions.

 

 

 

 

Configuration

Parameters

Description

Parameter

Default value

Manual control mode
▶ Configured during commissioning of system to define the control mode provided by the heating/cooling coil:

1:Auto
2:Heating
3:Cooling

CtlModMan

1:Auto

Interlocks

Switch-on point for air volume flow cooling request
▶ When the cooling coil cooling request (in percent) is above this value, the air volume flow cooling request goes to True.

SwiOnAirFlCReq

4 [%]

Hysteresis for air volume flow cooling request
▶ When the cooling coil cooling request (in percent) is below this value, the air volume flow cooling request goes to False.

HysAirFlCReq

2 [%]

Switch-on delay for air volume flow cooling request
▶ The time after the switch-on point for air volume flow cooling request is True that air volume flow cooling request goes from False to True.

DlyOnAirFlCReq

30 [s]

Switch-on point for air volume flow heating request
▶ When the heating coil heating request (in percent) is above this value, the air volume flow heating request goes to True.

SwiOnAirFlHReq

4 [%]

Hysteresis for air volume flow heating request
▶ When the heating coil heat request (in percent) is below this value, the air volume flow heating request goes to False.

HysAirFlHReq

2 [%]

Switch-on delay for air volume flow heating request
▶ The time after the switch-on point for air volume flow heating request is True that air volume flow heating request goes from False to True.

DlyOnAirFlHReq

30 [s]

Enable monitoring for air volume flow state
▶ Enable monitoring of the fan interlock signal (from fan) that keeps the heating/cooling coil closed unless the fan is running.

0:No
1:Yes

EnMonAirFlSta

0:No

Hot/chilled water demand

Switch-on point for chilled water demand
▶ When the cooling coil valve position is greater than the switch-on point, the cooling coil enables request chilled water for cooling.

SwiOnPtChwDmd

4 [%]

Hysteresis for chilled water demand
▶ When the cooling coil valve position is less than the hysteresis value, the cooling coil disables request chilled water for cooling.

HysChwDmd

2 [%]

Switch-on point for hot water demand
▶ When the heating coil valve position is greater than the switch-on point, the heating coil enables request hot water for heating.

SwiOnPtHwDmd

4 [%]

Hysteresis for hot water demand
▶ When the heating coil valve position is less than the hysteresis value, the heating coil disables request hot water for heating.

HysHwDmd

2 [%]

Interface

Interface

Description

Type

Ref.

Owned by

HCclVlvPosC

Heating/cooling coil valve position for cooling

AO

Room segment / Device

HCclVlvPosH

Heating/cooling coil valve position for heating

AO

Room segment / Device

HCclDevMod

Heating/cooling coil device mode

1:Off
2:Control mode
3:Fully open, heating
4:Fully open, cooling

MPrcVal

-

HCclCReq

Heating/cooling coil cooling request

ACalcVal

-

HCclHReq

Heating/cooling coil heating request

ACalcVal

-

HCclAvlC

Heating/cooling coil available for cooling

0:No
1:Yes

BCalcVal

-

HCclAvlH

Heating/cooling coil available for heating

0:No
1:Yes

BCalcVal

-

HCclChwDmd

Heating/cooling coil chilled water demand

1:Off
2:Cooling demand
3:Free cooling

MCalcVal

-

HCclHwDmd

Heating/cooling coil hot water demand

1:Off
2:Heating demand
3:Warm-up

MCalcVal

-

HCclChwAvl

Heating/cooling coil chilled water available

0:No
1:Yes

BPrcVal

-

HCclHwAvl

Heating/cooling coil hot water available

0:No
1:Yes

BPrcVal

-

HCclSplyChw

Heating/cooling coil supply chain for chilled water

GrpMbr

Room segment

HCclSplyHw

Heating/cooling coil supply chain for hot water

GrpMbr

Room segment

Engineering and commissioning

The H/C coil must be configured to provide one of the following conditions: Automatic (provides both heating and cooling), Heating, or Cooling. This is done using parameter CtlModMan.