Binary inputs
This section describes binary input objects (BI) for specific CET applications.
For the description of properties see chapter "TX-I/O modules" in the Hardware catalog.
List of specific I/Os
This list contains the specific CET binary input objects in the library.
Data point | Description |
|---|---|
BI_AirFlDet_None_NC | Binary input for air flow detection, normally closed |
BI_DoorContR_None_NC | Binary input for room door contact, normally closed |
BI_FhFireDet_None_NC | Binary input for fume hood fire detector, normally closed |
BI_FhPscDet_Switch on/off delay_NO | Binary input for fume hood presence detector, normally open |
BI_FhRemEmgPrg_None_NC | Binary input for fume hood remote emergency purge switch, normally closed |
BI_FhSashAlrtSwi_None_NC | Binary input for fume hood sash alert switch, normally closed |
BI_FhSashSwi_None_NC | Binary input for fume hood sash switch, normally closed |
BI_FhStbJetFanSta_None_NO | Binary input for fume hood stabilizing jet fan state, normally open |
BI_HuHiDctDet_None_NC | Binary input for High duct humidity detector, normally closed |
BI_HumFlt_None_NC | Binary input for humidifier fault, normally closed |