Airflow limits for critical spaces
Supply Air Flow Limits for Air Terminals - Configuration
The Supply Air Flow serves multiple functions: heating, cooling, ventilation, and pressurization. The following section explains how to configure each supply terminal for different use cases.
Cooling | Heating | Ventilation | |
Single CV (Constant Volume) Supply Terminal | Min = Max = 0 (or minimum flow value needed for the coil to cool the room) | Min = Max = 0 (or minimum flow value needed for the coil to heat the room) | Min = 0 |
Single VAV (Variable Air Volume) Supply Terminal (no fume hood) | Min = 0 (or minimum flow value needed for the coil to cool the room) | Min = 0 (or minimum flow value needed for the coil to heat the room) | Min = 0 |
Single VAV Supply Terminal (fume hood) | Min = 0 (or minimum flow value needed for the coil to cool the room) | Min = 0 (or minimum flow value needed for the coil to heat the room) | Min Ventilation = 0 |
Check the project specification to see if the various terminals are to be sequenced differently from each other: if they respond to different needs. If no difference is specified, follow the next table's instruction. If the flow limits are set the same for each terminal, then they run at equal flows.
Cooling | Heating | Ventilation | |
Multiple Supply Terminals (same size, same function) | Min = 0 (or minimum flow value needed for the coil to cool the room) | Min = 0 (or minimum flow value needed for the coil to heat the room) | Min = 0 |
Check the project specification to see if the various terminals are to be sequenced differently from each other: if they respond to different needs. If the supply terminals are different sizes but have the same function, follow the next table's instruction.
Cooling | Heating | Ventilation | |
Multiple Supply Terminals (different sizes, same function) | Min = 0 (or minimum flow value needed for the coil to cool the room) | Min = 0 (or minimum flow value needed for the coil to heat the room) | Min = 0 |
In the case of multiple supply terminals with different functions, the following tables provide an example of how to configure one CV (Constant Volume) Terminal serving a chilled beam, and one VAV (Variable Air Volume) Terminal without cooling.
Flow through the CV Terminal does not vary to heat or cool.
Flow is always set by ventilation or support for coil (minimum heat or minimum cooling) unless reducing it is the only way to maintain room pressurization.
Flow through the VAV Terminal may vary for heating, cooling, and ventilation, or to balance fume hood flow.
Cooling | Heating | Ventilation | |
Multiple Supply Terminals (different functions) | Min = Max = 0 (or minimum flow value needed for the coil to cool the room) | Min = Max = 0 (or minimum flow value needed for the coil to heat the room) | Min = Max = 0 (or value needed to support a heating or cooling coil) |
Multiple Supply Terminals (different function) | Min = 0 (or minimum flow value needed for the coil to cool the room) | Min = 0 (or minimum flow value needed for the coil to heat the room) | Min = 0 |