Sash calibration and verification

Sash calibration

The full travel of the sash must be used during calibration.

(Web interface Room segment/HVAC/Fume hood sash/Fume hood sash 1 position/properties)

  1. Set ‘Process value 1’ and ‘Signal value 1’ = 0. Set ‘Process value 2’ and ‘Signal value 2’ = 10,000.
  2. Fully close the sash.
  3. Record the reading of ‘Present value’ as SV1.
  4. Measure the distance from the bottom of the sash opening to the bottom of the sash in inches (cm). Record as PV1. Should be at or very near 0.
  5. Raise sash to maximum height.
  6. Record the reading of ‘Present value’ as SV2.
  7. Measure the distance from the bottom of the sash opening to the bottom of the sash in inches (cm). Record as as PV2.
  8. Set ‘Process value 1’ = PV1, ‘Signal value 1’ = SV1, ‘Process value 2’ = PV2, ‘Signal Value 2’ = SV2.

Sash calibration verification

(Web interface Room segment/HVAC/Fume hood sash)