Air volume flow tracking, pressure dependent (AirFlTck12)

Overview

The application function "Air volume flow tracking 12, pressure-dependent control" (AirFlTck12) collaborates / is used only with pressure dependent VAV supply and extract air terminal boxes to calculate the VAV extract air damper position setpoint.

Function

Room pressurization mode
The VAV extract air damper position setpoint depends on the setting of PRMode (Room pressurization mode). PRMode can be set for Neutral, Positive, or Negative room pressure.

Damper position for transferred air
DmpPosTrnAir (Damper position for transferred air) equals the difference, in absolute value, between the supply and extract damper positions needed to maintain room pressurization. It represents the amount of air that enters (infiltration) or exits (exfiltration) a pressurized room through cracks or small openings. In a pressurized room, the extract damper position setpoint differs from supply damper position by the value of DmpPosTrnAir.

Example:

DmpPosTrnAir is a positive number regardless of PRMode value.

Configuration

Parameters

Description

Parameter

Default value

Room pressurization mode

1:Neutral
2:Positive pressure
3:Negative pressure

PRMod

1:Neutral

Damper position for transferred air
▶ The equivalent damper position for the amount of air that enters (infiltration) or exits (exfiltration) a pressurized room through cracks or small openings.

DmpPosTrnAir

10 [%]

Interface

Interface

Description

Type

Ref.

Owned by

DmpPosSuR

Supply air damper position room

ACalcVal

-

PrSpDmpPosEx

Present setpoint extract air damper position

ACalcVal

-

RCtl

Room control

GrpMaster

Room

Engineering and commissioning