Supply air VAV box, dual-duct, pressure sensor (VavSuDuald11)

This application function operates 2 dampers in a dual duct box, using 2 internal air volume flow controllers to drive the measured air volume flows to their air volume flow setpoints.

To calculate air volume flow in each duct, this AF uses a duct area calculation and input from a differential pressure sensor.

The air volume flow setpoint is calculated based on request signals (from the room controllers) received for heating, cooling and ventilation.

There is an optional collection input for condensation detection at chilled beam(s) or chilled ceiling(s).

Functions to support air balancing are included.

Which duct is for hot and which is for cold air and which duct is connected to supply fresh air for ventilation can be selected. (Typically, Duct 1 is for cold and Duct 2 is for hot air and both can be used for ventilation). Supported are Mixing control or snap acting control as well. taking air from an outdoor system (DOAS)

Required elements and how to configure them:

Element

I/O

Signal type

VavSuDiffP1 "Supply air VAV differential pressure 1"

On-board input, Supply air VAV differential pressure 1

0…10V or P1

VavSuDiffP2 "Supply air VAV differential pressure 2"

On-board input, Supply air VAV differential pressure 2

0…10V or P1

VavSuPos1 "Supply air VAV position 1" and VavSuPos2 "Supply air VAV position 2"

On-board output, Setpoint for supply air VAV position

Dual-duct 0…10V or 3-position

or KNX PL-Link device, Supply air VAV

Dual-duct Position control

Function

The figure below shows BACnet objects associated with this application function. Primary signal flow is summarized as follows:
VAV supply heating, cooling, or ventilation request (VavSuHReq / VavSuCReq / VavSuVntReq) is received and processed into 2 output signals for VAV supply damper positions (VavSuPos1, VavSuPos2).

Basic function: Accept request signal from associated room controller and map it to appropriate air volume flow limits; Calculate the setpoint for each supply duct and compare to air volume flow in each supply duct; Pass result through a device mode logic switch for each duct prior to outputting as a command to the object that controls the device.

Command or request (or related)

Notification of condition or status, or availability

Device mode

Interlock (internal signal, not a BACnet object; see Interlocks section for additional information)

Interlocks

Room automation interlocks are internal signals that coordinate interaction between HVAC devices. They are not visible in ABT Site or web interface, but parameters associated with them are. See comment column for hints on parameters that affect interlock functionality.

Signal

Type

Direction

Description

Comment

AirFlCReq

Boolean

In

Air flow cooling request
▶ Initiates air flow (damper opens) to satisfy air flow support request from cooling coil.

 

AirFlHReq

Boolean

In

Air flow heating request
▶ Initiates air flow (damper opens) to satisfy air flow support request from heating coil.

 

AirFlHldH

Boolean

In

Air flow hold for heating
▶ Interlock signal from electric heating coil indicating the coil needs equipment protection air flow support. The damper is prevented from closing for a period of time.

 

AirFlSta

Boolean

Out

Air flow status
▶ Interlock signal that keeps the coil locked at equipment protection priority (PrPrio = 5) unless the supply damper provides air flow.

See Configuration section for parameters named "...AirFlSta"

AirFlVavReq

%

Out

Air flow vav request
▶ In a fan-powered box (FPB) application, the VAV damper sends a proportional analog request signal (AirFlVavReq) requesting air flow, so that the box can meet an air flow support or ventilation demand.

Fan-powered box application.

FanSta

Boolean

In

Fan state
▶ Interlock signal used in series fan-powered box applications: FanSta must be True (fan is running) before damper is allowed to open. This ensures that air flow from the damper does not rotate the series fan while at rest.

In series fan-powered box applications, parameter EnMonFanSta must = Yes. See Configuration section for additional information.

Air flow control loop

The two PID air flow controllers (VavSuAirFlCtr1, VavSuAirFlCtr2) compare the air volume flows of Duct 1 and Duct 2 to their respective VAV supply air flow setpoints. VavSuPos1 and VavSuPos2 are then modulated as necessary to keep the duct flows at their setpoints.

Air flow setpoint selection: When device mode is set to Control mode (VavSuDevMod = 2), the loops work independently, but the flow setpoints are coordinated to satisfy one or more of the following air flow demand values, as required by conditions during runtime:

(In some circumstances a dual duct flow setpoint may be set in response to a terminal heating or cooling coil air flow support request.)

Each duct is assigned to ignore or respond to a heating, cooling, or ventilation flow demand; the assignment depends on configuration settings (see "Dual duct VAV configurations" below).

Flow demand signals VavSuHReq, VavSuCReq, and VavSuVntReq (heat, cool, vent) are in percent. Each signal is mapped to a flow rate in physical air flow units, with flow limits set individually for each function (heat, cool, vent). The mapping from percent to physical air flow units includes a step-up at the low end: switch-on point of 4% with 2% hysteresis; the request signal must rise above 4% before its corresponding air flow value rises from 0 to the request’s minimum air flow.

From the three air flow demands assigned to a duct (heating, cooling, or ventilation), the application selects the largest one as the current air flow setpoint. Note that the "largest" flow demand is not based solely on its initial percent value, see example.

Example:

 

Current flow demands and parameter settings, along with the dynamic status of current changeover conditions (VavSuChovrCnd1, VavSuChovrCnd2) result in a variety of scenarios for overall behavior. Users configure changeover signals for each duct to indicate suitability for heating or cooling. In most cases, one duct has cool air and the other duct has hot air, and they don’t change. In less common systems the heating/cooling state of a duct can change dynamically, such that both ducts can be cold, or both can be hot. As one example, both ducts might be able to deliver cold air based on cooling demand: if cooling demand is 100%, each duct delivers its maximum cooling flow.

 

Device mode: The input signal for device mode is a multistate value.

VavSuDevMod supports the following states:

Device mode

Duct 1

Duct 2

1:Off

Setpoint is zero

Setpoint is zero

2:Control mode

Follows demand

Follows demand

3:Max.air vol.flow

Select from h/c maximum according to VavSuChovrCnd1:
- Neither (Vent max)
- Cooling (Cooling max)
- Heating (Heating max)
- Neutral (max of Cooling max and Heating max)

Select from h/c maximum according to VavSuChovrCnd2:
- Neither (Vent max)
- Cooling (Cooling max)
- Heating (Heating max)
- Neutral (max of Cooling max and Heating max)

4:Min.air vol.flow

Select from h/c minimum according to VavSuChovrCnd1:
- Neither (Vent min)
- Cooling (Cooling min)
- Heating (Heating min)
- Neutral (max of Cooling min and Heating min)

Select from h/c minimum according to VavSuChovrCnd2:
- Neither (Vent min)
- Cooling (Cooling min)
- Heating (Heating min)
- Neutral (max of Cooling min and Heating min)

5:Smoke ctrl.air flow setp

Setpoint is smoke value
(common setpoint for both ducts)

Setpoint is smoke value
(common setpoint for both ducts)

 

Saturation signal: The saturation signal (VavSuAflStrtn) is a binary object that is True ("Starved") when the air flow control loop cannot get enough air to reach setpoint for a time exceeding a built-in time delay. After the delay expires, open loop operation begins.

Note
Saturation signal is always off if parameter EnStrtnCal = 0 (No). This allows the user to exclude a particular terminal from the saturation pressure reset system.

 

Air flow deviation signal: The supply air flow deviation (VavSuAirFlDvn) signal (in percent) is used for fan speed (static pressure) reset strategies at the air handling unit. It is obtained by measuring the supply air flows (Duct 1, Duct 2) and comparing to the respective air flow setpoints.

VavSuAirFlDvn = VavSuSpAflRel minus VavSuAirFlRel

VavSuAirFlDvn will equal 0 in case of invalid conditions (i.e., invalid state of related BACnet objects).

 

Relief input signal: A VAV box’s binary air flow relief object (VavSuAirFlRlf) can be set to True by the air handling unit. This is done to relieve flow resistance in the duct system in order to maintain proper static pressure. The VAV controller responds by increasing its air flow setpoint (VavSuSpAirFl).

When device mode = control mode and both EnRlf (Enable relief) and VavSuAirFlRlf equal On, VavSuSpAirFl will be set to the maximum of either its current value or the parameter AirFlRlf (i.e., AirFlRlf1 or AirFlRlf2).

Note
Relief has no effect on the supply chain VAV air demand signal VavSuAirDmd.

 

Available status: When a VAV supply damper (Duct 1 or Duct 2) is available for heating or cooling or ventilation, the respective binary output signals that indicate availability (VavSuAvlH, VavSuAvlC, VavSuAvlVnt) will be "Yes" (available). The signals are calculated for each duct, or they may be calculated together as the "available" signal for the dual duct terminal. Note: In this AF, available signals do not respond to the activity of a heating coil or a cooling coil.

For available status to be "Yes", device mode must equal "Control mode" (modulation) and the Supply air VAV changeover condition object for the applicable duct (VavSuChovrCnd1 or VavSuChovrCn2) must not equal "Neither".

 

Ventilation available signal: The output signal VavSuAflPvdVnt (VAV supply air flow provided for ventilation) is the amount of air flow available for ventilation. When VavSuAvlVnt is True, a maximum value (VavSuAflMaxVnt) is transferred to VavSuAflPvdVnt. VavSuAflPvdVnt is the sum of maximal flow (in engineering units) from the dual duct box(es). (Value(s) are set in each box to total the maximum flow in the segment.)

Minimum ventilation flow

info

See the room level ventilation control AF (VavVntCtl.xx) for detailed information on configuring minimum ventilation levels for each occupancy mode. Note that the configured min. vent flow value can effectively replace the minimum cooling flow and minimum heating flow values.

 

Flow sensor failure: (Duct 1 and Duct 2 are same functionality) If the air flow sensor object is invalid, then open loop operation begins. In open loop operation, damper position is controlled without using the measured air volume flow value from the sensor; instead, damper position = air flow setpoint in % of nominal air flow (largest configured max flow setting).

The DXR can also be configured to interpret low flow as a failed sensor. Parameter EnMonNoAirFl (Enable monitoring for no air volume flow) enables/disables this function. By default it is disabled.

Air balancing

Air balance functions for Dual duct follow the pattern of other VAV applications. For Dual duct, the functions are implemented twice, once for each duct. Functions include:

Each duct has a balancing mode object. Users can command both ducts to perform balancing tasks. For example, command Duct 1 balancing mode to max cooling and command Duct 2 balancing mode to min heating.

 

Air flow tracking signal: For rooms with a controlled exhaust terminal, the AF generates a signal representing Duct 1 and Duct 2 total measured air flow, or Duct 1 and Duct 2 total flow setpoint. The selection depends on the configured flow tracking method (flow or flow setpoint). The signal is used in the air flow tracking calculations.

VAV Dual duct configurations

Note
Default settings assign Duct 1 as cold duct and Duct 2 as hot duct, but these assignments are configurable / reversible if desired or required. The following examples use the default assignments for cold duct and hot duct (use case 4 is special case, see below).

 

Use case 1: VAV DD - Ventilation source in one duct

Use case 2: VAV DD - Ventilation in both ducts, with mixing control

Use case 3: VAV DD - Ventilation in both ducts, snap acting control

Use case 4: VAV DD - Dedicated duct for ventilation from DOAS (dedicated outside air system)

Use case 5: Constant volume DD option - Ventilation in both ducts, with mixing control

 

Main objects / parameters for dual duct use case configurations:

Name

Description

Available settings

VavSuChovrCnd1

Supply air VAV changeover condition 1
▶ Changeover object for Duct 1

1:Neither
2:Heating
3:Cooling (default)
4:Neutral

VavSuChovrCnd2

Supply air VAV changeover condition 2
▶ Changeover object for Duct 2

1:Neither
2:Heating (default)
3:Cooling
4:Neutral

VntDuctSprt

Duct supporting ventilation
▶ Parameter that defines which duct(s) provide(s) ventilation air flow

1:No ventilation
2:Duct 1
3:Duct 2
4:Both ducts

CtlStrgy

Control strategy
▶ Parameter that defines whether mixing control is supported by the dual duct configuration

1:Snap acting control
2:Mixing control

VntSprtDdband

Ventilation support in dead band
▶ Parameter that defines how ventilation is provided during temperature deadband

1:Duct 1
2:Duct 2
3:Last duct

 

Color legend for graphics:

Use case 1: VAV DD - Ventilation source in one duct

In use case 1 configurations, the mechanical equipment consists of a multiple fan AHU with separate elements for heating and cooling air distribution. The hot and cold air streams are drawn from different sources and driven by separate fans. Outside air ventilation is provided in either the hot duct or the cold duct, not both.

 

Use Case 1a – VAV DD with ventilation in cold duct only (Duct 1):

 

Cold duct does not close if ventilation requirement remains constant.

 

Cold duct may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 1a:

1) CtlStrgy and VntSprtDdband are ignored when VntDuctSprt does not equal "Both ducts".

 

In use case 1a, when the thermal load is in deadband the cold duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the hot duct air flow will be zero.

On an increase in cooling load, the cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Cold duct air flow will be the greater of vent demand and cooling demand. Hot duct air flow will be zero.

On an increase in heating load, the heating flow demand on the hot duct modulates from heating flow min to heating flow max. Cold duct air flow will be the current value of ventilation flow demand. The total air flow during heating will be the sum of the ventilation air (from the cold duct) and the modulating heating flow.

 

Use Case 1b – VAV DD with ventilation in hot duct only (Duct 2):

 

Hot duct does not close if ventilation requirement remains constant.

 

Hot duct may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 1b:

1) CtlStrgy and VntSprtDdband are ignored when VntDuctSprt does not equal "Both ducts".

 

In use case 1b, when the thermal load is in deadband the hot duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the cold duct air flow will be zero.

On an increase in heating load, the heating flow demand on the hot duct modulates from heating flow min to heating flow max. Hot duct air flow will be the greater of vent demand and heating demand. Cold duct air flow will be zero.

On an increase in cooling load, the cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Hot duct air flow will be the current value of ventilation flow demand. The total air flow during cooling will be the sum of the ventilation air (from the hot duct) and the modulating cooling flow.

Use case 2: VAV DD - Ventilation in both ducts, with mixing control

In use case 2 configurations, the mechanical equipment consists typically of a single fan AHU with separate elements for heating and cooling air distribution. The hot and cold air streams are drawn from the same source(s) and driven by the same fan. Outside air ventilation is provided using both ducts.

Ventilation in deadband – When ventilation is provided in both ducts, different possibilities exist for ventilation in deadband: cold duct (Duct 1), hot duct (Duct 2), and "Last duct". The dual duct can be configured according to the relative costs of providing hot air or cold air. For example, if it takes more energy to provide hot air, then it makes sense to use cold air for ventilation in the deadband. If energy costs are approximately equal, then "last duct" configuration may be preferable.

Mixing control vs. Snap acting control – Some people associate mixing hot and cold air flows in the dual duct box with wasting energy. Others appreciate the gradual temperature modulation that comes with mixing. Snap action prevents the mixing of hot and cold air flows in the dual duct box. Select according to project specifications or end-user preference.

 

Use Case 2a – VAV DD with ventilation in both ducts, cold duct ventilation in deadband, with mixing control:

 

Cold duct will stay open in deadband to meet a ventilation requirement. As heating load ramps up, cold duct damper modulates to zero as hot duct damper modulates open (i.e., mixing control during ramp up of heating mode).

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 2a:

 

In use case 2a, with the thermal load in deadband the cold duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the hot duct air flow will be zero.

On an increase in cooling load, the cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Cold duct air flow will be the greater of vent demand and cooling demand. Hot duct air flow will be zero.

On an increase in heating load, the heating flow demand on the hot duct modulates from heating flow min to heating flow max. Cold duct air flow will be the value of the difference between hot duct air flow and the current ventilation flow demand, provided that the ventilation flow demand is greater than hot duct air flow, otherwise cold duct air flow will be zero.

 

Use Case 2b – VAV DD with ventilation in both ducts, hot duct ventilation in deadband, with mixing control:

 

Hot duct will stay open in deadband to meet a ventilation requirement. As cooling load ramps up, hot duct damper modulates to zero as cold duct damper modulates open (i.e., mixing control during ramp up of cooling mode).

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 2b:

 

In use case 2b, with the thermal load in deadband the hot duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the cold duct air flow will be zero.

On an increase in heating load, the heating flow demand on the hot duct modulates from heating flow min to heating flow max. Hot duct air flow will be the greater of vent demand and heating demand. Cold duct air flow will be zero.

On an increase in cooling load, the cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Hot duct air flow will be the value of the difference between cold duct air flow and the current value of ventilation flow demand, provided that the ventilation flow demand is greater than cold duct air flow, otherwise hot duct air flow will be zero.

 

Use Case 2c – VAV DD with ventilation in both ducts, last duct ventilation in deadband, with mixing control:

 

Last active duct will stay open in deadband to meet a ventilation requirement. Outside of deadband, as the heating load (or the cooling load) ramps up, the ducts provide a hot/cold mixture to meet the ventilation requirement. See additional information below.

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 2c:

 

In use case 2c, with the thermal load in deadband the air flow from the last active duct (heating or cooling) will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the inactive duct air flow will be zero.

 

If the last active duct = cold duct, then when the system exits the temperature deadband the behavior is as follows:

 

If the last active duct = hot duct, then when the system exits the temperature deadband the behavior is as follows:

Use case 3: VAV DD - Ventilation in both ducts, snap acting control

In use case 3 configurations, the mechanical equipment consists typically of a single fan AHU with separate elements for heating and cooling air distribution. The hot and cold air streams are drawn from the same source(s) and driven by the same fan. Outside air ventilation is provided using both ducts.

Ventilation in deadband – When ventilation is provided in both ducts, different possibilities exist for ventilation in deadband: cold duct (Duct 1), hot duct (Duct 2), and "Last duct". The dual duct can be configured according to the relative costs of providing hot air or cold air. For example, if it takes more energy to provide hot air, then it makes sense to use cold air for ventilation in the deadband. If energy costs are approximately equal, then "last duct" configuration may be preferable.

Mixing control vs. Snap acting control – Some people associate mixing hot and cold air flows in the dual duct box with wasting energy. Others appreciate the gradual temperature modulation that comes with mixing. Snap action prevents the mixing of hot and cold air flows in the dual duct box. Select according to project specifications or end-user preference.

 

Use Case 3a – VAV DD with ventilation in both ducts, cold duct ventilation in deadband, snap acting control:

 

Cold duct will stay open in deadband to meet ventilation requirement. On an exit to heating, the cold duct closes immediately and the hot duct takes over ventilation needs.

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 3a:

 

In use case 3a, with the thermal load in deadband the cold duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the hot duct air flow will be zero.

On an increase in cooling load, the cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Cold duct air flow will be the greater of vent demand and cooling demand. Hot duct air flow will be zero.

On an increase in heating load, the cold duct closes and the hot duct will open (snap action) to take over any active ventilation flow rate. Heating flow demand on the hot duct modulates from heating flow min to heating flow max. Hot duct air flow will be the greater of vent demand and heating demand. Cold duct air flow will be zero.

 

Use Case 3b – VAV DD with ventilation in both ducts, hot duct ventilation in deadband, snap acting control:

 

Hot duct will stay open in deadband to meet ventilation requirement. On an exit to cooling, the hot duct closes immediately and the cold duct takes over ventilation needs.

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 3b:

 

In use case 3b, with the thermal load in deadband the hot duct air flow will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the cold duct air flow will be zero.

On an increase in heating load, the heating flow demand on the hot duct modulates from heating flow min to heating flow max. Hot duct air flow will be the greater of vent demand and heating demand. Cold duct air flow will be zero.

On an increase in cooling load, the hot duct closes and the cold duct will open (snap action) to take over any active ventilation flow rate. Cooling flow demand on the cold duct modulates from cooling flow min to cooling flow max. Cold duct air flow will be the greater of vent demand and cooling demand. Hot duct air flow will be zero.

 

Use Case 3c – VAV DD with ventilation in both ducts, last duct ventilation in deadband, snap acting control:

 

Last active duct will stay open in deadband to meet ventilation requirement. For behavior outside of deadband see additional information below.

 

Ducts may close if ventilation requirement goes to zero.

 

Parameter configuration for use case 3c:

 

In use case 3c, with the thermal load in deadband the air flow from the last active duct will equal the current value of the ventilation flow demand (may vary per room operating mode or DCV); the inactive duct air flow will be zero.

 

If the last active duct = cold duct, then when the system exits the temperature deadband the behavior is as follows:

 

If the last active duct = hot duct, then when the system exits the temperature deadband the behavior is as follows:

Use Case 4: VAV DD - Dedicated duct for ventilation from DOAS (dedicated outside air system)

In use case 4 configurations, the mechanical equipment consists of a multiple fan AHU with DOAS, and separate elements (if present) for heating / cooling air distribution. When the thermal load is in deadband, air flow in the duct used for temperature control can be zero (Duct 1 in graphic).

 

Duct 1

 

Duct 2

 

Parameter configuration for use case 4:

1) CtlStrgy and VntSprtDdband are ignored when VntDuctSprt does not equal "Both ducts".

 

In use case 4, all ventilation is handled in Duct 2 by dedicated outside air system (DOAS). Minimum ventilation levels can be specified per room occupancy mode. When configured for DCV (demand control ventilation) an increase in ventilation flow is provided in response to room IAQ (CO2) setpoints configured per occupancy mode.

Temperature control is provided by Duct 1 and may include optional heating or cooling coils. On an increase in cooling load, Duct 1 will modulate from cooling flow min to cooling flow max. In heating mode, Duct 1 will provide air flow to support heating coil(s) from heating flow min to heating flow max.

Use Case 5: Constant volume DD option with ventilation in both ducts, with mixing control

In use case 5 configurations, the mechanical equipment consists typically of a single fan AHU with separate elements for heating and cooling air distribution. The hot and cold air streams are drawn from the same source(s) and driven by the same fan. Outside air ventilation is provided using both ducts.

To achieve the constant volume option, the minimum ventilation parameter(s) located in the room AF for ventilation control (VavVntCtl) are set equal or greater than the heating / cooling maximum flow setpoints (VavSuAirFlMaxC, VavSuAirFlMaxH). When this is done, the terminal provides constant air flow in the Comfort mode, and may be configured to reduce flow in other room operating modes.

In constant volume configurations, temperature control is maintained at a single setpoint, either heating or cooling, depending on the setting of parameter VntSprtDdband (Ventilation support in deadband). See following examples.

 

Use Case 5a – Constant volume DD option, ventilation in both ducts, mixing control, with cold duct ventilation in deadband

 

VntSprtDdband = Duct 1, example 1:

Cold duct stays at constant max volume during cooling and deadband to provide the elevated minimum ventilation setting.

At the heating setpoint, mixing control occurs to maintain constant volume dual duct air flow and room temperature control: as heating load ramps up, hot duct damper modulates open and cold duct damper modulates down.

Optional heat elements (e.g. hot water coil) can be configured to provide additional heating after the hot duct has reached maximum flow.

 

VntSprtDdband = Duct 1, example 2:

Cold duct stays at constant max volume during cooling and deadband with an additional level of supplemental ventilation air flow provided by hot duct. The air flows are summed to provide an elevated minimum ventilation setting larger than max cooling flow.

At the heating setpoint, mixing control occurs to maintain constant volume dual duct air flow and room temperature control: as heating load ramps up, hot duct damper modulates open and cold duct damper modulates down. When the total flow (ventilation setpoint) is larger than the max heating setpoint, the cold duct provides the additional supplemental ventilation air flow.

Optional heat elements (e.g. hot water coil) can be configured to provide additional heating after the hot duct has reached maximum flow.

Parameter configuration for use case 5a:

*In the room AF for ventilation control (VavVntCtl) set min vent parameter for Comfort mode (AirFlMinRCmf) to desired CV flow; the min vent setpoint object in VavSuDuald11 (VavSuAflMinVnt) can be set to zero when the minimum ventilation parameters are used for min vent settings.

Note that if minimum ventilation parameter is not set high (for example during Economy mode) constant volume is not provided:

 

Use Case 5b – Constant volume DD option, ventilation in both ducts, mixing control, and hot duct ventilation in deadband

 

VntSprtDdband = Duct 2, example 1:

Hot duct stays at constant max volume during heating and deadband to provide the elevated minimum ventilation setting.

At the cooling setpoint, mixing control occurs to maintain constant volume dual duct air flow and room temperature control: as cooling load ramps up, cold duct damper modulates open and hot duct damper modulates down.

Optional cooling elements (e.g. chilled water coil) can be configured to provide additional cooling after the cold duct has reached maximum flow.

 

VntSprtDdband = Duct 2, example 2:

Hot duct stays at constant max volume during heating and deadband with an additional level of supplemental ventilation air flow provided by cold duct. The air flows are summed to provide an elevated minimum ventilation setting larger than max heating flow.

At the cooling setpoint, mixing control occurs to maintain constant volume dual duct air flow and room temperature control: as cooling load ramps up, cold duct damper modulates open and hot duct damper modulates down. When the total flow (ventilation setpoint) is larger than the max cooling setpoint, the hot duct provides the additional supplemental ventilation air flow.

Optional cooling elements (e.g. chilled water coil) can be configured to provide additional cooling after the cold duct has reached maximum flow.

Parameter configuration for use case 5b:

*In the room AF for ventilation control (VavVntCtl) set min vent parameter for Comfort mode (AirFlMinRCmf) to desired CV flow; the min vent setpoint object in Duald11 (VavSuAflMinVnt) can be set to zero when the minimum ventilation parameters are used for min vent settings.

Note that if minimum ventilation parameter is not set high (for example during Economy mode) constant volume is not provided:

Configuration

Objects

Description

Object

Type

Default value

Supply air VAV flow coefficient 1

▶ The value used to calibrate span of air flow measurement; can be entered manually or the value of the calculated flow coefficient (VavSuFlCoeCal1) is written to this object following the Calibrate command.

VavSuFlCoef1

ACnfVal

0.780

Supply air VAV flow coefficient 2
▶ The value used to calibrate span of air flow measurement; can be entered manually or the value of the calculated flow coefficient (VavSuFlCoeCal2) is written to this object following the Calibrate command.

VavSuFlCoef2

ACnfVal

0.780

Supply air VAV initial flow coefficient 1
▶ The value of flow coefficient as found prior to balancing; this value is recorded when the user-entered Balancing Command is set to Balancing.

VavSuFlCoeIni1

ACnfVal

0.000

Supply air VAV initial flow coefficient 2
▶ The value of flow coefficient as found prior to balancing; this value is recorded when the user-entered Balancing Command is set to Balancing.

VavSuFlCoeIni2

ACnfVal

0.000

Air flow settings

Supply air VAV smoke control air volume flow setpoint
▶ Air flow setpoint if VavSuDevMod = 5. Air flow used in balancing if VavSuBalModx = 7; balancer can use this as a manual air flow setting.

VavSuSpAflSmk

ACnfVal

50.0 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Supply air VAV maximum air volume flow for cooling
▶ Maximum air flow setpoint for cooling; the air flow used for balancing when the Supply air VAV balancing mode = 1.

VavSuAirFlMaxC

ACnfVal

100.0 [m3/h]
58.9 [ft3/min]
27.78 [l/s]

Supply air VAV minimum air volume flow for cooling
▶ Minimum air flow setpoint for cooling; the air flow used for balancing when the Supply air VAV balancing mode = 4.

VavSuAirFlMinC

ACnfVal

50.0 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Supply air VAV maximum air volume flow for heating
▶ Maximum air flow setpoint for heating; the air flow used for balancing when the Supply air VAV balancing mode = 2.

VavSuAirFlMaxH

ACnfVal

100.0 [m3/h]
58.9 [ft3/min]
27.78 [l/s]

Supply air VAV minimum air volume flow for heating
▶ Minimum air flow setpoint for heating; the air flow used for balancing when the Supply air VAV balancing mode = 5.

VavSuAirFlMinH

ACnfVal

50.0 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Supply air VAV maximum air volume flow for ventilation
▶ Maximum ventilation air flow setpoint for indoor air quality (IAQ) controller and for Rapid ventilation; the air flow used for balancing when the Supply air VAV balancing mode = 3.

VavSuAflMaxVnt

ACnfVal

100.0 [m3/h]
58.9 [ft3/min]
27.78 [l/s]

Supply air VAV minimum air volume flow for ventilation
▶ Minimum air flow setpoint for ventilation, whether fixed or controlled by indoor air quality (IAQ) controller; see also section Minimum ventilation flow. The air flow used for balancing when the Supply air VAV balancing mode = 6.

VavSuAflMinVnt

ACnfVal

0.0 [m3/h]
0.0 [ft3/min]
0.00 [l/s]

Duct 1

Supply air VAV duct area 1

▶ Duct cross-sectional area, user-entered or calculated by automation station using the duct shape, dimension A and dimension B values. For user-entered method, VavSuDuctShape must be set to 4:Direct entry, otherwise data entry by user will trigger area calculation but the resulting value may be overwritten.

VavSuDuctArea1

ACnfVal

0.05 [m2]
0.54 [ft2]

Supply air VAV duct shape 1

▶ Duct cross-sectional shape; Direct entry uses user-entered area, not controller calculation.

1:Rectangular
2:Round
3:Flat oval
4:Direct entry

VavSuDuctShp1

MCnfVal

2:Round

Supply air VAV dimension A 1

▶ For rectangular duct: Width; for round duct: Diameter; for flat oval duct: Total width (major dimension); for Direct entry: Not used.

VavSuDmsnA1

ACnfVal

20.0 [cm]
7.9 [in]

Supply air VAV dimension B 1

▶ For rectangular duct: Height; for round duct: Not used; for flat oval duct: Height (minor dimension); for Direct entry: Not used.

VavSuDmsnB1

ACnfVal

20.0 [cm]
7.9 [in]

Duct 2

Supply air VAV duct area 2
▶ Duct cross-sectional area, user-entered or calculated by automation station using the duct shape, dimension A and dimension B values. For user-entered method, VavSuDuctShape must be set to 4:Direct entry, otherwise data entry by user will trigger area calculation but the resulting value may be overwritten.

VavSuDuctArea2

ACnfVal

0.05 [m2]
0.54 [ft2]

Supply air VAV duct shape 2
▶ Duct cross-sectional shape; Direct entry uses user-entered area, not controller calculation.

Enumeration see VavSuDuctShp1

VavSuDuctShp2

MCnfVal

2:Round

Supply air VAV dimension A 2
▶ For rectangular duct: Width; for round duct: Diameter; for flat oval duct: Total width (major dimension); for direct entry: Not used.

VavSuDmsnA2

ACnfVal

20.0 [cm]
7.9 [in]

Supply air VAV dimension B 2
▶ For rectangular duct: Height; for round duct: Not used; for flat oval duct: Height (minor dimension); for direct entry: Not used.

VavSuDmsnB2

ACnfVal

20.0 [cm]
7.9 [in]

Parameters

Description

Parameter

Default value

Nominal air volume flow 1

▶ Maximum air flow capacity for Duct 1 into the VAV Dual duct box. Can be set equal to the largest max flow setpoint related to Duct 1 or preferably set to zero and not used in application calculations.

AirFlNom1

100 [m3/h]
58.9 [ft3/min]
27.78 [l/s]

Nominal air volume flow 2

▶ Maximum air flow capacity for Duct 2 into the VAV Dual duct box. Can be set equal to the largest max flow setpoint related to Duct 2 or preferably set to zero and not used in application calculations.

AirFlNom2

100 [m3/h]
58.9 [ft3/min]
27.78 [l/s]

Settings

Control strategy
▶ Configuration value that determines how the DXR will sequence air flows from the two ducts during transition between deadband and low level thermal load. Has effect only when VntDuctSprt is set to "Both ducts." (See air flow sequence diagrams.) Snap acting control switches abruptly from flow in one duct to flow in the other duct; it does not draw air flow from both ducts at the same time. Mixing control draws air from both ducts in certain situations.

1:Snap acting control
2:Mixing control

CtlStrgy

1:Snap acting control

Duct supporting ventilation
▶ Configuration value that indicates which duct is mechanically connected to supply fresh air for ventilation. Affects sequencing of air flow from the two ducts. (See air flow sequence diagrams.)

1:No ventilation
2:Duct 1
3:Duct 2
4:Both ducts

VntDuctSprt

4:Both ducts

Ventilation support in dead band
▶ Configuration value that indicates which duct is selected to deliver air for ventilation in the deadband between heating and cooling. Has effect only when VntDuctSprt is set to "Both ducts". (See air flow sequence diagrams.) Also determines which room temperature setpoint (heating or cooling) will be used as the transition point between flow in one duct and flow in the other.

1:Duct 1
2:Duct 2
3:Last duct

VntSprtDdband

1:Duct 1

Setpoint selector for extract air VAV box
▶ Selects whether the supply air flow setpoint or the supply air volume flow is used to determine the extract air flow setpoint.

0:False (Supply air flow setpoint used)
1:True (Supply air volume flow used)

SpSelVavEx

1:Supply air flow

Differential pressure and air flow monitoring

Switch-on point for differential pressure 1

▶ The differential pressure sensor signal value for duct 1 must be above this value or else zero is used.

SwiOnPtDiffP1

0.2 [Pa]
0.001 [inWC]

Hysteresis for differential pressure 1

▶ Amount below SwiOnPtDiffP1, below which the pressure value used by the controller will be zero.

HysDiffP1

0.1 [Pa]
0.000 [inWC]

Switch-on point for differential pressure 2

▶ The differential pressure sensor signal value for duct 2 must be above this value or else zero is used.

SwiOnPtDiffP2

0.2 [Pa]
0.001 [inWC]

Hysteresis for differential pressure 2

▶ Amount below SwiOnPtDiffP2 below which the pressure value used by the controller will be zero.

HysDiffP2

0.1 [Pa]
0.000 [inWC]

Enable monitoring for missing air volume flow
▶ Yes means the DXR interprets very low or missing air flow as a failed sensor.
No means the DXR does not interpret very low or missing air flow as a failed sensor.
With Yes or No, an invalid air flow signal causes pressure dependent control.

0:No
1:Yes

EnMonNoAirFl

0:No

Interlocks

Switch-on point for air volume flow state
▶ The air volume flow above which the VavSuAirFlTck signal switches from the supply air flow setpoint to the actual supply air volume flow (assuming SpSelVavEx is set to True).

SwiOnAirFlSta

10 [%]

Hysteresis for air volume flow state
▶ The air volume flow below SwiOnAirFlSta, below which the VavSuAirFlTck signal switches from the supply air flow to the supply air flow setpoint (assuming SpSelVavEx is set to True).

HysAirFlSta

5 [%]

Enable monitoring for fan state
▶ Enables box fan state to affect VavSuSpAirFl1 or VavSuSpAirFl2. Must = Yes for series fan powered box (VavSuSpAirFl1 and/or VavSuSpAirFl2set to 0 @ priority 5 if fan = off). Must = No for parallel fan powered box.

0:No
1:Yes

EnMonFanSta

0:No

Deviation calculation

Enable deviation calculation 1

▶ When set to 1:Yes, enables the calculation of the deviation value for duct 1 (Air flow setpoint minus air flow value) to be available for AHU fan static setpoint reset. See also section Air flow deviation signal.

0:No
1:Yes

EnDvnCal1

1:Yes

Enable deviation calculation 2

▶ When set to 1:Yes, enables the calculation of the deviation value for duct 2 (Air flow setpoint minus air flow value) to be available for AHU fan static setpoint reset. See also section Air flow deviation signal.

0:No
1:Yes

EnDvnCal2

1:Yes

Saturation calculation

Enable saturation calculation 1

▶ When EnStrtnCal1 is set to 1:Yes, the calculation logic for the saturation signal for duct 1 (VavSuAflStrtn1) is enabled and active.

Saturation signal calculation logic:
VavSuAflStrtn1 will equal 1 ("Starved") if (VavSuPos1 > StrtnLvl1) and (VavSuAirFlDvn1 > AirFlErLm1). This feature is used for AHU fan static pressure reset. See also Saturation signal section.

0:No
1:Yes

EnStrtnCal1

1:Yes

Saturation level 1

▶ Level of damper opening used to indicate that the terminal is "nearly wide open". If VAV damper position VavSuPos1 > StrtnLvl1 and the air flow error (setpoint minus air flow value) > AirFlErLm1 and EnStrtnCal1 = Yes, then the Saturation signal for duct 1 will be True.

StrtnLvl1

90 [%]

Air volume flow error limit 1

▶ If the air flow error (setpoint minus air flow value) > AirFlErLm1 and VavSuPos1 > StrtnLvl1 and EnStrtnCal1 = Yes, then the Saturation signal for duct 1 will be True.

AirFlErLm1

0 [%]

Switch-on delay saturation 1

▶ The time after the saturation conditions for duct 1 are met that the saturation signal to the AHU goes from False to True.

DlyOnStrtn1

60 [s]

Enable saturation calculation 2

▶ When EnStrtnCal2 is set to 1:Yes, the calculation logic for the saturation signal (VavSuAflStrtn2) is enabled and active.

Saturation signal calculation logic:
VavSuAflStrtn2 will equal 1 ("Starved") if (VavSuPos2 > StrtnLvl2) and (VavSuAirFlDvn2 > AirFlErLm2). This feature is used for AHU fan static pressure reset. See also Saturation signal section.

0:No
1:Yes

EnStrtnCal2

1:Yes

Saturation level 2

▶ Level of damper opening used to indicate that the terminal is "nearly wide open". If VAV damper position VavSuPos2 > StrtnLvl2 and the air flow error (setpoint minus air flow value) > AirFlErLm2 and EnStrtnCal2 = Yes, then the Saturation signal for duct 2 will be True.

StrtnLvl2

90 [%]

Air volume flow error limit 2

▶ If the air flow error (setpoint minus air flow value) > AirFlErLm2 and VavSuPos2 > StrtnLvl2 and EnStrtnCal2 = Yes, then the Saturation signal for duct 2 will be True.

AirFlErLm2

0 [%]

Switch-on delay saturation 2

▶ The time after the saturation conditions for duct 2 are met that the saturation signal to the AHU goes from False to True.

DlyOnStrtn2

60 [s]

Air flow demand

Switch-on point for air flow demand
▶ The air volume flow value for duct 1 or duct 2, in percent of nominal air flow, above which the plant mode is written to VavSuAirDmd1 or VavSuAirDmd2, respectively.

SwiOnAirFlDmd

4 [%]

Hysteresis for air flow demand
▶ The air volume flow value below SwiOnAirFlDmd (for duct 1 or duct 2), in percent of nominal air flow, below which the plant mode is no longer written to VavSuAirDmd1 or VavSuAirDmd2, and at which the fan coast timer is triggered. See also section Fan coasting feature.

HysAirFlDmd

2 [%]

Relief functionality

Enable relief 1

▶ Yes: this terminal opens to relieve fan pressure.
No: this terminal does not open to relieve fan pressure.
If set to Yes, allows the value of AirFlRlf1 to be written to VavSuSpAirFl1 if the AHU writes a True to VavSuAirFlRlf1 and AirFlRlf1 > than the previous air flow setpoint value. See also section Relief input signal.

0:No
1:Yes

EnRlf1

0:No

Air volume flow relief 1

▶ The amount of air that this terminal draws when operating to relieve fan pressure.
The air flow value written to VavSuSpAirFl1 if EnRlf1 = True and if the AHU writes a True to VavSuAirFlRlf1 and if AirFlRlf1 > than the previous air flow setpoint value.

AirFlRlf1

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Enable relief 2

▶ Yes: this terminal opens to relieve fan pressure.
No: this terminal does not open to relieve fan pressure.
If set to Yes, allows the value of AirFlRlf2 to be written to VavSuSpAirFl2 if the AHU writes a True to VavSuAirFlRlf2 and AirFlRlf2 > than the previous air flow setpoint value. See also section Relief input signal.

0:No
1:Yes

EnRlf2

0:No

Air volume flow relief 2

▶ The amount of air that this terminal draws when operating to relieve fan pressure.
The air flow value written to VavSuSpAirFl2 if EnRlf2 = True and if the AHU writes a True to VavSuAirFlRlf2 and if AirFlRlf2 > than the previous air flow setpoint value.

AirFlRlf2

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Internal settings – do not change

Pressure unit
▶ Defined by selected engineering unit – do not change.

PUnit

[Pa]
[inWC]

Air volume flow unit
▶ Defined by selected engineering unit – do not change.

AirFlUnit

[m3/h]
Ft3/min
[l/s]

Interface

Interface

Description

Type

Ref.

Owned by

VavSuPos1

Supply air VAV position 1

AO

Room segment / Device

VavSuPos2

Supply air VAV position 2

AO

Room segment / Device

VavSuDiffP1

Supply air VAV differential pressure 1

AI

Room segment / Device

VavSuDiffP2

Supply air VAV differential pressure 2

AI

Room segment / Device

VavSuAirVEff1

Supply air VAV effective air velocity 1

ACalcVal

-

VavSuSpAirFl1

Supply air VAV setpoint for air volume flow 1

APrcVal

-

TrndVavSuAfl1

Trend for supply air VAV air volume flow 1

FtrSel

-

TrndVavSuAfl2

Trend for supply air VAV air volume flow 2

FtrSel

-

VavSuSpAflRel1

Supply air VAV setpoint for relative air volume flow 1

ACalcVal

-

VavSuAirFl1

Supply air VAV air volume flow 1

ACalcVal

-

VavSuAirFlRel1

Supply air VAV relative air volume flow 1

0:Off
1:On

ACalcVal

-

VavSuAirFlDvn1

Supply air VAV air volume flow deviation 1

ACalcVal

-

VavSuAflStrtn1

Supply air VAV air volume flow saturation 1

0:Satisfied
1:Starved

BCalcVal

-

VavSuAirVEff2

Supply air VAV effective air velocity 2

ACalcVal

-

VavSuSpAirFl2

Supply air VAV setpoint for air volume flow 2

APrcVal

-

VavSuSpAflRel2

Supply air VAV setpoint for relative air volume flow 2

ACalcVal

-

VavSuAirFl2

Supply air VAV air volume flow 2

ACalcVal

-

VavSuAirFlRel2

Supply air VAV relative air volume flow 2

Enumeration see VavSuAirFlRel1

ACalcVal

-

VavSuAirFlDvn2

Supply air VAV air volume flow deviation 2

ACalcVal

-

VavSuAflStrtn2

Supply air VAV air volume flow saturation 2

Enumeration see VavSuAflStrtn1

BCalcVal

-

VavSuAirFlTot

Supply air VAV total air volume flow

ACalcVal

-

VavSuDevMod

Supply air VAV device mode

1:Off
2:Control mode
3:Maximum air volume flow
4:Minimum air volume flow
5:Smoke control air volume flow setpoint

MPrcVal

-

VavSuAirFlCtr1

Supply air VAV air flow controller 1

Controller

-

VavSuAirFlCtr2

Supply air VAV air flow controller 2

Controller

-

VavSuCReq

Supply air VAV cooling request

ACalcVal

-

VavSuHReq

Supply air VAV heating request

ACalcVal

-

VavSuVntReq

Supply air VAV ventilation request

ACalcVal

-

VavSuAvlC

Supply air VAV available for cooling

0:No
1:Yes

BCalcVal

-

VavSuAvlH

Supply air VAV available for heating

0:No
1:Yes

BCalcVal

-

VavSuAvlVnt

Supply air VAV available for ventilation

0:No
1:Yes

BCalcVal

-

FanSuCstVal1

Coasting value of supply air fan 1

0:Off
1:On

BCalcVal

-

FanSuCstVal2

Coasting value of supply air fan 2

Enumeration see FanSuCstVal1

BCalcVal

-

VavSuChovrCnd1

Supply air VAV changeover condition 1

1:Neither
2:Heating
3:Cooling
4:Neutral

MPrcVal

-

VavSuChovrCnd2

Supply air VAV changeover condition 2

Enumeration see VavSuChovrCnd1

MPrcVal

-

VavSuAirDmd1

Supply air VAV air demand 1 for plant mode

1:Off
2:Protection
3:Economy
4:Pre-Comfort
5:Comfort
6:Warm-up
7:Cool down
8:Room low temperature protection
9:Condensation overflow protection
10:Free cooling
11:Night cooling
12:Ventilation
13:Equipment temperature protection
14:Air volume flow off
15:Smoke extraction positive pressure
16:Smoke extraction negative pressure
17:Purge

MCalcVal

-

VavSuAirDmd2

Supply air VAV air demand 2 for plant mode

Enumeration see VavSuAirDmd1

MCalcVal

-

VavSuAirFlRlf1

Supply air VAV air volume flow relief 1

BPrcVal

-

VavSuAirFlRlf2

Supply air VAV air volume flow relief 2

BPrcVal

-

VavSuCDmd

Supply air VAV cooling demand

ACalcVal

-

VavSuHDmd

Supply air VAV heating demand

ACalcVal

-

VavSuVntDmd

Supply air VAV ventilation demand

ACalcVal

-

VavSuAflPvdVnt

Supply air VAV provided air volume flow for ventilation

ACalcVal

-

VavSuAirFlTck

Supply air VAV air volume flow tracking

ACalcVal

-

VavSuFlCoeCal1

Supply air VAV calculated flow coefficient 1

ACalcVal

-

VavSuBalCmd1

Supply air VAV balancing command 1

1:Ready
2:Balancing
3:Calibrate
4:Record
5:Balanced

MTrgVal

-

VavSuFlCoeCal2

Supply air VAV calculated flow coefficient 2

ACalcVal

-

VavSuBalCmd2

Supply air VAV balancing command 2

Enumeration see VavSuBalCmd1

MTrgVal

-

CdnMsgCol

Collection of condensation message

ColView

-

 

CdnMsgRs

Result of condensation message

0:Normal
1:Alert

BCalcVal

-

CdnMsg

Condensation message

0:Normal
1:Alert

BCalcVal

Room segment / Field device

CclCdnMsg

Cooling coil condensation message

0:Normal
1:Alert

BCalcVal

Room segment / Field device

VavSuSplyAir1

Supply air VAV supply chain for air 1

GrpMbr

Room segment

VavSuSplyAir2

Supply air VAV supply chain for air 2

GrpMbr

Room segment

VavSuBalSta1

Supply air VAV balancing state 1

1:Initial
2:Balancing
3:Balanced

MCnfVal

-

VavSuBalMod1

Supply air VAV balancing mode 1

1:Maximum cooling
2:Maximum heating
3:Maximum ventilation
4:Minimum cooling
5:Minimum heating
6:Minimum ventilation
7:Smoke

MCnfVal

-

VavSuAirFlHod1

Supply air VAV air volume flow at hood 1

ACnfVal

-

VavSuBalMRec1

Supply air VAV recorded balancing mode 1

Enumeration see VavSuBalMod1

MCnfVal

-

VavSuAflreHod1

Supply air VAV recorded air volume flow at hood 1

ACnfVal

 

VavSuFlCoeRec1

Supply air VAV recorded flow coefficient 1

ACnfVal

-

VavSuFlCoeIni1

Supply air VAV initial flow coefficient 1

ACnfVal

-

VavSuAirFlRec1

Supply air VAV recorded air volume flow 1

ACnfVal

-

VavSuPosRec1

Supply air VAV recorded position 1

ACnfVal

-

VavSuDuctArea1

Supply air VAV duct area 1

ACnfVal

-

VavSuDuctShp1

Supply air VAV duct shape 1

1:Rectangular
2:Round
3:Flat oval
4:Direct entry

MCnfVal

-

VavSuDmsnA1

Supply air VAV dimension A 1

ACnfVal

-

VavSuDmsnB1

Supply air VAV dimension B 1

ACnfVal

-

VavSuFlCoef1

Supply air VAV flow coefficient 1

ACnfVal

-

VavSuBalSta2

Supply air VAV balancing state 2

Enumeration see VavSuBalSta1

MCnfVal

-

VavSuBalMod2

Supply air VAV balancing mode 2

Enumeration see VavSuBalMod1

MCnfVal

-

VavSuAirFlHod2

Supply air VAV air volume flow at hood 2

ACnfVal

-

VavSuBalMRec2

Supply air VAV recorded balancing mode 2

Enumeration see VavSuBalMod1

MCnfVal

-

VavSuAflreHod2

Supply air VAV recorded air volume flow at hood 2

ACnfVal

-

VavSuFlCoeRec2

Supply air VAV recorded flow coefficient 2

ACnfVal

-

VavSuFlCoeIni2

Supply air VAV initial flow coefficient 2

ACnfVal

-

VavSuAirFlRec2

Supply air VAV recorded air volume flow 2

ACnfVal

-

VavSuPosRec2

Supply air VAV recorded position 2

ACnfVal

-

VavSuDuctArea2

Supply air VAV duct area 2

ACnfVal

-

VavSuDuctShp2

Supply air VAV duct shape 2

Enumeration see VavSuDuctShp1

MCnfVal

-

VavSuDmsnA2

Supply air VAV dimension A 2

ACnfVal

-

VavSuDmsnB2

Supply air VAV dimension B 2

ACnfVal

-

VavSuFlCoef2

Supply air VAV flow coefficient 2

ACnfVal

-

VavSuSpAflSmk

Supply air VAV smoke control air volume flow setpoint

ACnfVal

-

VavSuAirFlMaxC

Supply air VAV maximum air volume flow for cooling

ACnfVal

-

VavSuAirFlMinC

Supply air VAV minimum air volume flow for cooling

ACnfVal

-

VavSuAirFlMaxH

Supply air VAV maximum air volume flow for heating

ACnfVal

-

VavSuAirFlMinH

Supply air VAV minimum air volume flow for heating

ACnfVal

-

VavSuAflMaxVnt

Supply air VAV maximum air volume flow for ventilation

ACnfVal

-

VavSuAflMinVnt

Supply air VAV minimum air volume flow for ventilation

ACnfVal

-

Engineering and commissioning

Air balancing

Air balance functions for Dual duct follow the pattern of other VAV applications. For Dual duct, the functions are implemented twice, once for each duct. Functions include:

Each duct has a balancing mode object. Users can command both ducts to perform balancing tasks. For example, command duct 1 balancing mode to max cooling and command duct 2 balancing mode to min heating.