Heating / Cooling coil 2-pipe system, external flow control (HCcl2Pipe13)
| This application function generates a water flow setpoint to the pressure independent control valve for a heating / cooling coil that is supplied with hot or chilled water from a 2-pipe changeover system. The water flow setpoint is calculated based on request signals (from the room controllers) received for heating and cooling. This application function is ONLY available for: |
Required elements and how to configure them:
Element | I/O | Signal type |
|---|---|---|
HCclSpWfl "Heating/cooling coil setpoint for water volume flow" | On-board output, Heating/cooling coil valve position | 2-pipe; Setpoint for water volume flow 0…10V |
Function
The figure below shows BACnet objects associated with this application function. Primary signal flow is summarized as follows:
H/C coil heating or cooling request (HCclHReq / HCclCReq) is received and processed into the output signal for H/C coil valve position (HCclSpWFl).
Basic function: Accept request signal from associated room controller and map it to the appropriate water flow setpoint. Pass it through a device mode logic switch; Output the result as a command to the BACnet object that controls the device.

| Command or request (or related) |
| Notification of condition or status, or availability |
| Device mode |
| Interlock (internal signal, not a BACnet object; see Interlocks section for additional information) |
Interlocks
Room automation interlocks are internal signals that coordinate interaction between HVAC devices. They are not visible in ABT Site or web interface, but parameters associated with them are. See comment column for hints on parameters that affect interlock functionality.
Signal | Type | Direction | Description | Comment |
|---|---|---|---|---|
AirFlCReq | Boolean | Out | Air flow cooling request | See Configuration section for parameters named "...AirFlCReq". |
AirFlHReq | Boolean | Out | Air flow heating request | See Configuration section for parameters named "...AirFlHReq". |
AirFlSta | Boolean | In | Air flow status | Parameter EnMonAirFlSta must = Yes. See Configuration section for additional information. |
Sequence
Hot/Chilled water flow setpoint modulation: In response to heating or cooling demand, the water flow setpoint is modulated/adjusted to control the room temperature at setpoint. In response to external triggers for special modes such as warm-up, cool down, or safety conditions, device mode may be set to off or fully open.
Note
This AF does not perform loop control; its main purpose is to run commands. Loop control processes (for this AF) are managed in the "room" AF(s) that collaborate with this AF to command the end device.
External water flow controller / valve: The water flow setpoint (HclSpWFl) drives the external water flow controller / valve through a 0-10V DC signal.
Changeover: The Heating/cooling coil changeover condition multistate object (HCclChovrCnd) provides information received from central plant regarding the status of heating / cooling changeover. Three states are supported:
- Neither (the plant is switching to / from heating or cooling, and neither is available)
- Heating
- Cooling
Device mode: The input signal for device mode is a multistate value.
HCclDevMod supports the following states:
- Off
- Control mode (modulation)
- Fully open, heating (allows maximum flow for flushing the water circuit)
- Fully open, cooling (allows maximum flow for flushing the water circuit)
Heating available status: When the H/C coil is available for heating, the binary output signal for "Heating/cooling coil available for heating " (HCclAvlH) will be "Yes" (available). HCclAvlH is used by the system to regulate heating resources. For example, if there is a call for heating but the H/C coil is not available because it is already at maximum capacity (because device mode is fully open), then HCclAvlH will signal "No" and the next available heating resource in the temperature control sequence will be activated.
For heating available status to be "Yes", device mode must equal "Control mode" (modulation).
Also, HCclChovrCnd must indicate that the central plant is changed over to heating.
Cooling available status: When the H/C coil is available for cooling, the binary output signal for "Heating/cooling coil available for cooling" (HCclAvlC) will be "Yes" (available). HCclAvlC is used by the system to regulate cooling resources. For example, if there is a call for cooling but the H/C coil is not available because it is already at maximum capacity (because device mode is fully open), then HCclAvlC will signal "No" and the next available cooling resource in the temperature control sequence will be activated.
For cooling available status to be "Yes", device mode must equal "Control mode" (modulation).
Also, HCclChovrCnd must indicate that the central plant is changed over to cooling.
Supply chain interface outputs
HCclHwDmd supports the following states:
- Off (no demand signal)
- Heating demand (demand signal is active)
- Warm-up (Hot water demand is initiated when plant operating mode is set to warm-up)
HCclChwDmd supports the following states:
- Off (no demand signal)
- Cooling demand (demand signal is active)
- Free cooling (cooling device is in free cooling mode)
Free cooling can be initiated by the central plant when surplus cooling capacity is available. Under certain conditions, the room can take advantage of surplus cooling capacity in the absence of an explicit cooling demand; the room temperature must be below the setpoint associated with the current room climate mode (Comfort, Pre-Comfort etc.). This type of free cooling is different from "economizer" free cooling, which uses an outside air damper.
Supply chain interface inputs
The input signals for hot water availability / chilled water availability are binary values [No|Yes] determined by central command. They are commanded via supply chain group communication for the purpose of TOa-dependent device lockout. The relinquish default value for each is Yes.
HCclHwAvl: If the outside air temperature is above the hi limit value, HCclHwAvl is set to No and the heating valve is closed. (see Central AF SplyHwxx for additional information)
HCclChwAvl: If the outside air temperature is below the low limit value, HCclChwAvl is set to No and the cooling valve is closed. (see Central AF SplyChwxx for additional information)
If for some reason HCclHwAvl and HCclChwAvl are both "No", then device mode (HCclDevMod) is set to Off at priority 9.
The following figure(s) illustrates control modulation and related functions.


Configuration
Objects
Description | Object | Type | Default value |
|---|---|---|---|
Heating/cooling coil maximum water volume flow for cooling | HCclWflMaxC | ACnfVal | 100.0 [l/h] |
Heating/cooling coil maximum water volume flow for heating | HCclWflMaxH | ACnfVal | 100.0 [l/h] |
Parameters
Description | Parameter | Default value |
|---|---|---|
Manual control mode 1:Auto | CtlModMan | 1:Auto |
Interlocks | ||
Switch-on point for air volume flow cooling request | SwiOnAirFlCReq | 4 [%] |
Hysteresis for air volume flow cooling request | HysAirFlCReq | 2 [%] |
Switch-on delay for air volume flow cooling request | DlyOnAirFlCReq | 30 [s] |
Switch-on point for air volume flow heating request | SwiOnAirFlHReq | 4 [%] |
Hysteresis for air volume flow heating request | HysAirFlHReq | 2 [%] |
Switch-on delay for air volume flow heating request | DlyOnAirFlHReq | 30 [s] |
Enable monitoring for air volume flow state 0:No | EnMonAirFlSta | 0:No |
Hot/chilled water demand | ||
Switch-on point for hot/chilled water demand | SwiOnHwChwDmd | 4 [%] |
Hysteresis for hot/chilled water demand | HysHwChwDmd | 2 [%] |
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
HCclSpWfl | Heating/cooling coil setpoint for water volume flow | AO | ◉ | Room segment / Device |
HCclSpWflRel | Heating/cooling coil setpoint for relative water volume flow | APrcVal | ● | - |
HCclSpWflCRel | Heating/cooling coil setpoint for relative water volume flow for cooling | ACalcVal | ● | - |
HCclSpWflHRel | Heating/cooling coil setpoint for relative water volume flow for heating | ACalcVal | ● | - |
HCclDevMod | Heating/cooling coil device mode 1:Off | MPrcVal | ● | - |
HCclCReq | Heating/cooling coil cooling request | ACalcVal | ● | - |
HCclHReq | Heating/cooling coil heating request | ACalcVal | ● | - |
HCclAvlC | Heating/cooling coil available for cooling 0:No | BCalcVal | ● | - |
HCclAvlH | Heating/cooling coil available for heating 0:No | BCalcVal | ● | - |
HCclChovrCnd | Heating/cooling coil changeover condition 1:Neither | MPrcVal | ● | - |
HCclChwDmd | Heating/cooling coil chilled water demand 1:Off | MCalcVal | ● | - |
HCclHwDmd | Heating/cooling coil hot water demand 1:Off | MCalcVal | ● | - |
HCclChwAvl | Heating/cooling coil chilled water available 0:No | BPrcVal | ● | - |
HCclHwAvl | Heating/cooling coil hot water available 0:No | BPrcVal | ● | - |
HCclSplyChw | Heating/cooling coil supply chain for chilled water | GrpMbr | ● | Room segment |
HCclSplyHw | Heating/cooling coil supply chain for hot water | GrpMbr | ● | Room segment |
HCclWflMaxC | Heating/cooling coil maximum water volume flow for cooling | ACnfVal | ● | - |
HCclWflMaxH | Heating/cooling coil maximum water volume flow for heating | ACnfVal | ● | - |
Engineering and commissioning
Device capacity configuration
The H/C coil must be configured to provide one of the following conditions: Auto (provides both heating/cooling), Heating, or Cooling. To configure the H/C coil set CtlModMan to the appropriate control mode (e.g., heat) for the room segment.
When concerned with operation of a coil in a changeover system, remember to check:
- Changeover state of the central system
- Local indication of the changeover state
The relative water flow setpoint (HCclSpWFlCRel / HCclSpWFlHRel) is normalized as a percentage (0-100%) of HCclSpWFl where 100% represents the value configured in "Process value 2" property for HCclSpWFl.




