Using play/pause function
The play/pause function can be used for performing delta downloads.

It is recommended to perform a full download before using the play/pause function. A prior full download is especially recommended when a Modbus network is created or a BACnet/SC certificate must be renewed.
Properties for device configuration are not loaded via play/pause function.
Downloading device configurations
Use play/pause function
- The device is configured and assigned.
- Click .
- Online parameter changes are uploaded.
- The changed hardware is downloaded.
- The engineering editor is online.
- An orange frame around the I/O configuration area becomes visible.
- Live status and online Values/Unit of all data points are displayed.

You cannot add new data points in the online session.
- Check and fix wrongly displayed values in data points.
- The Live status is updated as soon as the values are correct.
- Change the Commissioning state of the data points tested to passed.
- Click when all changes are made.
- The engineering editor is offline.
- The changes done in play mode are written in the device and in the offline data.
- Verify that the changes you made are reflected offline.
- Click again.
- Commissioning status entered in the last session is saved and visible.

When using the play/pause function, the status of the engineering data on the device is set to Outdated engineering data. It is therefore mandatory to download the engineering data.