Extraction arm, no flow sensor (ExtrcEqp11)
| This application function monitors a binary input object (ExtrcSpSel) that activates an extraction arm. The first configured setpoint value (ExtrcSp1) is selected when the BI is active. The second configured setpoint value (ExtrcSp2) is selected when the BI is inactive. |
Required elements and how to configure them:
Element | I/O | Signal type |
|---|---|---|
ExtrcSpSel "Extraction setpoint selector" | On-board output, Extraction setpoint selector | Binary input |
Function
The AF functions as described above. The main output signal is the calculated value from object ExtrcPrSp (Extraction present setpoint).

BI Valid
The validity pin is always True. The application never sets airflow object Invalid.
Main features:
- Binary input monitor for extraction arm activation
- Setpoints for extract airflow, configurable
- Trend for extraction present setpoint
Configuration
Objects
Description | Object | Type | Default value |
|---|---|---|---|
Extraction setpoint 1 | ExtrcSp1 | ACnfVal | 0 |
Extraction setpoint 2 | ExtrcSp2 | ACnfVal | 0 |
Extraction setpoint 3 (not used) | ExtrcSp3 (not used) |
|
|
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
ExtrcSpSel | Extraction setpoint selector | BI | ◉ | Room segment / Field device |
ExtrcPrSp | Extraction present setpoint | ACalcVal | ● | - |
TrndExtrcPrSp | Trend for extraction present setpoint | FtrSel | ● | - |
ExtrcSp1 | Extraction setpoint 1 | ACnfVal | ● | - |
ExtrcSp2 | Extraction setpoint 2 | ACnfVal | ● | - |
ExtrcSp3 (not used) | Extraction setpoint 3 (not used) |
|
|
|