Extraction arm, velocity sensor and duct area (ExtrcEqp14)

This application function monitors a velocity sensor on an analog input object (ExtrcAirV) and calculates the air flow through the extraction arm using a data model with a duct area value.

The AF works with or without a binary input (ExtrcSpSel) to select the air flow setpoint. If a binary input is not connected, the setpoint will always equal ExtrcSp1. If a binary input is connected, the setpoint will equal ExtrcSp1 when the BI is active, and it will equal ExtrcSp2 when the BI is inactive.

Required elements and how to configure them:

Element

I/O

Signal type

ExtrcAirV "Extraction air velocity"

On-board output,

Extraction air velocity

0…10V

(Optional)
ExtrcSpSel "Extraction setpoint selector"

On-board output,

Extraction setpoint selector

Binary input

Function

The AF functions as described above. The main output signals are calculated values for Extraction effective air velocity, Extraction present setpoint, and Extraction air volume flow.

Main features:

 

Configuration

Objects

Description

Object

Type

Default value

Extraction duct area

ExtrcDuctArea

ACnfVal

0.05 [m2]
0.538 [ft2]

Extraction duct shape

ExtrcDuctShape

MCnfVal

Round

Extraction dimension A

ExtrcDmsnA

ACnfVal

20 [cm]
7.87 [in]

Extraction dimension B

ExtrcDmsnB

ACnfVal

20 [cm]
7.87 [in]

Extraction flow coefficient

ExtrcFlCoef

ACnfVal

1

Extraction setpoint 1

ExtrcSp1

ACnfVal

0
[m3/h]
[ft3/min]
[l/s]

Extraction setpoint 2

ExtrcSp2

ACnfVal

0
[m3/h]
[ft3/min]
[l/s]

Extraction setpoint 3 (not used)

ExtrcSp3 (not used)

 

 

Configuration

Parameters

Description

Parameter

Default value

Enable propagation air volume flow failure

Determines whether the system receives updates from the digital pressure sensor about airflow failures. If set to "No," the system assumes that the airflow is valid. Refer to the room pressure control application failure response and configuration.

EnPrpgAflFail

No

Time constant for air volume flow

The time constant for the attenuation filter on the air volume flow sensor. Larger values help to stabilize fluctuating air volume flow sensor values. Larger values for this constant also cause the values reported by the air volume flow sensor to be more heavily weighted toward measurements in the past. Leaving at 0 disables the filter.

TiConAirFl

0 [s]

Switch delay for tracking method to air volume flow

If the tracking method switches from the setpoint to airflow (see SwiTolTckMthd), this sets the amount of time to wait before making the switch.

SwiDlyTckMthd

6000 [s]

Switch tolerance for tracking method to air volume flow

Sets an acceptable level of difference (percentage) between the relative airflow setpoint and current relative airflow.By default, the system tracking method follows the airflow setpoint. But if current relative airflow deviates from the relative setpoint by a percentage amount greater than what is set by the SwiTolTckMthd parameter, the system switches from tracking to the setpoint to tracking to the actual airflow.

Setting the tolerance level (SwiTolTckMthd) to 100% will not always prevent tracking from switching from setpoint to airflow.

SwiTolTckMthd

5 [%]

Nominal air volume flow

Represents the maximum expected airflow value when the damper is all the way open. To help normalize the airflow and the airflow setpoint for control purposes, the system will always pick the highest between AirFlNom and any other airflow configuration values.

AirFlNom

0 [m3/h]

0 [ft3/min]

0 [l/s]

Air volume flow unit

AirFlUnit

 

 

Interface

Interface

Description

Type

Ref.

Owned by

ExtrcSpSel

Extraction setpoint selector

BI

Room segment / Field device

ExtrcAirV

Extraction air velocity

AI

Room segment / Field device

ExtrcAirVEff

Extraction effective air velocity

ACalcVal

-

ExtrcPrSp

Extraction present setpoint

ACalcVal

-

TrndExtrcPrSp

Trend for extraction present setpoint

FtrSel

-

ExtrcAirFl

Extraction air volume flow

ACalcVal

-

TrndExtrcAirFl

Trend for extraction air volume flow

FtrSel

-

ExtrcAirFlMon

Monitoring for extraction air vol.flow

FtrSel

-

ExtrcDuctArea

Extraction duct area

ACnfVal

-

ExtrcDuctShape

Extraction duct shape

MCnfVal

-

ExtrcDmsnA

Extraction dimension A

ACnfVal

-

ExtrcDmsnB

Extraction dimension B

ACnfVal

-

ExtrcFlCoef

Extraction flow coefficient

ACnfVal

-

ExtrcSp1

Extraction setpoint 1

ACnfVal

-

ExtrcSp2

Extraction setpoint 2

ACnfVal

-

ExtrcSp3 (not used)

Extraction setpoint 3 (not used)