Predefined I/Os

Name

Description

Type

Signal

Range / State text / Unit

Trend/Type

Preferred object

AckBtn

Acknowledgement button1

BI

Contact NO

No I Yes

Yes, 4

AckBtn

AirFl

Air volume flow1

AI

0...10 [V] DC

0...5000 [m3/h]

Yes, 1

AirFl

AirV

Air velocity1

AI

0...10 [V] DC

0...20 [m/s]

Yes, 2

AirV

AQualR

Room air quality

Notification class 4, High priority notification (acknowledge, reset)

High limit: 2000 [ppm]

High warning limit: 1950 [ppm]

Low warning limit: 50 [ppm]

Low limit: 0 [ppm]

Time deviation: 0 [s]

AI

0...10 [V] DC

0...2000 [ppm]

Yes, 3

AQualR

AtmP

Atmospheric pressure1

AI

0...10 [V] DC

0...1,5 [bar]

Yes, 2

AtmP

BrgtFcd

Brightness on facade1

AI

0...10 [V] DC

0...150000 [lx]

N/A

BrgtFcd

BrgtOdr

Outdoor brightness1

AI

0...10 [V] DC

0...150000 [lx]

Yes, 2

BrgtOdr

BySwi

Bypass switch1

BI

Contact NO

Off I On

Yes, 4

BySwi

CdnMon

Condensation monitor

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

CdnMon

ClsCmd

Close command2

BO

Relay

Off I On

Yes, 4

ClsCmd

CmdByOn

Instance: Cmd

Bypass command: Off, on2

Command

BO

Relay

Off I On

Yes, 4

CmdByOn

CmdClg

Instance: Cmd

Command: Heating, cooling2

Command

BO

Relay

Heating I Cooling

Yes, 4

CmdClg

CmdOn

Instance: Cmd

Command: Off, on2

Command

BO

Relay

Off I On

Yes, 4

CmdOn

CmdOpn

Instance: Cmd

Command: Close, open2

Command

BO

Relay

Close I Open

Yes, 4

CmdOpn

CmdSpd2

Instance: Cmd

Command: Off, speed 1, speed 22

Command

MO

2x Relay

1 to n mapping

Off I Speed 1 I Speed 2

Yes, 4

CmdSpd2

CmdSt2

Instance: Cmd

Command: Off, stage 1, stage 22

Command

MO

2x Relay

1 to n mapping

Off I Stage 1 I Stage 2

Yes, 4

CmdSt2

CmdSt3

Instance: Cmd

Command: Off, stage 1 to stage 32

Command

MO

3x Relay

1 to n mapping

Off I Stage 1 I Stage 2 I Stage 3

Yes, 4

CmdSt3

CmdSt4

Instance: Cmd

Command: Off, stage 1 to stage 42

Command

MO

4x Relay

1 to n mapping

Off I Stage 1 I Stage 2 I Stage 3 I Stage 4

Yes, 4

CmdSt4

CmdSt5

Instance: Cmd

Command: Off, stage 1 to stage 52

Command

MO

5x Relay

1 to n mapping

Off I Stage 1 I Stage 2 I Stage 3 I Stage 4 I Stage 5

Yes, 4

CmdSt5

DfrSta

Defrost state1

BI

Contact NO

Off I On

Yes, 4

DfrSta

DiffP

Instance: P

Differential pressure

Notification class 4, High priority notification (acknowledge, reset)

High limit: 450 [Pa]

High warning limit: 400 [Pa]

Low warning limit: 50 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...500 [Pa]

Yes, 2

DiffP

DiffPAhu

Instance: PAhu

Differential pressure close to air handler

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1500 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...2500 [Pa]

Yes, 2

DiffPAhu

DiffPAir

Instance: DiffP

Differential pressure: for air

Differential pressure

Notification class 8, Medium priority notification (acknowledge)

High limit: 450 [Pa]

High warning limit: 400 [Pa]

Low warning limit: 50 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [min]

AI

0...10 [V] DC

0...500 [Pa]

Yes, 2

DiffPAir

DiffPAirFlCalc

Differential pressure for air volume flow calculation1

AI

0...10 [V] DC

0...1000 [Pa]

Yes, 2

DiffPAirFlCalc

DiffPMon

Differential pressure monitor

Notification class 4, High priority notification (acknowledge, reset)

Reference value: On

Time deviation: 30 [s]

BI

Contact NO

Off I On

N/A

DiffPMon

DiffPMonErc

Instance: DiffPMon

Differential pressure monitoring for ERC

Differential pressure monitor

Notification class 8, Medium priority notification (acknowledge)

Reference value: On

Time deviation: 30 [s]

BI

Contact NO

Off I On

N/A

DiffPMonErc

DiffPWater

Instance: DiffP

Differential pressure: for water

Differential pressure

Notification class 8, Medium priority notification (acknowledge)

High limit: 450 [kPa]

High warning limit: 425 [kPa]

Low warning limit: 25 [kPa]

Low limit: 0 [kPa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...500 [kPa]

Yes, 2

DiffPWater

DoorSwi

Door switch

BI

Contact NO

Closed I Opened

Yes, 4

DoorSwi

El230V

Supply 230 Volt

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

El230V

El24V

Supply 24 Volt

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

El24V

El400V

Supply 400 Volt

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

El400V

ElCrtBrk

Electrical circuit breaker

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

ElCrtBrk

ElPhMon

Electrical phase monitoring

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

ElPhMon

EmgSwi

Emergency switch

Notification class 4, High priority notification (acknowledge, reset)

BI

Contact NC

Normal I Tripped

N/A

EmgSwi

EvtLmp1

Event lamp 12

BO

Relay

Off I On

N/A

EvtLmp1

EvtLmp2

Event lamp 22

BO

Relay

Off I On

N/A

EvtLmp2

Fb

Feedback

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Off

Time deviation: 10 [s]

BI

Contact NO

Off I On

N/A

Fb

Fb1

Feedback 1

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Off

Time deviation: 10 [s]

BI

Contact NO

Off I On

N/A

Fb1

Fb2

Feedback 2

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Off

Time deviation: 10 [s]

BI

Contact NO

Off I On

N/A

Fb2

FbInf

Instance: Fb

Feedback, information1

Feedback

BI

Contact NO

Off I On

N/A

FbInf

FbClsd

Feedback closed1

BI

Contact NO

Off I On

N/A

FbClsd

FbOpnd

Feedback opened1

BI

Contact NO

Off I On

N/A

FbOpnd

FbPos

Position feedback1

AI

0...10 [V] DC

0...100 [%]

Yes, 3

FbPos

FbPosOpnd

Feedback position: in motion, closed, opened1

MI

2x Contact NO

1 to n mapping

In motion I Closed I Opened

N/A

FbPosOpnd

FilDet

Filter detector

Notification class 8, Medium priority notification (acknowledge)

Reference value: Tripped

Time deviation: 5 [min]

BI

Contact NO

Normal I Tripped

N/A

FilDet

FireDetCont

Fire detection contact

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

FireDetCont

Fl

Flow1

AI

0...10 [V] DC

0...10 [m3/h]

Yes, 1

Fl

FlDet

Flow detector

Notification class 4, High priority notification (acknowledge, reset)

Reference value: No flow

Time deviation: 10 [s]

BI

Contact NO

No flow I Flow

N/A

FlDet

FlDetInf

Instance: FlDet

Flow detector, information1

Flow detector

BI

Contact NO

No flow I Flow

N/A

FlDetInf

FltExpsVss

Fault expansion vessel

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

FltExpsVss

FltNotifCl4

Instance: Flt

Fault: for high priority notification (acknowledge, reset)

Fault

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

Flt

FltNotifCl5

Instance: Flt

Fault: for high priority notification (acknowledge)

Fault

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

Flt

FrPrtMon

Frost protection monitor

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

FrPrtMon

GasDet

Gas detector

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

GasDet

HCSwi

Heating/cooling switch1

MI

2x Contact NO

1 to n mapping

Automatic I Heating I Cooling

Yes, 4

HCSwi

HtgClgMod

Heating/cooling mode2

BO

Relay

Heating I Cooling

Yes, 4

HtgClgMod

HuDet

Humidity detector

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

HuDet

HuEx

Extract air humidity

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [%rH]

High warning limit: 80 [%rh]

Low warning limit: 20 [%rh]

Low limit: 10 [%rH]

Time deviation: 1 [min]

AI

0...10 [V] DC

0...100 [%RH]

Yes, 3

HuEx

HuExBfErc

Extract air humidity before energy recovery

Notification class 8, Medium priority notification (acknowledge)

High limit: 95 [%rH]

Low limit: 10 [%rH]

Time deviation: 1 [min]

AI

0...10 [V] DC

0...100 [%RH]

Yes, 3

HuExBfErc

HuOa

Outside air humidity

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [%rH]

Low limit: 10 [%rH]

Time deviation: 0 [s]

AI

0...10 [V] DC

0...100 [%RH]

Yes, 3

HuOa

HuR

Room air humidity

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [%rH]

High warning limit: 80 [%rh]

Low warning limit: 20 [%rh]

Low limit: 10 [%rH]

Time deviation: 1 [min]

AI

0...10 [V] DC

0...100 [%RH]

Yes, 3

HuR

HuSu

Supply air humidity

Notification class 4, High priority notification (acknowledge, reset)

High limit: 90 [%rH]

High warning limit: 80 [%rh]

Low warning limit: 20 [%rh]

Low limit: 10 [%rH]

Time deviation: 1 [min]

AI

0...10 [V] DC

0...100 [%RH]

Yes, 1

HuSu

LgtEmgDet

Emergency detector for lighting

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

LgtEmgDet

LgtEmgSwi

Emergency switch for lighting

MI

2x Contact NC

1 to n mapping

Auto I Off I On

Yes, 4

LgtEmgSwi

Lmp

Lamp2

BO

Relay

Off I On

N/A

Lmp

ManIntvLmp

Manual intervention active lamp2

BO

Relay

Inactive I Active

N/A

ManIntvLmp

Mdlt

Modulating2

AO

0...10 [V] DC

0...100 [%]

Yes, 2

Mdlt

MnSwi

Main switch

Notification class 5, High priority notification (acknowledge)

Reference value: Off

Time deviation: 0 [s]

BI

Contact NO

Off I On

N/A

MnSwi

MntnSwi

Maintenance switch

Notification class 5, High priority notification (acknowledge)

Reference value: Maintenance

Time deviation: 0 [s]

BI

Contact NC

Normal I Maintenance

N/A

MntnSwi

MtrEl

(RP_REAL for PropID=4433 usage)

Electric meter

Accu

N/A

N/A

N/A

MtrEl

OpInd

Operation indication2

BO

Relay

Off I On

N/A

OpInd

OpModSwiCmf

Instance: OpModSwi

Operating mode switch: Auto, protection, comfort1

Operating mode switch

MI

2x Contact NO

1 to n mapping

Auto I Protection I Comfort

Yes, 4

OpModSwiCmf

OpModSwiOn

Instance: OpModSwi

Operating mode switch: Auto, off, on1

Operating mode switch

MI

2x Contact NO

1 to n mapping

Auto I Off I On

Yes, 4

OpModSwiOn

OpModSwiSpd2

Operating mode switch: Auto, off, speed 1, speed 21

Operating mode switch

MI

3x Contact NO

1 to n mapping

Auto I Off I Speed 1 I Speed 2

Yes, 4

OpModSwiSpd2

OpModSwiSt2

Operating mode switch: Auto, off, stage 1, stage 21

Operating mode switch

MI

3x Contact NO

1 to n mapping

Auto I Off I Stage 1 I Stage 2

Yes, 4

OpModSwiSt2

OpnCmd

Open command2

BO

Relay

Off I On

Yes, 4

OpnCmd

OvrTDet

Overtemperature detector

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal | Tripped

N/A

OvrTDet

OvrVtgPrt

Overvoltage protection

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

OvrVtgPrt

PcpDet

Precipitation detector1

BI

Contact NC

Inactive I Active

N/A

PcpDet

PEx

Extract air pressure

Notification class 4, High priority notification (acknowledge, reset)

High limit: 450 [Pa]

High warning limit: 400 [Pa]

Low warning limit: 50 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...500 [Pa]

Yes, 2

PEx

PExAhu

Extract air pressure near air handling unit (ventilation monoblock)

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1500 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...2500 [Pa]

Yes, 2

PExAhu

PMaxMon

Maximum pressure monitor

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 10 [s]

BI

Contact NC

Normal I Tripped

N/A

PMaxMon

PMin

Minimum pressure

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1'000 [kPa]

High warning limit: 950 [kPa]

Low warning limit: 150 [kPa]

Low limit: 100 [kPa]

Time deviation: 30 [s]

AI

0...10 [V] DC

0...1'000 [kPa]

Yes, 3

PMin

PMinChw

Minimum pressure chilled water

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1'000 [kPa]

High warning limit: 950 [kPa]

Low warning limit: 150 [kPa]

Low limit: 100 [kPa]

Time deviation: 30 [s]

AI

0...10 [V] DC

0...1'000 [kPa]

Yes, 3

PMinChw

PMinHw

Minimum pressure hot water

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1'000 [kPa]

High warning limit: 950 [kPa]

Low warning limit: 150 [kPa]

Low limit: 100 [kPa]

Time deviation: 30 [s]

AI

0...10 [V] DC

0...1'000 [kPa]

Yes, 3

PMinHw

Pos

Position2

AO

0...10 [V] DC

0...100 [%]

Yes, 2

Pos

PR

Room pressure

Notification class 5, High priority notification (acknowledge)

High limit: 90 [Pa]

High warning limit: 70 [Pa]

Low warning limit: -70 [Pa]

Low limit: -90 [Pa]

Time deviation: 30 [s]

AI

0...10 [V] DC

-100...100 [Pa]

Yes, 2

PR

PrfSwi

Profile switch1

MI

2x Contact NO

1 to n mapping

Auto I Profile 1 I Profile 2

Yes, 4

PrfSwi

PrPwr

Present power1

AI

0...10 [V] DC

0...1000 [kW]

Yes, 2

PrPwr

PSu

Supply air pressure

Notification class 4, High priority notification (acknowledge, reset)

High limit: 450 [Pa]

High warning limit: 400 [Pa]

Low warning limit: 50 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...500 [Pa]

Yes, 2

PSu

PSuAhu

Supply air pressure near air handling unit (ventilation monoblock)

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1500 [Pa]

Low limit: 0 [Pa]

Time deviation: 10 [s]

AI

0...10 [V] DC

0...2500 [Pa]

Yes, 2

PSuAhu

PWater

Pressure: for water

Notification class 4, High priority notification (acknowledge, reset)

High limit: 1'000 [kPa]

High warning limit: 950 [kPa]

Low warning limit: 150 [kPa]

Low limit: 100 [kPa]

Time deviation: 30 [s]

AI

0...10 [V] DC

0...1'000 [kPa]

Yes, 2

PWater

RainDet

Rain detector1

BI

Contact NC

Inactive I Active

Yes, 4

RainDet

RainFll

Rainfall1

AI

0...10 [V] DC

0...1'000 [mm]

Yes, 2

RainFll

ReCCmd

Recooling command2

BO

Relay

Inactive I Active

Yes, 4

ReCCmd

ResetCmd

Reset command2

BO

Relay

Off I On

Yes, 4

Reset

SftyTLm

Safety temperature limiter

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

SftyTLm

ShdEmgDet

Emergency detector for shading

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

ShdEmgDet

ShdSrvSwi

Service switch for shading

MI

3x Contact NO

1 to n mapping

Auto I Open I Height 100% I Angle 0% I Closed

Yes, 4

ShdSrvSwi

SmextEh

Smoke extraction exhaust air

Notification class 5, High priority notification (acknowledge)

Reference value: On

Time deviation: 0 [s]

BI

Contact NO

Off I On

N/A

SmextEh

SmextSu

Smoke extraction supply air

Notification class 5, High priority notification (acknowledge)

Reference value: On

Time deviation: 0 [s]

BI

Contact NO

Off I On

N/A

SmextSu

SmkDet

Smoke detector

Notification class 4, High priority notification (acknowledge, reset)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

SmkDet

SmkDetMntn

Smoke detector maintenance

Notification class 8, Medium priority notification (acknowledge)

Reference value: Maintenance

Time deviation: 0 [s]

BI

Contact NO

Normal I Maintenance

N/A

SmkDetMntn

SolRdn

Solar radiation1

AI

0...10 [V] DC

0...2000 [W/m2]

Yes, 2

SolRdn

SolRdnFcd

Solar radiation on facade1

AI

0...10 [V] DC

0...2000 [W/m2]

N/A

SolRdnFcd

SpAirFlRel

Setpoint for relative air volume flow2

AO

0...10 [V] DC

0...100 [%]

Yes, 2

SpAirFlRel

Spd

Speed2

AO

0...10 [V] DC

0...100 [%]

Yes, 2

Spd

SpTClg

Instance: SpT

Temperature setpoint: for cooling2

Temperature setpoint

AO

0...10 [V] DC

0...20 [°C]

Yes, 4

SpTClg

SpTHtg

Instance: SpT

Temperature setpoint: for heating2

Temperature setpoint

AO

0...10 [V] DC

0...100 [°C]

Yes, 4

SpTHtg

SupEvtNotifLmp

Suppress event notification active lamp2

BO

Relay

Off I On

N/A

SupEvtNotifLmp

SupEvtNotifSwi

Suppress event notification switch1

BI

Contact NO

No I Yes

N/A

SupEvtNotifSwi

T

Temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

T

TAfEgIn

Temperature after energy supply

Notification class 4, High priority notification (acknowledge, reset)

High limit: 90 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TAfEgIn

TDhw

Domestic hot water temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 75 [°C]

High warning limit: 70 [°C]

Low warning limit: 5 [°C]

Low limit: 0 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TDhw

TDhwCns

Consumer domestic hot water temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 75 [°C]

High warning limit: 70 [°C]

Low warning limit: 5 [°C]

Low limit: 0 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TDhwCns

TEhAfErc

Exhaust air temperature after energy recovery

Notification class 8, Medium priority notification (acknowledge)

High limit: 40 [°C]

Low limit: 4 [°C]

Time deviation: 0 [s]

AI

LG-Ni1000 -50...180 [°C]

-70...70 [°C]

Yes, 2

TEhAfErc

TEx

Extract air temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 40 [°C]

High warning limit: 34 [°C]

Low warning limit: 14 [°C]

Low limit: 10 [°C]

Time deviation: 1 [min]

AI

LG-Ni1000 -50...180 [°C]

0...50 [°C]

Yes, 3

TEx

TExBfErc

Extract air temperature before energy recovery

Notification class 8, Medium priority notification (acknowledge)

High limit: 40 [°C]

Low limit: 10 [°C]

Time deviation: 0 [s]

AI

LG-Ni1000 -50...180 [°C]

0...50 [°C]

Yes, 3

TExBfErc

TFlClg

Instance: TFl

Flow temperature: for cooling

Flow temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 30 [°C]

High warning limit: 28 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TFlClg

TFlGly

Instance: TFl

Flow temperature glycol

Flow temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 50 [°C]

Low limit: -25 [°C]

Time deviation: 10 [s]

AI

LG-Ni1000 -50...180 [°C]

-30...50 [°C]

Yes, 2

TFlGly

TFlHtg

Instance: TFl

Flow temperature: for heating

Flow temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TFlHtg

TFlPrim

Primary flow temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TFlPrim

TFlSec

Secondary flow temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TFlSec

TFrPrtA

Frost protection for air temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 50 [°C]

Low limit: 4 [°C]

Time deviation: 0 [s]

AI

0...10 [V] DC

0...50 [°C]

Yes, 2

TFrPrtA

TGly

Glycol temperature1

AI

LG-Ni1000 -50...180 [°C]

-20...50 [°C]

Yes, 2

TGly

ThOvrld

Thermoelectrical overload

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NO

Normal I Tripped

N/A

ThOvrld

TIn

Inlet temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TIn

TMnFlCns

Main flow temperature consumer side

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnFlCns

TMnFlCnsChw

Main flow temperature consumer, chilled water

Notification class 8, Medium priority notification (acknowledge)

High limit: 30 [°C]

High warning limit: 28 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnFlCnsChw

TMnFlCnsHw

Main flow temperature consumer side, hot water

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnFlCnsHw

TMnRtCnsChw

Main return temperature consumer side, chilled water

Notification class 8, Medium priority notification (acknowledge)

High limit: 30 [°C]

High warning limit: 28 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnRtCnsChw

TMnRtCnsHw

Main return temperature consumer side, hot water

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnRtCnsHw

TMnRtGen

Main return temperature generation side

Notification class 8, Medium priority notification (acknowledge)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TMnRtGen

TmrBtn

Timer button1

BI

Contact NO

No I Yes

Yes, 4

TmrBtn

TOa

Outside air temperature1

AI

LG-Ni1000 -50...180 [°C]

-70...70 [°C]

Yes, 3

TOa

TOut

Outlet temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TOut

TR

Room temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 40 [°C]

High warning limit: 34 [°C]

Low warning limit: 14 [°C]

Low limit: 10 [°C]

Time deviation: 1 [min]

AI

LG-Ni1000 -50...180 [°C]

0...50 [°C]

Yes,3

TR

TRtClg

Instance: TRt

Return temperature: for cooling

Return temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 30 [°C]

High warning limit: 28 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 10 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TRtClg

TRtGly

Instance: TRt

Return temperature glycol

Return temperature

Notification class 8, Medium priority notification (acknowledge)

High limit: 50 [°C]

Low limit: -25 [°C]

Time deviation: 10 [s]

AI

LG-Ni1000 -50...180 [°C]

-30...50 [°C]

Yes, 2

TRtGly

TRtHtg

Instance: TRt

Return temperature: for heating

Return temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 90 [°C]

High warning limit: 85 [°C]

Low warning limit: 6 [°C]

Low limit: 4 [°C]

Time deviation: 10 [s]

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TRtHtg

TRtPrim

Primary return temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TRtPrim

TRtSec

Secondary return temperature1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 2

TRtSec

TSu

Supply air temperature

Notification class 4, High priority notification (acknowledge, reset)

High limit: 40 [°C]

High warning limit: 34 [°C]

Low warning limit: 14 [°C]

Low limit: 10 [°C]

Time deviation: 1 [min]

AI

LG-Ni1000 -50...180 [°C]

0...50 [°C]

Yes, 1

TSu

TSuAfErc

Supply air temperature after energy recovery

Notification class 8, Medium priority notification (acknowledge)

High limit: 40 [°C]

Low limit: 10 [°C]

Time deviation: 0 [s]

AI

LG-Ni1000 -50...180 [°C]

-70...70 [°C]

Yes, 2

TSuAfErc

TTnkBtm

Tank temperature, bottom1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 3

TTnkBtm

TTnkTop

Tank temperature, top1

AI

LG-Ni1000 -50...180 [°C]

0...100 [°C]

Yes, 3

TTnkTop

WdDrct

Wind direction1

AI

0...10 [V] DC

0...360 [°Angle]

N/A

WdDrct

WDet

Water detector

Notification class 5, High priority notification (acknowledge)

Reference value: Tripped

Time deviation: 0 [s]

BI

Contact NC

Normal I Tripped

N/A

WDet

WdSpd

Wind speed

Notification class 5, High priority notification (acknowledge)

High limit: 15 [m/s]

High warning limit: 12 [m/s]

Low warning limit: 0 [m/s]

Low limit: 0 [m/s]

Time deviation: 0 [s]

AI

0...10 [V] DC

0...50 [m/s]

Yes, 2

WdSpd

WLanBtn

WLAN button1

BI

Contact NO

No I Yes

Yes, 4

WLanBtn

1 Notification class 8, Medium priority notification (acknowledge), Suppress event detection: Yes

2 Notification class 4, High priority notification (acknowledge, reset), Suppress event detection: Yes