Set the BACnet/SC device back to BACnet/IP communication
If a BACnet/SC communication has to be changed back to BACnet/IP communication, the device must be completely purged. Only after a complete purge can the device be reloaded with the BACnet/IP settings.
NOTICE

Warranty expires prematurely
When updating an IP configuration to a BACnet/SC configuration, a clear device1 must be performed which will delete all data on the device. As a result, the warranty of any approved project will expire prematurely. Please contact the operator in advance to find out how the warranty can be retained.
- A network connection is established
/
.
- Go to Startup.
- Open the Configure and download task.
- In the Discovered devices area, select the device.
- Right-click the device and select Clear device.
- The current device is cleared.
Note: Clear device resets the device to its factory settings. This command deletes all:
- Loaded applications (control programs, data points, BACnet objects)
- All field devices on local field networks (such as TX I/O modules, onboard IO configurations, PL-Link/ DALI/Modbus devices)
- All network settings
- All loaded certificates
- The entire control program