Recommended engineering pattern applications
The standard device charts available with the PL-Link RDG20..KN & RDG26..KN instances in the Field Device Catalog refer to the features of RDG20..KN & RDG26..KN (BACnet objects owned by RDG20..KN & RDG26..KN) with programming patterns, see chapter "Recommended programming patten applications".
Recommended programming pattern applications
In addition, there are features (BACnet objects owned by RDG20..KN & RDG26..KN) without a related programming pattern, so-called engineering patterns.
Engineering pattern: Configuration object value
- BACnet object can be configured by an O&M client
Engineering pattern: Monitoring object value
- BACnet object can be monitored by an O&M client
Engineering pattern: Operation object value
- BACnet object can be operated by an O&M client
The following table gives an overview of the recommended engineering patterns for the most relevant and configurable features of the RDG20..KN & RDG26..KN.
Feature | BACnet objects (owned by RDG20..KN & RDG26..KN) | Engineering pattern |
|---|---|---|
Cooling setpoints | SpTRCCmf / SpTRCEco | Configuration object value |
Heating setpoints | SpTRHCmf / SpTRHEco | Configuration object value |
Air quality setpoint | SpAQualR | Configuration object value |
Humidity setpoint | SpHuRel | Configuration object value |
Effective cooling setpoint | SpTRCEff | Monitoring object value |
Effective heating setpoint | SpTRHEff | Monitoring object value |
Cooling valve position | VlvPosC / VlvPosC(1) | Monitoring object value |
Heating valve position | VlvPosH / VlvPosH(1) | Monitoring object value |
Effective operating mode | OpModEff | Monitoring object value |
Effective fan speed | FanSpd | Monitoring object value |
Condensation | CdnMon | Monitoring object value |
Zone supply air temperature | TSuZn | Monitoring object value |
Manual operating mode | OpModMan | Operation object value |
Setpoint shift | SpTRShft | Operation object value |
Fan operation | FanOp / FanSpdMan | Operation object value |