Binary Process Value object (BPrcVal)

The Binary Process Value (BPrcVal) object type defines the functions by representing binary process values as virtual variables and running a Binary Process Value object. BPrcVal object properties are:

✳ Indicates a Siemens proprietary property.

Present value

 

 

'Present value' indicates the present value of the virtual variable.

Property ID: 85

Present priority

 

 

"Present priority" property indicates the priority of the highest not released priority slot. If all priority slots are released and "Default command" is used as "Present value", "Present priority" will be set to 17.

Default command

 

 

"Default command" is the default value to be used for the "Present value" property when all command priority values in the "Priority array" property have a NULL value. The placement of NULL in the value parameter indicates the absence of any command at that priority. When all elements of the priority table array contain NULL, the commandable property shall assume the value defined in the "Default command" property of the object.

State flag

 

 

"State flag" represents four boolean flags ("Out of service", "Overridden", "Fault", "In-Alarm") that indicate the general status of an object.

Reliability

 

 

'Reliability' indicates whether the property value 'Present value' is reliable. If the 'Present value' is not reliable, the property 'Reliability' indicates the cause of the fault and the bit "Fault" of the state indication is set to 'True'. In a normal case, the property 'Reliability' is set to "No fault".

Property ID: 103

Out of service

 

 

"Out of service" allows decoupling the object from being modified by a control program, system program or peripheral device.

  • If "Out of service" is TRUE, the properties "Present value" and "Reliability" will no longer be updated by the respective control program, system program or peripheral device.
  • If "Out of service" is TRUE, the properties "Present value" and "Reliability" can be modified for simulating and testing purposes.
  • If "Out of service" will be changed from FALSE to TRUE, the properties "Present value" and "Reliability" keep their values. Nevertheless, they can be individually modified afterwards.
  • If "Out of service" will be changed from TRUE to FALSE, the properties "Present value" and "Reliability" keep their values. They will be modified by the next update of the producer.

Property ID: 81

I/O address

 

 

"I/O address" identifies and documents the data source, and facilitates configuring, modifying, and querying the assignment in a standardized way.

The content of "I/O address" is technology-specific and includes:

  • Unique selector to identify and document the respective data acquisition. For example, TX-I/O or KNX PL-Link.
  • Unique address to identify the peripheral data source. For example, TX-I/O 3.4.
  • Blank until assigned to a Module.

Min.switch-on time

 

 

"Min.switch-on time" defines the minimum time that a device must be switched on during a switching cycle.

Range: 1...30 [1 s]

Property ID: 67

Min.switch-off time

 

 

"Min.switch-off time" defines the minimum time that a device must be switched off during a switching cycle.

Range: 1...30 [1 s]

Property ID: 66

Inactive text

 

 

'Inactive text' describes the inactive state of property 'Present value'.

Property ID: 46

Active text

 

 

'Active text' describes the active state of property 'Present value'.

Property ID: 4

Object access level

 

 

"Object access level" defines the instance-specific object access level. "Object access level" is used for generic filtering and processing an object by a client application.

  • "Object access level" is a configuration property which can only be set up offline (ABT, application configuration).
  • "Object access level" is evaluated by client applications such as Technical Operator, DB-Import, and APOGEE Point Team mapping.

Access level

Name

Description

7

Basic operation

Access to BACnet objects and properties for a room user e.g. data points visible on a room unit.

6

Standard operation

Access to BACnet objects and properties for standard operation and monitoring (daily business), .e.g. room and plant information on a management station.

5

Extended operation

Access to BACnet objects and properties for extended operation and monitoring such as network and device objects. All I/Os are visible

4

Administrator

Not used by HQ solutions yet.

3

Basic service

Access to BACnet objects and properties used for commissioning, e.g. configuration value extensions, I/O extensions, etc.

2

Extended service

Not used by HQ solutions yet.

1

Internal

Access to all BACnet objects and properties for very specialized actions e.g. during development.

Object usage

 

 

"Object usage" indicates whether the object is used or unused. The "Object usage" property can hide or display respective objects and their functionality in a client. For example, room functionality can be marked for flexible room arrangements as used/unused. An object that is marked as unused behaves as if the object does not exist.

Property ID: 4930

Description

 

 

"Description" is a string of printable characters whose content is not restricted.

Object name

 

 

"Object name" represents a name for the object that is unique internetwork-wide. The minimum length of the string is one character. The set of characters used in the "Object name" are restricted to printable characters.

Comment

 

 

A string of printable characters whose content is not restricted.