Service and expert level parameters

The properties list shows more properties than are supported in ABT Site. The other properties may be required for commissioning with a KNX tool.

The parameter display depends on the selected application and function. Appl means application. Parameter values are only visible when the device is set as Manager (M), Subordinate (S) or both identification (✓).

Parameter

Name

Factory setting

Range

RDG20..

RDG26..

Dependencies

Service level

P001

Control sequence 1)

2-pipe:
1 = Cooling only

 

4-pipe:
4 = Heating and cooling

0 = Heating only

1 = Cooling only

2 = H/C changeover auto

3 = H/C changeover manual

4 = Heating and cooling

P002

P0024)

Operation via room operating mode selector 1)

1

1 = Auto – Protection / Auto - Comfort – Protection (when there is local scheduler)

2 = Auto - Comfort - Economy - Protection

3 = Auto (Comfort) - Protection Hospitality

4 = Auto - Protection (RDG2..T)

M

M

P001, P005, P258

P0034)

Operation via fan operating selector 2)

0

0 = Auto - Manual

1 = Manual

2 = Auto - Manual - Protection

3 = Auto – Protection

4 = Forced ventilation (RDG2x4KN)

5 = Forced ventilation, fan auto-manual (RDG2x4KN)

M

M

P350, P258

P004

Unit

0

0 = °C (parameter in °C)

1 = °F (parameter in °F)

P0054)6)

Scheduler

RDG2..KN: OFF

RDG2..T: ON

ON = Enabled

OFF = Disabled

M

M

P002, P258

P006

Measured value correction

0 K

–5…5 K

P007

Humidity value correction (RDG2..KN)

0

-10…0…10 %

P008

Standard display

0

0 = Room temperature

1 = Setpoint

P009

Additional display information

RDG200KN, RDG260KN: 0…5
RDG204KN, RDG264KN: 0…9
RDG2..T: 0, 1, 3, 4

0

0 = --- (No display)

1 = °C and °F

2 = Outside temperature

3 = Time of day (12 h)

4 = Time of day (24 h)

5 = Humidity

6 = Indoor air quality (numeric) 5)

7 = Indoor air quality (text) 5)

8 = Humidity and IAQ (numeric) 5)

9 = Humidity and IAQ (text) 5)

P010

Setpoint concept

1

1 = Comfort concept

2 = Energy saving concept

P104

P0114)

Comfort basic setpoint

21 °C (70 °F)

5…40 °C (41…104 °F)

M

M

P258

P013

Comfort setpoint minimum

5 °C (41 °F)

(P010 = 1): 5 °C (41 °F)...P016-1 K

(P010 = 2): 5 °C (41 °F)...P014-1 K

P010

P014

Comfort setpoint maximum heating

21 °C (70 °F)

P013+1 K…P015-1 K

P010

P015

Comfort setpoint minimum cooling

25 °C (77 °F)

P014+1 K…P016 -1 K

P010

P016

Comfort setpoint maximum

35 °C (95 °F)

(P010 = 1): P013 +1 K...40 °C (104 °F)

(P010 = 2): P015 +1 K...40 °C (104 °F)

P010

P0174)

Summer time

1

OFF

1 = Europe

2 = Australia

3 = New Zealand

M

M

P258

P0194)

Economy heating setpoint

15 °C (59 °F)

--- (0), 5 °C…P020 (41 °F…P020)

P020 = 40 °C max. (P020 = 104 °F max.)

M

M

P258

P0204)

Economy cooling setpoint

30 °C (86 °F)

--- (0), P019…40 °C (P019…104 °F)

P019 = 5 °C min. (P019 = 41 °F min.)

M

M

P258

P0235) 7)

Indoor air quality setpoint (RDG2..KN)

1000 ppm

10...2000 ppm

P450

P0244)

Humidity setpoint high (RDG2..KN)

50

--- (0), P026 or 20…90 %

M

M

P450, P258

P025

Humidity setpoint high ECO (RDG2..KN)

OFF

--- (0), P026…90 %, or 20…90 %

M

M

P258

P0264)

Humidity setpoint low (RDG2..KN)

OFF

--- (0), 20…90 % or P024

M

M

P450, P258

P0273)

Electric heater when cooling

ON

ON: Enabled

OFF: Disabled

Appl

P0284)

Keypad

0

0 = Unlocked

1 = Auto lock

2 = Manual lock

3 = Auto lock the operating mode

4 = Auto lock the Setpoint shift

5 = Auto lock fan speed

6 = Auto lock operating mode, setpoint shift

7 = Auto lock operating mode, fan speed

8 = Auto lock fan speed, setpoint shift

9 = Auto lock scheduler

10 = Auto lock operating mode, scheduler

11 = Auto lock scheduler, fan speed

12 = Auto lock operating mode, scheduler, fan speed

13 = Auto lock scheduler, setpoint shift

14 = Auto lock operating mode, scheduler, setpoint shift

15 = Auto lock scheduler, fan speed, setpoint shift

M

M

P258

P029

Fan: Dead zone Comfort mode 2)

0

0 = Fan disable

1 = Low speed (Heating and Cooling)

2 = Low speed (Cooling only)

3 = Fan disable Auto & Manual

4 = Low speed Auto & Manual

5 = Low speed Auto & Manual Cooling

P350

P030

Buzzer function

ON

ON = Enabled

OFF = Disabled

P031

Language

1

1 = English

2 = Francais (French)

3 = Deutsch (German)

4 = Italiano (Italian)

5 = Espanol (Spanish)

6 = Nederlands (Dutch)

7 = Turkce (Turkish)

8 = Cesky (Czech)

9 = Suomi (Finnish)

10 = Polski (Polish)

11 = Magyar (Hungarian)

12 = Slovenski (Slovak)

13 = (Limba) Romana (Romanian)

14 = Dansk (Danish)

15 = Norsk (Norwegian)

P0324)

Room operating mode holidays

0

0 = Economy

1 = Protection

M

M

P005, P258

Note:

1)P001 cannot be set to 3 if P002 is set to 3, and vice versa.

2) For RDG200KN and RDG260KN: If P350 = 0, P003 is disabled. P029 is invisible. For RDG204KN and RDG264KN: If P350 = 0, P003 is set to 4.

3) Only available when application is 2-pipe with electric heater

4) If P258 = 0 (Subordinate), the parameter values are not available.

5) The parameters are valid for RDG204KN and RDG264KN.

6) Time of day cannot be set via ETS, see Scheduler.

7) If P450 = 2…6 with IAQ control, P023 is visible.

The parameter display depends on the selected application and function. Parameter values are only visible when the device is set as Manager (M), Subordinate (S) or both identification (✓).

Parameter

Name

Factory setting

Range

RDG20..

RDG26..

Dependencies

Expert level

Control settings

P050

Heat P-band Xp

2 K

0.5…6 K

P001

P051

Switching differential heating

1 K

0.5…6 K

P001

P052

Cool P-band Xp

P053

Switching differential cooling

P054

Radiator P-band Xp/switching differential

2 K

0.5…6 K

P05510)

Dead zone Comfort mode

2 K

0.5…5 K

M

M

P258

P056

Setpoint differential

2 K

0.5…5 K

P0571)

Integral action time Tn for heating

45 min

0...120 min

P201, P203, P204

P0581)

Integral action time Tn for cooling

P0592)10)

H/C changeover switching point cooling

16 °C (61 °F)

5 °C…P060-2 K (41 °F…P060-2 K)

M

M

P001, P150, P153, P155, P258

P0602)10)

H/C changeover switching point heating

28 °C (82 °F)

P059+2 K…40 °C (P059+2 K…104 °F)

M

M

P001, P150, P153, P155, P258

P06111)

Setpoint ΔT cooling

---

--- (0), 1...40 K

P150, P153, P155

P06211)

Setpoint ΔT heating

---

--- (0), 1...40 K

P150, P153, P155

P063

Minimum supply air temperature

---

---, 0 °C…P064 (32 °F…P064)

P150, P153, P155

P064

Maximum supply air temperature

---

---, P063…50 °C (P063…122 °F)

P150, P153, P155

Mode and setpoints

P10010)

Protection heating setpoint

8 °C (46 °F)

--- (0), 5 °C…P101; (41 °F…P101)

M

M

P258

P10110)

Protection cooling setpoint

---

--- (0), P100…40 °C; (P100…104 °F)

M

M

P258

P1023)10)

Temporary Comfort mode

---

--- (0), 1...360 min

M

M

P002, P005, P258

P10310)

Temporary Comfort setpoint

OFF

0 = Disabled (OFF)

1 = Enabled (ON)

2 = Enabled (ON), excluded Window contact

3 = Enabled (ON), excluded presence detector (include hotel presence)

M

M

P258

P10410)

Setpoint display (RDG2..KN)

1

1 = Absolute setpoints

2 = Relative setpoints

M

M

P010

P258

P10913) 19)

Outside damper frost protection (RDG2..4KN)

---

---; 2...14 °C (36...50 °F)

P450

P11010)

Energy indicator (RDG2..KN)

1

OFF = Disabled

1 = Green and Red dimmed out

2 = Green dimmed out / Red fixed

3 = Green and Red fixed

M

M

P258

P11110)

Energy indicator range (RDG2..KN)

2 K

0…10 K

M

M

P258

Inputs

P150

Input X1

RDG2..KN: 0...14

RDG2..T: 0...6 & 9...14

P150:1

P153: RDG2..KN: 0
RDG2..T: 2

P155: RDG200KN, RDG260KN, RDG200T, RDG260T: 3
RDG204KN & RDG264KN: 0

Synco ACS / PCT Go, ETS terminology

0 = --- (no function)

1 = Room / return temperature

2 = H/C changeover 10)

3 = Window contact (DI)

4 = Dewpoint (DI)

5 = Enable electric heater (DI)

6 = Fault input (DI)

7 = Monitor input (DI)

8 = Monitor input temp. (AI)

9 = Supply air temperature (AI)

10 = Presence detector (DI) 10)

11 = External temperature limit (AI)

12 = Coil flow temperature (AI)

13 = Hotel presence detector / card reader (DI) 10)

14 = Coil return temperature (AI)

M

M

M

M

M

M

P153: P150, P155

P155: P150, P153

P258

P153

Input X2

RDG2..KN: 0...14

RDG2..T: 0...6 & 9...14

P155 20)

Input U1 (RDG200KN&RDG260KN)

Input and output U1 (RDG204KN&RDG264KN)

RDG2..KN: 0...14

Input X3 (RDG2..T): 0...6 & 9...14

Desigo ABT Site terminology

0 = --- (no function)

1 = Room temperature control, external or return air temperature sensor

2 = Heating/cooling changeover 10)

3 = Window contact

4 = Dewpoint sensor

5 = Electric heater, enabled

6 = Fault input

7 = Switching state input

8 = Temperature sensor input

9 = Supply air temperature

10 = Presence detector 10)

11 = External temperature sensor, limitation

12 = Coil flow temperature

13 = Presence detector or card reader, hotel 10)

14 = Coil return temperature

 

-

M

M

 

-

M

M

P151

X1: Normal position and sensor

0 when DI or AI/DI

2 when AI

0 = Normally Open

1 = Normally Closed

2 = NTC-3K

3 = LG-Ni1000

P151: P150

P154: P153

P156: P155

P154

X2: Normal position and sensor

P156

U1 (RDG2..KN): Normal position and sensor

X3 (RDG2..T): Normal position and sensor

Outputs

P200

Number of heating / cooling sequences

Note: for 2-/4-pipe 2-stage application

1

1 = Heating 2 sequences, cooling 2 sequences

2 = Heating 2 sequences, cooling 1 sequence

3 = Heating 1 sequence, cooling 2 sequences

d01

P201

RDG20..: Output Y1 (and Y3 for 3-pos)
RDG26..: Output Y10 (DC) or Q1 (2-pos)

RDG20..: 4

RDG26..: 5 (6 when application type is 4-pipe with 6-port ball valve)

1 = 3-position

2 = On/Off (3 wires)

3 = PWM

4 = On/Off

5 = DC

6 = 6-port valve (DC 0…10 V)

Appl

7 = 6-port valve (DC 2…10 V)

Appl

8 = Inverse signal, 6-port valve (DC 10…0 V)

Appl

9 = Inverse signal 6-port valve (DC 10…2 V)

Appl

10 = 6-port valve (DC 0... 10 V) 3rd part

Appl

11 = 6-port valve (DC 2... 10 V) 3rd part

Appl

P203

RDG20..: Output Y2 (and Y4 for 3-pos)
RDG26..: Output Y20 (DC) or Q2 (2-pos)

RDG20..: 4

RDG26..: 5

1 = 3-position

2 = On/Off (3 wires)

3 = PWM

4 = On/Off

5 = DC

P204

RDG20..: Output Y3
RDG26..: Output Y30 (DC)

RDG20..: 4

RDG26..: 5

3 = PWM

4 = On/Off

5 = DC

P205

RDG20xKN: Output Y4
RDG26xKN: Output U1

Note: for 4-pipe 2-stage application

RDG20..KN: 4

RDG26..KN: 5

3 = PWM

d01

4 = On/Off

d01

5 = DC

d01

P206 5)

PWM algorithm cycle Y1

1200 s

20…3600 s

P206: P201

P207: P203

P208: P204

P209: P205

P2075)

PWM algorithm cycle Y2

P2085)

PWM algorithm cycle Y3

P2095)

PWM algorithm cycle Y4 (RDG2..KN)

P210

On time minimum PWM output

5 %

1…20 %

P211

Off time minimum PWM output

P212

On time minimum 2-pos output

1 min

1…20 min

P400, P401, P402

P213

Off time minimum 2-pos output

P214 6))

RDG20..: Actuator running time Y1 and Y3 for 3-pos

150 s

20…300 s

P214: P201

P215: P203

P215 6

RDG20..: Actuator running time Y2 and Y4 for 3-pos

P217

RDG26..: Power of electric heater on Q2

0 kW

0.0…1.2 kW

P203, P204

Features

P250

Valve kick

OFF

ON = Enabled

OFF = Disabled

P251 7)10)

Purge time (every 2 hours)

---

--- (0, Not active), 1…5 min

M

M

P258

P252 8)

Flow temp limit floor heating

28 °C (82 °F)

10...50 °C (50…122 °F)

P254 4)

Swap sequences between H and C (2-pipe / 2-stage)

OFF

ON = Enabled

OFF = Disabled

P001

P25510)

Track setpoint for cooling depends on outside temperature (RDG2..KN)

OFF

ON = Enabled

OFF = Disabled

M

M

P258

P256

Flow limitation in heating mode for PICV (RDG264KN)

Note: Available on devices only with previous SW versions

10 V

0…10 V

P258

Manager/subordinate (M/S) (RDG2..KN)

1

0 = Subordinate

1 = Manager

P25912)

Subordinate identification (RDG2..KN)

1

"---"

1...9

S

S

P258

P260

PICV: Heating maximal position (RDG26..)

100 %

0...100 %

P001

P261

PICV: Cooling maximal position (RDG26..)

100 %

0...100 %

P001

Fan control

P350

Fan control

1

0 = Disabled

1 = Enabled

2 = Heating only

3 = Cooling only

4 = 2nd stage

5 = Heating and 2nd stage cooling

6 = Cooling and 2nd stage heating

7 = 2nd stage Cooling only

8 = 2nd stage Heating only

P351

Fan speeds

3

1 = 1-speed fan

2 = 3-speed fan

3 = DC 0...10 V fan

P350, P201, P203, P204, P400, P401, P402

P352

Fan overrun time

2-pipe/4-pipe el. Heater: 60 s

Other applications: 0 s

0...600 s

P350

P353

Fan speed switching point low

10 %

1 %...Fan speed 2 (P354)

P350

P354

Fan speed switching point med

65 %

Fan speed 1 (P353)…fan speed 3 (P355)

P350, P351

P355

Fan speed switching point high

100 %

Fan speed 2 (P354)…100 %

P350, P351

P356

DC fan switching point

DC: 10 %

DC: 1...100 %

P350

P357

DC fan speed low min. output

DC: 30 %

DC: 1 %...Fan speed med (P358)

P350

P358

DC fan speed med output

DC: 60 %

DC: fan speed low (P357)…fan speed high(lower value of P359 and P360)

P350

P359

DC fan speed high max. out. heat

DC: 80 %

DC: fan speed med (P358)…100 %

P350

P360

DC fan speed high max. out.cool

P361

Fan start kick

ON

ON: Enabled

OFF: Disabled

P350

P362

On time minimum fan

2 min

1...6 min

P350

P363

Periodic fan kick Comfort

---

1…89 min, --- (0)

P350

P364

Periodic fan kick Economy

---

0…359 min, ---

P350

P365

Fan start delay

0 s

0...360 s

P350

P366

Fan start, minimum water temperature

30 °C

--- (0),5…60 °C

P350

Input

Relay functions

P400 9)

Output Q1 function

RDG2..KN: 0...8

RDG2..T: 0...6

0

0 = No function

1 = Switch OFF in Protection

2 = Switch ON in Heat/Cool demand

3 = Switch ON in Heat demand

4 = Switch ON in Cool demand

5 = Heating sequence active

6 = Cooling sequence active

7 = External dehumidifier control 10)

8 = External humidifier control 10)

M

M

M

M

P350, P351, P258

P401 9)

Output Q2 function

RDG2..KN: 0...8

RDG2..T: 0...6

P402 21)

Output Q3 function

RDG2..KN: 0...8

RDG2..T: 0...6

Controller

P45015)

Control strategy (RDG2..KN)

RDG200KN & RDG260KN: 0

 

RDG204KN & RDG264KN: 2

0 = Temperature (T)

1 = Temperature (T) + Relative humidity (r.h.)

2 = Temperature (T) + Air quality (IAQ) 13)

3 = Temperature + Humidity + Air quality 13)

4 = T.+ Air quality (damper, fan)

5 = T + Air quality + air cooling

6 = T + Air quality + 2nd air cooling

M

 

M

M

M

M

M

 

M

M

M

M

P258

P45110)

Humidity control strategy (RDG2..KN)

2

1 = With setpoint shift

2 = With setpoint shift + external equipment (humid / dehum)

M

M

P450, P258

P453 13) 16)

Indoor air quality damper (RDG2..KN)

1 14)

1 = DC 0...10 V (U1)

2 = On/Off (normally open)

3 = On/Off (normally closed)

P450

P454 13) 16)

IAQ damper P-band Xp (RDG2..KN)

400 ppm (CO2)

10…2000 ppm (CO2)

P450

P455 13) 16)

Minimum damper position (RDG2..KN)

0 %

0…P457

P450

P456 13) 16)

IAQ fan P-band Xp (RDG2..KN)

400 ppm (CO2)

10…2000 ppm (CO2)

P450

P457 16)

Maximum damper position

100 %

P455...100 %

P450, P453

P458 17)

Fan during IAQ control

ON

ON = Enabled

OFF = Disabled

P450

P46110)

T setpoint shift (humidity) (RDG2..KN)

3 K

-3…3 K

M

M

P450, P258

Side Features

P500

NFC

ON

ON = Enabled

OFF = Disabled

P50110)

Service filter

---

--- (OFF), 100…9900 h

M

M

P350, P258

P502

Password

OFF

ON = Enabled

OFF = Disabled

P503

Password

000

000…999

P505

Reset parameter setting

OFF

OFF = Disabled

ON = Reload start

P506 18)

Reset device

OFF

OFF = Disabled

ON = Reload start

System

P898

Area address (RDG2..KN)

0

0...15

P899

Line address (RDG2..KN)

2

0...15

P900

Device address 3) (RDG2..KN)

255

1…255

P901

Geographical zone (apartment) 4) (RDG2..KN)

---

---(0), 1...126

P902

Geographical zone (room) 3) (RDG2..KN)

1

---(0), 1...63

P903

Heat distr zone heating coil (RDG2..KN)

---

---(0), 1...31

P904

Refrig distr zone cooling coil (RDG2..KN)

P905

Heat distr zone heating surface (RDG2..KN)

P910

Transformation Precomfort (RDG2..KN)

0

0 = Economy 10)

1 = Comfort

M

M

P258

Note: Appl means application.

1) When P201/P203 = 1/3/5, P204/P205 = 3/5, P057 & P058 are visible.

2) When P150, P153 or P155 = 2 and P001 = 2, P059 & P060 are visible.

3) For KNX version: When P002 ≠ 2 and P005 ≠ ON, P102 is visible.
For standalone version: When P002 = 4, P102 is visible.

4) Only available for application 2-pipe/2-stage.

5) When P201 = 3, P206 is visible; P203 = 3, P207 is visible; P204 = 3, P208 is visible; P205 = 3, P209 is visible.

6) When P201 = 1, P214 is visible; P203 = 1, P215 is visible.

7) When"H/C changeover" function on X1, X2, U1 is selected, P251 is visible.

8) When"External temperature limit (AI)" on X1, X2, U1 is selected, P252 is visible.

9) When application is 4-pipe with 6-port ball valve as changeover and PICV, P400 & P401 are invisible.

10) If P258 = 0 (Subordinate), the parameter values are not visible.

11) Only available for applications 2-pipe, 2-pipe with electric heater and 2-pipe with radiator.

12) If P258 = 0 (Subordinate), the parameter values are visible.

13) The parameters are valid for RDG204KN and RDG264KN.

14) For RDG264KN, the parameter factory setting is 2 for the 4-pipe/2-stage application.

15) For RDG204KN and RDG264KN, values 0 and 2 are visible for P258 = 0 (Subordinate). Values 4…6 are visible for P453 = 1 (DC damper).

16) When P450 = 2...6 and P453 = 1, P457 is visible.

17) When P450 = 2...6, P458 is visible.

18) PL-Link reset device is available only on the HMI of RDG2..0KN index E or higher and RDG2..4KN index C or higher. When P506 = On, all parameters are factory reset including the device address.

19) When P450 = 2…6 with IAQ control and P350 ≠ 0, P109 is visible.

20) When P450 = 2…6 with IAQ control and P453 = 1 (DC damper), P155 is invisible.

21) When P450 = 2…6 with IAQ control, P350 = 1, P351 = 3 and P453 = 1 (DC damper), P402 is visible.

Diagnostics and test

 

Parameter

Name

Range

Dependencies

Diagnostics and test

d01

Application number

0 = (No application)

1 = 2-pipe

2 = 2-pipe with electric heater

3 = 2-pipe with radiator

4 = 4-pipe

5 = 2-pipe / 2-stage

6 = 4-pipe with electric heater

7 = 4-pipe / 2-stage (RDG2..KN)

8 = 4-pipe:6-port H/C

9 = 4-pipe:6-port CO + PICV

10 = 4-pipe 6wv PICV

d02

X1 state

"---" = Function not selected

0 = Not activated (for DI)

1 = Activated (DI)

0…49 °C = Current temp. value (for AI)

00 = H/C Input shorted

100 = H/C Input open

d03

X2 state

"---" = Function not selected

0 = Not activated (for DI)

1 = Activated (DI)

0…49 °C = Current temp. value (for AI)

00 = H/C Input shorted

100 = H/C Input open

d04

U1 state

"---" = Function not selected

0 = Not activated (for DI)

1 = Activated (DI)

2 = Activated (DC input)

3 = Activated (DC output)

0…49 °C = Current temp. value (for AI)

00 = H/C Input shorted

100 = H/C Input open

d05 1)

Test mode for checking the Y1/Y3 actuator's running direction 5)

"---" = No signal on outputs Y1 and Y3

OPE = Output Y1 forced opening

CLO = Output Y3 forced closing

d06 1)

Test mode for checking the Y2/Y4 actuator's running direction 5)

"---" = No signal on outputs Y2 and Y4

OPE = Output Y2 forced opening

CLO = Output Y4 forced closing

d08

Test mode for checking the Q1 output (ex P400 function)

"---" = no signal at output Q1

OPE = output Q1 forced opening

CLO = output Q1 forced closing

d09

Test mode for checking the Q2 output (ex P401 function)

"---" = no signal at output Q2

OPE = output Q2 forced opening

CLO = output Q2 forced closing

d10

Test mode for checking the Q3 output (ex P402 function)

"---" = no signal at output Q3

OPE = output Q3 forced opening

CLO = output Q3 forced closing

d14

Firmware version

v x-x-x is displayed

d15

Unit ID number (Serial number)

Unit ID is displayed (Serial number)

d16

Bootloader version (RDG2..KN)

v x-x-x is displayed

d17

Touch firmware version

v x-x-x is displayed

d18

LCD version

Note: The parameter display depends on the selected application and function.

1) When output type is 3-position/3-wire, d05 and d06 are visible.