Service and expert level parameters
The properties list shows more properties than are supported in ABT Site. The other properties may be required for commissioning with a KNX tool.
The parameter display depends on the selected application and function. Appl means application. Parameter values are only visible when the device is set as Manager (M), Subordinate (S) or both identification (✓).
Parameter | Name | Factory setting | Range | RDG20.. | RDG26.. | Dependencies |
|---|---|---|---|---|---|---|
Service level | ||||||
|
P001 | Control sequence 1) | 2-pipe:
4-pipe: | 0 = Heating only 1 = Cooling only 2 = H/C changeover auto 3 = H/C changeover manual 4 = Heating and cooling | ✓ | ✓ | P002 |
P0024) | Operation via room operating mode selector 1) | 1 | 1 = Auto – Protection / Auto - Comfort – Protection (when there is local scheduler) 2 = Auto - Comfort - Economy - Protection 3 = Auto (Comfort) - Protection Hospitality 4 = Auto - Protection (RDG2..T) | M | M | P001, P005, P258 |
P0034) | Operation via fan operating selector 2) | 0 | 0 = Auto - Manual 1 = Manual 2 = Auto - Manual - Protection 3 = Auto – Protection 4 = Forced ventilation (RDG2x4KN) 5 = Forced ventilation, fan auto-manual (RDG2x4KN) | M | M | P350, P258 |
P004 | Unit | 0 | 0 = °C (parameter in °C) 1 = °F (parameter in °F) | ✓ | ✓ | ‒ |
P0054)6) | Scheduler | RDG2..KN: OFF RDG2..T: ON | ON = Enabled OFF = Disabled | M | M | P002, P258 |
P006 | Measured value correction | 0 K | –5…5 K | ✓ | ✓ | ‒ |
P007 | Humidity value correction (RDG2..KN) | 0 | -10…0…10 % | ✓ | ✓ | ‒ |
P008 | Standard display | 0 | 0 = Room temperature 1 = Setpoint | ✓ | ✓ | ‒ |
P009 | Additional display information RDG200KN, RDG260KN: 0…5 | 0 | 0 = --- (No display) 1 = °C and °F 2 = Outside temperature 3 = Time of day (12 h) 4 = Time of day (24 h) 5 = Humidity 6 = Indoor air quality (numeric) 5) 7 = Indoor air quality (text) 5) 8 = Humidity and IAQ (numeric) 5) 9 = Humidity and IAQ (text) 5) | ✓ | ✓ | ‒ |
P010 | Setpoint concept | 1 | 1 = Comfort concept 2 = Energy saving concept | ✓ | ✓ | P104 |
P0114) | Comfort basic setpoint | 21 °C (70 °F) | 5…40 °C (41…104 °F) | M | M | P258 |
P013 | Comfort setpoint minimum | 5 °C (41 °F) | (P010 = 1): 5 °C (41 °F)...P016-1 K (P010 = 2): 5 °C (41 °F)...P014-1 K | ✓ | ✓ | P010 |
P014 | Comfort setpoint maximum heating | 21 °C (70 °F) | P013+1 K…P015-1 K | ✓ | ✓ | P010 |
P015 | Comfort setpoint minimum cooling | 25 °C (77 °F) | P014+1 K…P016 -1 K | ✓ | ✓ | P010 |
P016 | Comfort setpoint maximum | 35 °C (95 °F) | (P010 = 1): P013 +1 K...40 °C (104 °F) (P010 = 2): P015 +1 K...40 °C (104 °F) | ✓ | ✓ | P010 |
P0174) | Summer time | 1 | OFF 1 = Europe 2 = Australia 3 = New Zealand | M | M | P258 |
P0194) | Economy heating setpoint | 15 °C (59 °F) | --- (0), 5 °C…P020 (41 °F…P020) P020 = 40 °C max. (P020 = 104 °F max.) | M | M | P258 |
P0204) | Economy cooling setpoint | 30 °C (86 °F) | --- (0), P019…40 °C (P019…104 °F) P019 = 5 °C min. (P019 = 41 °F min.) | M | M | P258 |
P0235) 7) | Indoor air quality setpoint (RDG2..KN) | 1000 ppm | 10...2000 ppm | ✓ | ✓ | P450 |
P0244) | Humidity setpoint high (RDG2..KN) | 50 | --- (0), P026 or 20…90 % | M | M | P450, P258 |
P025 | Humidity setpoint high ECO (RDG2..KN) | OFF | --- (0), P026…90 %, or 20…90 % | M | M | P258 |
P0264) | Humidity setpoint low (RDG2..KN) | OFF | --- (0), 20…90 % or P024 | M | M | P450, P258 |
P0273) | Electric heater when cooling | ON | ON: Enabled OFF: Disabled | ✓ | ✓ | Appl |
P0284) | Keypad | 0 | 0 = Unlocked 1 = Auto lock 2 = Manual lock 3 = Auto lock the operating mode 4 = Auto lock the Setpoint shift 5 = Auto lock fan speed 6 = Auto lock operating mode, setpoint shift 7 = Auto lock operating mode, fan speed 8 = Auto lock fan speed, setpoint shift 9 = Auto lock scheduler 10 = Auto lock operating mode, scheduler 11 = Auto lock scheduler, fan speed 12 = Auto lock operating mode, scheduler, fan speed 13 = Auto lock scheduler, setpoint shift 14 = Auto lock operating mode, scheduler, setpoint shift 15 = Auto lock scheduler, fan speed, setpoint shift | M | M | P258 |
P029 | Fan: Dead zone Comfort mode 2) | 0 | 0 = Fan disable 1 = Low speed (Heating and Cooling) 2 = Low speed (Cooling only) 3 = Fan disable Auto & Manual 4 = Low speed Auto & Manual 5 = Low speed Auto & Manual Cooling | ✓ | ✓ | P350 |
P030 | Buzzer function | ON | ON = Enabled OFF = Disabled | ✓ | ✓ | ‒ |
P031 | Language | 1 | 1 = English 2 = Francais (French) 3 = Deutsch (German) 4 = Italiano (Italian) 5 = Espanol (Spanish) 6 = Nederlands (Dutch) 7 = Turkce (Turkish) 8 = Cesky (Czech) 9 = Suomi (Finnish) 10 = Polski (Polish) 11 = Magyar (Hungarian) 12 = Slovenski (Slovak) 13 = (Limba) Romana (Romanian) 14 = Dansk (Danish) 15 = Norsk (Norwegian) | ✓ | ✓ | ‒ |
P0324) | Room operating mode holidays | 0 | 0 = Economy 1 = Protection | M | M | P005, P258 |
Note:
1)P001 cannot be set to 3 if P002 is set to 3, and vice versa.
2) For RDG200KN and RDG260KN: If P350 = 0, P003 is disabled. P029 is invisible. For RDG204KN and RDG264KN: If P350 = 0, P003 is set to 4.
3) Only available when application is 2-pipe with electric heater
4) If P258 = 0 (Subordinate), the parameter values are not available.
5) The parameters are valid for RDG204KN and RDG264KN.
6) Time of day cannot be set via ETS, see Scheduler.
7) If P450 = 2…6 with IAQ control, P023 is visible.
The parameter display depends on the selected application and function. Parameter values are only visible when the device is set as Manager (M), Subordinate (S) or both identification (✓).
Parameter | Name | Factory setting | Range | RDG20.. | RDG26.. | Dependencies |
|---|---|---|---|---|---|---|
Expert level | ||||||
|
Control settings | ||||||
P050 | Heat P-band Xp | 2 K | 0.5…6 K | ✓ | ✓ | P001 |
P051 | Switching differential heating | 1 K | 0.5…6 K | ✓ | ✓ | P001 |
P052 | Cool P-band Xp | |||||
P053 | Switching differential cooling | |||||
P054 | Radiator P-band Xp/switching differential | 2 K | 0.5…6 K | ✓ | ✓ | ‒ |
P05510) | Dead zone Comfort mode | 2 K | 0.5…5 K | M | M | P258 |
P056 | Setpoint differential | 2 K | 0.5…5 K | ✓ | ✓ | ‒ |
P0571) | Integral action time Tn for heating | 45 min | 0...120 min | ✓ | ✓ | P201, P203, P204 |
P0581) | Integral action time Tn for cooling | |||||
P0592)10) | H/C changeover switching point cooling | 16 °C (61 °F) | 5 °C…P060-2 K (41 °F…P060-2 K) | M | M | P001, P150, P153, P155, P258 |
P0602)10) | H/C changeover switching point heating | 28 °C (82 °F) | P059+2 K…40 °C (P059+2 K…104 °F) | M | M | P001, P150, P153, P155, P258 |
P06111) | Setpoint ΔT cooling | --- | --- (0), 1...40 K | ✓ | ✓ | P150, P153, P155 |
P06211) | Setpoint ΔT heating | --- | --- (0), 1...40 K | ✓ | ✓ | P150, P153, P155 |
P063 | Minimum supply air temperature | --- | ---, 0 °C…P064 (32 °F…P064) | ✓ | ✓ | P150, P153, P155 |
P064 | Maximum supply air temperature | --- | ---, P063…50 °C (P063…122 °F) | ✓ | ✓ | P150, P153, P155 |
Mode and setpoints | ||||||
P10010) | Protection heating setpoint | 8 °C (46 °F) | --- (0), 5 °C…P101; (41 °F…P101) | M | M | P258 |
P10110) | Protection cooling setpoint | --- | --- (0), P100…40 °C; (P100…104 °F) | M | M | P258 |
P1023)10) | Temporary Comfort mode | --- | --- (0), 1...360 min | M | M | P002, P005, P258 |
P10310) | Temporary Comfort setpoint | OFF | 0 = Disabled (OFF) 1 = Enabled (ON) 2 = Enabled (ON), excluded Window contact 3 = Enabled (ON), excluded presence detector (include hotel presence) | M | M | P258 |
P10410) | Setpoint display (RDG2..KN) | 1 | 1 = Absolute setpoints 2 = Relative setpoints | M | M | P010 P258 |
P10913) 19) | Outside damper frost protection (RDG2..4KN) | --- | ---; 2...14 °C (36...50 °F) | ✓ | ✓ | P450 |
P11010) | Energy indicator (RDG2..KN) | 1 | OFF = Disabled 1 = Green and Red dimmed out 2 = Green dimmed out / Red fixed 3 = Green and Red fixed | M | M | P258 |
P11110) | Energy indicator range (RDG2..KN) | 2 K | 0…10 K | M | M | P258 |
Inputs | ||||||
P150 | Input X1 RDG2..KN: 0...14 RDG2..T: 0...6 & 9...14 | P150:1 P153: RDG2..KN: 0 P155: RDG200KN, RDG260KN, RDG200T, RDG260T: 3 |
Synco ACS / PCT Go, ETS terminology 0 = --- (no function) 1 = Room / return temperature 2 = H/C changeover 10) 3 = Window contact (DI) 4 = Dewpoint (DI) 5 = Enable electric heater (DI) 6 = Fault input (DI) 7 = Monitor input (DI) 8 = Monitor input temp. (AI) 9 = Supply air temperature (AI) 10 = Presence detector (DI) 10) 11 = External temperature limit (AI) 12 = Coil flow temperature (AI) 13 = Hotel presence detector / card reader (DI) 10) 14 = Coil return temperature (AI) | ✓ ✓ M ✓ ✓ ✓ ✓ ✓ ✓ ✓ M ✓ ✓ M ✓ | ✓ ✓ M ✓ ✓ ✓ ✓ ✓ ✓ ✓ M ✓ ✓ M ✓ | P153: P150, P155 P155: P150, P153 P258 |
P153 | Input X2 RDG2..KN: 0...14 RDG2..T: 0...6 & 9...14 | |||||
P155 20) | Input U1 (RDG200KN&RDG260KN) Input and output U1 (RDG204KN&RDG264KN) RDG2..KN: 0...14 Input X3 (RDG2..T): 0...6 & 9...14 | |||||
|
Desigo ABT Site terminology 0 = --- (no function) 1 = Room temperature control, external or return air temperature sensor 2 = Heating/cooling changeover 10) 3 = Window contact 4 = Dewpoint sensor 5 = Electric heater, enabled 6 = Fault input 7 = Switching state input 8 = Temperature sensor input 9 = Supply air temperature 10 = Presence detector 10) 11 = External temperature sensor, limitation 12 = Coil flow temperature 13 = Presence detector or card reader, hotel 10) 14 = Coil return temperature |
✓ ✓ - ✓ ✓ ✓ ✓ ✓ ✓ ✓ M ✓ ✓ M ✓ |
✓ ✓ - ✓ ✓ ✓ ✓ ✓ ✓ ✓ M ✓ ✓ M ✓ | ||||
P151 | X1: Normal position and sensor | 0 when DI or AI/DI 2 when AI | 0 = Normally Open 1 = Normally Closed 2 = NTC-3K 3 = LG-Ni1000 | ✓ | ✓ | P151: P150 P154: P153 P156: P155 |
P154 | X2: Normal position and sensor | |||||
P156 | U1 (RDG2..KN): Normal position and sensor X3 (RDG2..T): Normal position and sensor | |||||
Outputs | ||||||
P200 | Number of heating / cooling sequences Note: for 2-/4-pipe 2-stage application | 1 | 1 = Heating 2 sequences, cooling 2 sequences 2 = Heating 2 sequences, cooling 1 sequence 3 = Heating 1 sequence, cooling 2 sequences | ✓ | ✓ | d01 |
P201 | RDG20..: Output Y1 (and Y3 for 3-pos) | RDG20..: 4 RDG26..: 5 (6 when application type is 4-pipe with 6-port ball valve) | 1 = 3-position | ✓ | ‒ | ‒ |
2 = On/Off (3 wires) | ✓ | ‒ | ‒ | |||
3 = PWM | ✓ | ‒ | ‒ | |||
4 = On/Off | ✓ | ✓ | ‒ | |||
5 = DC | ‒ | ✓ | ‒ | |||
6 = 6-port valve (DC 0…10 V) | ‒ | ✓ | Appl | |||
7 = 6-port valve (DC 2…10 V) | ‒ | ✓ | Appl | |||
8 = Inverse signal, 6-port valve (DC 10…0 V) | ‒ | ✓ | Appl | |||
9 = Inverse signal 6-port valve (DC 10…2 V) | ‒ | ✓ | Appl | |||
10 = 6-port valve (DC 0... 10 V) 3rd part | ‒ | ✓ | Appl | |||
11 = 6-port valve (DC 2... 10 V) 3rd part | ‒ | ✓ | Appl | |||
P203 | RDG20..: Output Y2 (and Y4 for 3-pos) | RDG20..: 4 RDG26..: 5 | 1 = 3-position | ✓ | ‒ | ‒ |
2 = On/Off (3 wires) | ✓ | ‒ | ‒ | |||
3 = PWM | ✓ | ‒ | ‒ | |||
4 = On/Off | ✓ | ✓ | ‒ | |||
5 = DC | ‒ | ✓ | ‒ | |||
P204 | RDG20..: Output Y3 | RDG20..: 4 RDG26..: 5 | 3 = PWM | ✓ | ‒ | ‒ |
4 = On/Off | ✓ | ✓ | ‒ | |||
5 = DC | ‒ | ✓ | ‒ | |||
P205 | RDG20xKN: Output Y4 Note: for 4-pipe 2-stage application | RDG20..KN: 4 RDG26..KN: 5 | 3 = PWM | ✓ | ‒ | d01 |
4 = On/Off | ✓ | ‒ | d01 | |||
5 = DC | ‒ | ✓ | d01 | |||
P206 5) | PWM algorithm cycle Y1 | 1200 s | 20…3600 s | ✓ | ‒ | P206: P201 P207: P203 P208: P204 P209: P205 |
P2075) | PWM algorithm cycle Y2 | |||||
P2085) | PWM algorithm cycle Y3 | |||||
P2095) | PWM algorithm cycle Y4 (RDG2..KN) | |||||
P210 | On time minimum PWM output | 5 % | 1…20 % | ✓ | ‒ | ‒ |
P211 | Off time minimum PWM output | |||||
P212 | On time minimum 2-pos output | 1 min | 1…20 min | ✓ | ✓ | P400, P401, P402 |
P213 | Off time minimum 2-pos output | |||||
P214 6)) | RDG20..: Actuator running time Y1 and Y3 for 3-pos | 150 s | 20…300 s | ✓ | ‒ | P214: P201 P215: P203 |
P215 6 | RDG20..: Actuator running time Y2 and Y4 for 3-pos | |||||
P217 | RDG26..: Power of electric heater on Q2 | 0 kW | 0.0…1.2 kW | ✓ | ✓ | P203, P204 |
Features | ||||||
P250 | Valve kick | OFF | ON = Enabled OFF = Disabled | ✓ | ✓ | ‒ |
P251 7)10) | Purge time (every 2 hours) | --- | --- (0, Not active), 1…5 min | M | M | P258 |
P252 8) | Flow temp limit floor heating | 28 °C (82 °F) | 10...50 °C (50…122 °F) | ✓ | ✓ | ‒ |
P254 4) | Swap sequences between H and C (2-pipe / 2-stage) | OFF | ON = Enabled OFF = Disabled | ✓ | ✓ | P001 |
P25510) | Track setpoint for cooling depends on outside temperature (RDG2..KN) | OFF | ON = Enabled OFF = Disabled | M | M | P258 |
P256 | Flow limitation in heating mode for PICV (RDG264KN) Note: Available on devices only with previous SW versions | 10 V | 0…10 V | ‒ | ✓ | ‒ |
P258 | Manager/subordinate (M/S) (RDG2..KN) | 1 | 0 = Subordinate 1 = Manager | ✓ | ✓ | ‒ |
P25912) | Subordinate identification (RDG2..KN) | 1 | "---" 1...9 | S | S | P258 |
P260 | PICV: Heating maximal position (RDG26..) | 100 % | 0...100 % | ‒ | ✓ | P001 |
P261 | PICV: Cooling maximal position (RDG26..) | 100 % | 0...100 % | ‒ | ✓ | P001 |
Fan control | ||||||
P350 | Fan control | 1 | 0 = Disabled 1 = Enabled 2 = Heating only 3 = Cooling only 4 = 2nd stage 5 = Heating and 2nd stage cooling 6 = Cooling and 2nd stage heating 7 = 2nd stage Cooling only 8 = 2nd stage Heating only | ✓ | ✓ | ‒ |
P351 | Fan speeds | 3 | 1 = 1-speed fan 2 = 3-speed fan 3 = DC 0...10 V fan | ✓ | ✓ | P350, P201, P203, P204, P400, P401, P402 |
P352 | Fan overrun time | 2-pipe/4-pipe el. Heater: 60 s Other applications: 0 s | 0...600 s | ✓ | ✓ | P350 |
P353 | Fan speed switching point low | 10 % | 1 %...Fan speed 2 (P354) | ✓ | ✓ | P350 |
P354 | Fan speed switching point med | 65 % | Fan speed 1 (P353)…fan speed 3 (P355) | ✓ | ✓ | P350, P351 |
P355 | Fan speed switching point high | 100 % | Fan speed 2 (P354)…100 % | ✓ | ✓ | P350, P351 |
P356 | DC fan switching point | DC: 10 % | DC: 1...100 % | ✓ | ✓ | P350 |
P357 | DC fan speed low min. output | DC: 30 % | DC: 1 %...Fan speed med (P358) | ✓ | ✓ | P350 |
P358 | DC fan speed med output | DC: 60 % | DC: fan speed low (P357)…fan speed high(lower value of P359 and P360) | ✓ | ✓ | P350 |
P359 | DC fan speed high max. out. heat | DC: 80 % | DC: fan speed med (P358)…100 % | ✓ | ✓ | P350 |
P360 | DC fan speed high max. out.cool | |||||
P361 | Fan start kick | ON | ON: Enabled OFF: Disabled | ✓ | ✓ | P350 |
P362 | On time minimum fan | 2 min | 1...6 min | ✓ | ✓ | P350 |
P363 | Periodic fan kick Comfort | --- | 1…89 min, --- (0) | ✓ | ✓ | P350 |
P364 | Periodic fan kick Economy | --- | 0…359 min, --- | ✓ | ✓ | P350 |
P365 | Fan start delay | 0 s | 0...360 s | ✓ | ✓ | P350 |
P366 | Fan start, minimum water temperature | 30 °C | --- (0),5…60 °C | ✓ | ✓ | P350 Input |
Relay functions | ||||||
P400 9) | Output Q1 function RDG2..KN: 0...8 RDG2..T: 0...6 | 0 | 0 = No function 1 = Switch OFF in Protection 2 = Switch ON in Heat/Cool demand 3 = Switch ON in Heat demand 4 = Switch ON in Cool demand 5 = Heating sequence active 6 = Cooling sequence active 7 = External dehumidifier control 10) 8 = External humidifier control 10) | ✓ ✓ ✓ ✓ ✓ ✓ ✓ M M | ✓ ✓ ✓ ✓ ✓ ✓ ✓ M M | P350, P351, P258 |
P401 9) | Output Q2 function RDG2..KN: 0...8 RDG2..T: 0...6 | |||||
P402 21) | Output Q3 function RDG2..KN: 0...8 RDG2..T: 0...6 | |||||
Controller | ||||||
P45015) | Control strategy (RDG2..KN) | RDG200KN & RDG260KN: 0
RDG204KN & RDG264KN: 2 | 0 = Temperature (T) 1 = Temperature (T) + Relative humidity (r.h.) 2 = Temperature (T) + Air quality (IAQ) 13) 3 = Temperature + Humidity + Air quality 13) 4 = T.+ Air quality (damper, fan) 5 = T + Air quality + air cooling 6 = T + Air quality + 2nd air cooling | ✓ M
✓ M M M M | ✓ M
✓ M M M M | P258 |
P45110) | Humidity control strategy (RDG2..KN) | 2 | 1 = With setpoint shift 2 = With setpoint shift + external equipment (humid / dehum) | M | M | P450, P258 |
P453 13) 16) | Indoor air quality damper (RDG2..KN) | 1 14) | 1 = DC 0...10 V (U1) 2 = On/Off (normally open) 3 = On/Off (normally closed) | ✓ | ✓ | P450 |
P454 13) 16) | IAQ damper P-band Xp (RDG2..KN) | 400 ppm (CO2) | 10…2000 ppm (CO2) | ✓ | ✓ | P450 |
P455 13) 16) | Minimum damper position (RDG2..KN) | 0 % | 0…P457 | ✓ | ✓ | P450 |
P456 13) 16) | IAQ fan P-band Xp (RDG2..KN) | 400 ppm (CO2) | 10…2000 ppm (CO2) | ✓ | ✓ | P450 |
P457 16) | Maximum damper position | 100 % | P455...100 % | ✓ | ✓ | P450, P453 |
P458 17) | Fan during IAQ control | ON | ON = Enabled OFF = Disabled | ✓ | ✓ | P450 |
P46110) | T setpoint shift (humidity) (RDG2..KN) | 3 K | -3…3 K | M | M | P450, P258 |
Side Features | ||||||
P500 | NFC | ON | ON = Enabled OFF = Disabled | ✓ | ✓ | ‒ |
P50110) | Service filter | --- | --- (OFF), 100…9900 h | M | M | P350, P258 |
P502 | Password | OFF | ON = Enabled OFF = Disabled | ✓ | ✓ | ‒ |
P503 | Password | 000 | 000…999 | ✓ | ✓ | ‒ |
P505 | Reset parameter setting | OFF | OFF = Disabled ON = Reload start | ✓ | ✓ | ‒ |
|
P506 18) |
Reset device |
OFF |
OFF = Disabled ON = Reload start |
✓ |
✓ |
‒ |
System | ||||||
P898 | Area address (RDG2..KN) | 0 | 0...15 | ✓ | ✓ | ‒ |
P899 | Line address (RDG2..KN) | 2 | 0...15 | ✓ | ✓ | ‒ |
P900 | Device address 3) (RDG2..KN) | 255 | 1…255 | ✓ | ✓ | ‒ |
P901 | Geographical zone (apartment) 4) (RDG2..KN) | --- | ---(0), 1...126 | ✓ | ✓ | ‒ |
P902 | Geographical zone (room) 3) (RDG2..KN) | 1 | ---(0), 1...63 | ✓ | ✓ | ‒ |
P903 | Heat distr zone heating coil (RDG2..KN) | --- | ---(0), 1...31 | ✓ | ✓ | ‒ |
P904 | Refrig distr zone cooling coil (RDG2..KN) | |||||
P905 | Heat distr zone heating surface (RDG2..KN) | |||||
P910 | Transformation Precomfort (RDG2..KN) | 0 | 0 = Economy 10) 1 = Comfort | M ✓ | M ✓ | P258 |
Note: Appl means application.
1) When P201/P203 = 1/3/5, P204/P205 = 3/5, P057 & P058 are visible.
2) When P150, P153 or P155 = 2 and P001 = 2, P059 & P060 are visible.
3) For KNX version: When P002 ≠ 2 and P005 ≠ ON, P102 is visible.
For standalone version: When P002 = 4, P102 is visible.
4) Only available for application 2-pipe/2-stage.
5) When P201 = 3, P206 is visible; P203 = 3, P207 is visible; P204 = 3, P208 is visible; P205 = 3, P209 is visible.
6) When P201 = 1, P214 is visible; P203 = 1, P215 is visible.
7) When"H/C changeover" function on X1, X2, U1 is selected, P251 is visible.
8) When"External temperature limit (AI)" on X1, X2, U1 is selected, P252 is visible.
9) When application is 4-pipe with 6-port ball valve as changeover and PICV, P400 & P401 are invisible.
10) If P258 = 0 (Subordinate), the parameter values are not visible.
11) Only available for applications 2-pipe, 2-pipe with electric heater and 2-pipe with radiator.
12) If P258 = 0 (Subordinate), the parameter values are visible.
13) The parameters are valid for RDG204KN and RDG264KN.
14) For RDG264KN, the parameter factory setting is 2 for the 4-pipe/2-stage application.
15) For RDG204KN and RDG264KN, values 0 and 2 are visible for P258 = 0 (Subordinate). Values 4…6 are visible for P453 = 1 (DC damper).
16) When P450 = 2...6 and P453 = 1, P457 is visible.
17) When P450 = 2...6, P458 is visible.
18) PL-Link reset device is available only on the HMI of RDG2..0KN index E or higher and RDG2..4KN index C or higher. When P506 = On, all parameters are factory reset including the device address.
19) When P450 = 2…6 with IAQ control and P350 ≠ 0, P109 is visible.
20) When P450 = 2…6 with IAQ control and P453 = 1 (DC damper), P155 is invisible.
21) When P450 = 2…6 with IAQ control, P350 = 1, P351 = 3 and P453 = 1 (DC damper), P402 is visible.
Diagnostics and test
Parameter | Name | Range | Dependencies |
|---|---|---|---|
Diagnostics and test | |||
|
d01 | Application number | 0 = (No application) 1 = 2-pipe 2 = 2-pipe with electric heater 3 = 2-pipe with radiator 4 = 4-pipe 5 = 2-pipe / 2-stage 6 = 4-pipe with electric heater 7 = 4-pipe / 2-stage (RDG2..KN) 8 = 4-pipe:6-port H/C 9 = 4-pipe:6-port CO + PICV 10 = 4-pipe 6wv PICV | ‒ |
d02 | X1 state | "---" = Function not selected 0 = Not activated (for DI) 1 = Activated (DI) 0…49 °C = Current temp. value (for AI) 00 100 | ‒ |
d03 | X2 state | "---" = Function not selected 0 = Not activated (for DI) 1 = Activated (DI) 0…49 °C = Current temp. value (for AI) 00 100 | ‒ |
d04 | U1 state | "---" = Function not selected 0 = Not activated (for DI) 1 = Activated (DI) 2 = Activated (DC input) 3 = Activated (DC output) 0…49 °C = Current temp. value (for AI) 00 100 | ‒ |
d05 1) | Test mode for checking the Y1/Y3 actuator's running direction 5) | "---" = No signal on outputs Y1 and Y3 OPE = Output Y1 forced opening CLO = Output Y3 forced closing | ‒ |
d06 1) | Test mode for checking the Y2/Y4 actuator's running direction 5) | "---" = No signal on outputs Y2 and Y4 OPE = Output Y2 forced opening CLO = Output Y4 forced closing | ‒ |
d08 | Test mode for checking the Q1 output (ex P400 function) | "---" = no signal at output Q1 OPE = output Q1 forced opening CLO = output Q1 forced closing | ‒ |
d09 | Test mode for checking the Q2 output (ex P401 function) | "---" = no signal at output Q2 OPE = output Q2 forced opening CLO = output Q2 forced closing | ‒ |
d10 | Test mode for checking the Q3 output (ex P402 function) | "---" = no signal at output Q3 OPE = output Q3 forced opening CLO = output Q3 forced closing | ‒ |
d14 | Firmware version | v x-x-x is displayed | ‒ |
d15 | Unit ID number (Serial number) | Unit ID is displayed (Serial number) | ‒ |
d16 | Bootloader version (RDG2..KN) | v x-x-x is displayed | ‒ |
d17 | Touch firmware version | v x-x-x is displayed | ‒ |
d18 | LCD version | ‒ | ‒ |
Note: The parameter display depends on the selected application and function.
1) When output type is 3-position/3-wire, d05 and d06 are visible.
= H/C Input shorted
= H/C Input open