SELMS_4V: Multistate selector for four values

The SELM_4V (FC443) blocks switches multistate inputs to the outputs in dependence of a selector and a corresponding input selector condition. The multiple inputs have two multistate values and two real values available.

Functionality

The block switches that input [In0xx]-[In7xx] whose selector condition [KCnd0]-[KCnd7] matches selector [K] to output [Outxx]. If there is no match, 'default value' [Defxx] is output at outputs [Outxx].

If several input selector conditions [KCnd0]...[KCnd7] are the same and selector [K] corresponds to a condition, input [In0xx]-[In7xx] of the lowest selector condition [KCnd0xx]-[KCnd7xx] is switched to output [Outxx].

Inputs

Pin

E

Description

K

pa

Selector.

Value range: 1...16 (Off...Stage15)

Multistate (Default value= 1)

KCnd0..KCnd7

pa

Selector condition for input 0.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

In0Ms1

pa

Input 0, multistate 1.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

In0Ms2

pa

Input 0, multistate 2.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

In0R1

pa

Input 0, real 1.

Real (Default value= 0.0)

In0R2

pa

Input 0, real 2.

Real (Default value= 0.0)

KCnd1..KCnd7

pa

Selector condition for input 1..7.

In1Msx..In7Msx

pa

Input 1..7, multistate 1 and 2.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

In1Rx..In7Rx

pa

Input 1..7, real 1 and 2.

Real (Default value= 0.0)

DefMs1

pa

Default value, multistate 1.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

DefMs2

pa

Default value, multistate 2.

Value range: 1...16 (Off...Stage15)

Multistate (Default value = 1)

DefR1

pa

Default value, Real 1.

Real (Default value= 0.0)

DefMs1

pa

Default value, Real 2.

Real (Default value= 0.0)

Outputs

Pin

E

Description

OutMs1

a

Multistate output 1.

Multistate (Default value = 1)

OutMs2

a

Multistate output 2.

Multistate (Default value = 1)

OutR1

a

Real output 1.

Real (Default value= 0.0)

OutR2

a

Real output 2.

Real (Default value= 0.0)

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).