SELMS_MS: Multistate selector for multistate value
The SELMS_MS (FC430) blocks switches one of 8 multistate inputs to the output in dependence of a selector and a corresponding input selector condition.
Functionality
The block switches that input [In0]...[In7] whose selector condition [KCnd0]...[KCnd7] matches selector [K] to output [Out]. If there is no match, default value [DefVal] is output at output [Out].
If several input selector conditions [KCnd0]...[KCnd7] are the same and selector [K] corresponds to a condition, input [In0]...[In7] of the lowest selector condition [KCnd0]...[KCnd7] is switched to output [Out].
Inputs
Pin | E | Description |
K | pa | Selector |
In0..In7 | pa | Inputs 0..7. |
KCnd0..KCnd7 | pa | Selector condition for input 0..7. |
DefVal | pa | Default value. |
Outputs
Pin | E | Description |
Out | a | Output |
Input values
Pin | Description | Data Type | Default value | E.g. Engineering unit or Text group | Min. | Max. |
K | Selector | Multistate | 1 (Off) | Off...Stage15 |
|
|
KCnd0..KCnd7 | Selector cond. for input 0 | Multistate | 1 (Off) | Off...Stage15 |
|
|
In0..In7 | Input 0 | Multistate | 1 (Off) | Off...Stage15 |
|
|
DefVal | Default value | Multistate | 1 (Off) | Off...Stage15 |
|
|
Output values
Pin | Description | Data Type | Default value | E.g. Engineering unit or Text group | Min. | Max. |
Out | Output | Multistate | 1 (Off) | Off...Stage15 |
|
|
Process response
Standard (see General rules and information).
Troubleshooting
Standard (see General rules and information).