SWI_2P: On/off switch with adjustable switch-on and switch-off point

The SWI_2P (FB411) block generates a binary output signal after a comparison between the input signal and the switch-on and switch-off point.

Functionality

The block generates the binary output signal [Out] after a comparison between the input signal [In] and the switch-on point [SwiOnPt] and the switch-off point [SwiOffPt].

The relative mutual position of the switch-on point [SwiOnPt] and the switch-off point [SwiOffPt] defines the direction of control action.

The block function can be fully enabled or disabled via pin [EnFnct].

Action: direct

 

Action: reverse

 

Inputs

Pin

E

Description

EnFnct

p

Enable function.

1 (Yes) = The function is enabled.

0 (No) = The function is disabled.

In

pa

Input.

SwiOnPt

pa

Switch-on point.

The switch-on and switch-off points define the switching frequency and the direction of control action.

The direction of control action is direct if [SwiOnPt] ≥ [SwiOffPt].

The direction of control action is reverse if [SwiOnPt] < [SwiOffPt].

SwiOffPt

pa

Switch-off point.

The switch-on and switch-off points define the switching frequency and the direction of control action (see [SwiOnPt]).

Outputs

Pin

E

Description

Out

a

Output.

Input values

Pin

Description

Data type

Default value

E.g. Engineering unit or Text group

Min.

Max.

EnFnct

Enable function.

Boolean

1 (Yes)

No, Yes

 

 

In

Input.

Real

0.0

 

-3.403E38

3.403E38

SwiOnPt

Switch-on point.

Real

0.0

 

-3.403E38

3.403E38

SwiOffPt

Switch-off point.

Real

0.0

 

-3.403E38

3.403E38

Output values

Pin

Description

Data type

Default value

E.g. Engineering unit or Text group

Min.

Max.

Out

Output.

Boolean

0 (Off)

Off, On

 

 

Application

If a setpoint with settable position relative to the switch-on and switch-off point for On/Off switches/On/Off controllers represents a known or adjustable variable, block SWI_2PH (FB432) is to be used.

Process response

The block is processed with the values at the inputs, starting from the first cycle in the process. During start-up, if the value [In] is between the switch-on and switch-off point, the output is set to [Out] = 0 (Off).

Troubleshooting

Standard (see General rules and information).