TPHI_HX: Temperature & relative humidity to enthalpy & absolute humidity

The TPHI_HX (FB421) block calculates the following values from the temperature and relative humidity (as per the h,x diagram):

The following functions are integrated in the block:

TPHI_HX_SiUn (FB421), TPHI_HX_UsUn (FB794), TPHI_HX_CaUn (FB789)

 

Inputs

Pin

E

Description

T

pa

Temperature

HuRel

pa

Relative humidity

AP

pa

Air pressure

Measured value for air pressure or constant value. See Engineering.

EnTWet

pa

Enable wetbulb temperature

Outputs

Pin

E

Description

E

pa

Enthalpy

Enthalpy of air converted from the inputs.

HuAbs

a

Absolute humidity

Absolute humidity of air converted from the inputs.

TDwp

a

Dew point temperature

Dew point temperature of air calculated from the inputs. The dew point temperature can be used as a setpoint in dew point control or for monitoring the surfaces where air possibly condenses.

EDwp

a

Enthalpy at dew point

ADen

a

Air density

Air density calculated from the inputs.

TWet

a

Wetbulb temperature

Wetbulb temperature for the air calculated from the inputs.

Input values

Pin

Description

Data type

Default value

E.g. Engineering unit or Text group

Min.

Max.

T

Temperature

Real

20.0

°C

-50.0

150.0

68.0

°F

-58.0

302.0

HuRel

Relative humidity

Real

50.0

%RH

0.0

100.0

AP

Air pressure

Real

0.96

bar

0.0

4.0

28.35

inHg

0.0

118.1

EnTWet

Enable wetbulb temp.

Boolean

0 (No)

No, Yes

 

 

Output values

Pin

Description

Data type

Default value

E.g. Engineering unit or Text group

Min.

Max.

E

Enthalpy

Real

40.0

kJ/kg

0.0

100.0

17.2

Btu/lb

0.0

43.0

HuAbs

Absolute humidity

Real

7.8

g/kg

0.0

50.0

0.008

lb/lbda

0.0

0.05

TDwp

Dew point temperature

Real

9.5

°C

-50.0

150.0

49.1

°F

-58.0

302.0

EDwp

Enthalpy at dew point

Real

29.0

kJ/kg

-50.0

150.0

12.5

Btu/lb

-21.5

64.5

ADen

Air density

Real

1.2

kg/m3

0.0

5.0

0.075

lb/ft3

0.0

0.312

TWet

Wetbulb temp.

Real

13.8

°C

-3.402822E38

3.402822E38

56.9

°F

-3.402822E38

3.402822E38

Engineering

Parameterizing the air pressure [AP]

If the air pressure is not available as a measured variable, it can be defined as a constant. Air pressure decreases at increasing altitude above sea level; the constant thus needs to be defined in dependence of the altitude above sea level:

Altitude (m)

AP (bar)

 

Altitude (ft)

AP (inHg)

0

1.013

0

29.91

300

0.978

1000

29.34

600

0.943

2000

28.29

900

0.910

3000

27.30

1200

0.877

4000

26.31

1500

0.846

5000

25.38

1800

0.815

6000

24.45

2100

0.785

7000

23.52

Application

Dew point control

The block can be used for instance to calculate the setpoint for dew point control. The set room air state is entered at inputs [T] and [HuRel]. The block determines the dew point temperature [TDwp] of the air state, suited as a setpoint for the dew point temperature controller.

Dew point supervision

In a room supply air cascade control, the block can be used for dew point supervision. The supply air temperature is entered at input [T]; a fixed value such as 90% is set for input [HuRel]. The output [TDwp] can be interconnected as a supply air limit value [SpMinSu] to CAS_CTR.

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).