QMX3.P36
This section describes room operator units QMX3.P36 for specific applications.
For the description of properties see chapter "KNX PL-Link devices" in the Hardware catalog.
Devices in the library
The devices in the library represent layouts with settings for specific applications. The name of the device in the library refers to its application.
The unit system of the library and the selected Page layout determine the unit for the display of the temperature.
The device names are independent of the unit system of the library. If units are part of the device name, only SI units are used.
The following devices are included in the library:
Name | Name of selected Page Layout |
|---|---|
Multi Page Layouts | |
ROpUn_QMX3.P36_GenHvac_Multi-page | M_SetC_0_allPages_01 |
Single Page Layouts | |
ROpUn_QMX3.P36_Fcu_FanSpd-SpTRAbs-HCSta-PscBtn | S_Set04_2_AbsTempSetpoint_FanSpeed_Occup_01 |
ROpUn_QMX3.P36_Fcu_FanSpd-SpTRRel,C-HCSta-PscBtn | S_Set04_7_RelTempSetpoint_FanSpeed_Occup_01 |
ROpUn_QMX3.P36_Fcu_FanSpd-SpTRRel,K-HCSta-PscBtn | S_Set04_7K_RelTempSetpoint_FanSpeed_Occup_01 |
ROpUn_QMX3.P36_Fcu_FanSpd-TR-SpTRRel,C-PscBtn | S_Set04_8_RoomTemp_RelTempSetpoint_FanSpeed_Occup_01 |
ROpUn_QMX3.P36_Fcu_FanSpd-TR-SpTRRel,K-PscBtn | S_Set04_8K_RoomTemp_RelTempSetpoint_FanSpeed_Occup_01 |
ROpUn_QMX3.P36_GenHvac_Single-page | S_Set01_0_RelTempSetpoint_RoomTemp_01 |
ROpUn_QMX3.P36_Rcg/Rad_SpTRAbs-HCSta-PscBtn | S_Set04_0_AbsTempSetpoint_Occup_01 |
ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,C-HCSta-PscBtn | S_Set04_1_RelTempSetpoint_Occup_01 |
ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,K | S_Set04_13K_RelTempSetpoint_01 |
ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,K-HCSta-PscBtn | S_Set04_4K_RelTempSetpoint_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRAbs-AQual-PscBtn | S_Set04_11_AQ_AbsTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRAbs-HCSta-PscBtn | S_Set04_5_AbsTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,C-AQual-PscBtn | S_Set04_12_AQ_RelTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,C-HCSta-PscBtn | S_Set04_6_RelTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,K-AQual-PscBtn | S_Set04_12K_AQ_RelTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,K-HCSta-PscBtn | S_Set04_6K_RelTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRAbs-PscBtn | S_Set04_9_RoomTemp_AbsTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRRel,C-PscBtn | S_Set04_10_RoomTemp_RelTempSetpoint_RpdVent_Occup_01 |
ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRRel,K-PscBtn | S_Set04_10K_RoomTemp_RelTempSetpoint_RpdVent_Occup_01 |
Page Layouts
The tables below contain the page layouts for QMX3.P36 room operator units in the library and their use with suitable application functions. Room operator units from the library already include a certain page layout fitting the application. The preconfigured layout can be exchanged for another layout in the hardware and network editor.
Multi Page Layouts
Name | Application | Pages | ||||
|---|---|---|---|---|---|---|
Page 1 | Page 2 | Page 3 | Page 4 | Page 5 | ||
M_SetA_1_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Settings | (not used) | (not used) |
|
|
| ||||
M_SetA_3_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Settings | Room Mode | (not used) |
|
|
|
| |||
M_SetA_4_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Relative temperature set-point in [°C] or [°F] Actual temperature in [°C] or [°F] | Setting | Room Mode | (not used) |
|
|
|
| |||
M_SetA_5_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Settings | Occupancy | (not used) |
|
|
|
| |||
M_SetA_20_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Relative temperature set-point in [°C] or [°F] Actual temperature in [°C] or [°F] | Settings | Room Mode | Date |
|
|
|
|
| ||
M_SetB_0_AbsTemp_ | Fcu01 | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Fan Speed | Settings | (not used) | (not used) |
|
|
| ||||
M_SetB_1_Scene_ | Fcu01 | Scene
| Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Fan Speed
| Settings
| (not used) |
|
|
|
| |||
M_SetB_2_Scene_ | Fcu01 | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Fan Speed | Settings | Room Mode |
|
|
|
|
| ||
M_SetB_3_Scene_ | Fcu01, Rapid Ventilation | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Rapid Ventilation | Settings | Room Mode |
|
|
|
|
| ||
M_SetB_4_RelTemp_ | Fcu01 | Set-point relative temperature in [°C] or [°F] Actual temperature in [°C] or [°F] | Fan Speed | Settings | (not used) | (not used) |
|
|
| ||||
M_SetB_5_Scene_ | Fcu01 | Scene
| Set-point relative temperature in [°C] or [°F] Actual temperature in [°C] or [°F] | Fan Speed
| Settings
| (not used) |
|
|
|
| |||
M_SetB_6_Scene_ | Fcu01 | Scene | Setpoint relative temperature in [°C] or [°F] Actual temperature in [°C] or [°F] | Fan Speed | Settings | Room Mode |
|
|
|
|
| ||
M_SetB_7_Scene_ | Fcu01, Rapid Ventilation | Scene | Set-point relative temperature in [°C] or [°F] Actual temperature in [°C] or [°F] | Rapid Ventilation | Settings | Room Mode |
|
|
|
|
| ||
M_SetB_8_Scene_ | Fcu01 | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Fan Speed | Settings | Occupancy |
|
|
|
|
| ||
M_SetB_9_Scene_ | Fcu01, Rapid Ventilation | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Rapid Ventilation | Settings | Occupancy |
|
|
|
|
| ||
M_SetB_10_Scene_ | Fcu01, Rapid Ventilation | Scene | Set-point absolute temperature in [°C] or [°F] Plant state (Heating or Cooling) | Rapid Ventilation | Settings | (not used) |
|
|
|
| |||
M_SetB_11_Scene_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 | Scene | Relative temperature set-point in [°C] or [°F] Actual temperature in [°C] or [°F] | Settings
| (not used) | (not used) |
|
|
| ||||
M_SetB_12_Scene_ | Fcu01, Rapid Ventilation | Scene | Relative temperature set-point in [°C] or [°F] Actual temperature in [°C] or [°F] | Rapid Ventilation | Settings | (not used) |
|
|
|
| |||
M_SetB_20_RelTemp_ | Fcu01 | Relative temperature set-point in [°C] or [°F] Actual temperature in [°C] or [°F] | Fan Speed | Settings | Date | (not used) |
|
|
|
| |||
M_SetC_0_allPages | - | All existing pages in one template Information pages for:
| ||||
Single Page Layouts
Name | Application | Layout | Lines | |||
|---|---|---|---|---|---|---|
Line 1 | Line 2 | Line 3 | Line 4 | |||
S_Set01_0_RelTempSetpoint_RoomTemp | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | (not used) | (not used) |
S_Set01_1_AbsTempSetpoint_OpMode | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | (not used) | Operating Mode |
S_Set01_4_AbsTempSetpoint_Scene | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | (not used) | Scene |
S_Set01_5_RelTempSetpoint_OpMode | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | (not used) | Operating Mode |
S_Set01_6_RelTempSetpoint_Scene | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | (not used) | Scene |
S_Set01_20_DateTime_RelTempSetpoint_ | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Date | Set-point relative temperature in [°C] or [°F] | Actual temperature in [°C] or [°F] | (not used) |
S_Set02_0_AbsTempSetpoint_FanSpeed | Fcu01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Fan Speed | (not used) |
S_Set02_1_AbsTempSetpoint_FanSpeed_ | Fcu01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Fan Speed | Operating Mode |
S_Set02_4_AbsTempSetpoint_FanSpeed_ | Fcu01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Fan Speed | Scene |
S_Set02_5_RelTempSetpoint_FanSpeed | Fcu01 |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Fan Speed | (not used) |
S_Set02_6_RelTempSetpoint_FanSpeed_ | Fcu01 |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Fan Speed | Operating Mode |
S_Set02_7_RelTempSetpoint_FanSpeed_ | Fcu01 |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | Fan Speed | Scene |
S_Set02_8_ActRoomTemp_RelTempSetpoint_FanSpeed | Fcu01 |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | Fan Speed | (not used) |
S_Set02_20_DateTime_ | Fcu01 |
| Date | Set-point relative temperature in [°C] or [°F] | Actual temperature in [°C] or [°F] | Fan Speed |
S_Set03_0_AbsTempSetpoint_Prolongation | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | (not used) | Prolongation |
S_Set03_1_AbsRoomTemp_FanSpeed_ | Fcu01, Rapid Ventilation |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Fan Speed | Prolongation |
S_Set03_2_RelTempSetpoint_Prolongation | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | (not used) | Prolongation |
S_Set03_3_RelTempSetpoint_FanSpeed_ | Fcu01, Rapid Ventilation |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Fan Speed | Prolongation |
S_Set04_0_AbsTempSetpoint_Occup | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | (not used) | Occupancy |
S_Set04_1_RelTempSetpoint_Occup | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | (not used) | Occupancy |
S_Set04_2_AbsTempSetpoint_FanSpeed_ | Fcu01, Rapid Ventilation |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Fan Speed | Occupancy |
S_Set04_3_RelTempSetpoint_FanSpeed_ | Fcu01, Rapid Ventilation |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Fan Speed | Occupancy |
S_Set04_4_AbsTempSetpoint | Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01 |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | (not used) | (not used) |
S_Set04_4_RelTempSetpoint_Occup | Rad, Ccg |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Actual temperature in [°C] or [°F] | Occupancy |
S_Set04_4K_RelTempSetpoint_Occup | Rad, Ccg |
| Plant state (Heating or Cooling) | Set-point relative temperature in [K] or [°F] | Actual temperature in [°C] or [°F] | Occupancy |
S_Set04_5_AbsTempSetpoint_RpdVent_ | VAV |
| Plant state (Heating or Cooling) | Set-point absolute temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_6_RelTempSetpoint_RpdVent_ | VAV |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_6K_RelTempSetpoint_RpdVent_ | VAV |
| Plant state (Heating or Cooling) | Set-point relative temperature in [K] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_7_RelTempSetpoint_FanSpeed_ | FCU |
| Plant state (Heating or Cooling) | Set-point relative temperature in [°C] or [°F] | Fan Speed | Occupancy |
S_Set04_7K_RelTempSetpoint_FanSpeed_ | FCU |
| Plant state (Heating or Cooling) | Set-point relative temperature in [K] or [°F] | Fan Speed | Occupancy |
S_Set04_8_RoomTemp_RelTempSetpoint_FanSpeed_ | FCU |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | Fan Speed | Occupancy |
S_Set04_8K_RoomTemp_RelTempSetpoint_FanSpeed_ | FCU |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [K] or [°F] | Fan Speed | Occupancy |
S_Set04_9_RoomTemp_AbsTempSetpoint_RpdVent_ | VAV |
| Actual temperature in [°C] or [°F] | Set-point absolute temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_10_RoomTemp_RelTempSetpoint_RpdVent_ | VAV |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_10K_RoomTemp_RelTempSetpoint_RpdVent_ | VAV |
| Actual temperature in [°C] or [°F] | Set-point relative temperature in [K] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_11_AQ_AbsTempSetpoint_RpdVent_ | VAV |
| Room Air Quality | Set-point absolute temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_12_AQ_RelTempSetpoint_RpdVent_ | VAV |
| Room Air Quality | Set-point relative temperature in [°C] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_12K_AQ_RelTempSetpoint_RpdVent_ | VAV |
| Room Air Quality | Set-point relative temperature in [K] or [°F] | Rapid Ventilation | Occupancy |
S_Set04_13K_RelTempSetpoint | Rad, Ccg |
| (not used) | Set-point relative temperature in [K] or [°F] | (not used) | (not used) |
S_Set05_0_Scene | Only Scene, Meeting Room |
| Scene | Scene names | ||