QMX3.P36

This section describes room operator units QMX3.P36 for specific applications.

For the description of properties see chapter "KNX PL-Link devices" in the Hardware catalog.

Devices in the library

The devices in the library represent layouts with settings for specific applications. The name of the device in the library refers to its application.

The unit system of the library and the selected Page layout determine the unit for the display of the temperature.

The device names are independent of the unit system of the library. If units are part of the device name, only SI units are used.

The following devices are included in the library:

Name

Name of selected Page Layout

Multi Page Layouts

ROpUn_QMX3.P36_GenHvac_Multi-page

M_SetC_0_allPages_01

Single Page Layouts

ROpUn_QMX3.P36_Fcu_FanSpd-SpTRAbs-HCSta-PscBtn

S_Set04_2_AbsTempSetpoint_FanSpeed_Occup_01

ROpUn_QMX3.P36_Fcu_FanSpd-SpTRRel,C-HCSta-PscBtn

S_Set04_7_RelTempSetpoint_FanSpeed_Occup_01

ROpUn_QMX3.P36_Fcu_FanSpd-SpTRRel,K-HCSta-PscBtn

S_Set04_7K_RelTempSetpoint_FanSpeed_Occup_01

ROpUn_QMX3.P36_Fcu_FanSpd-TR-SpTRRel,C-PscBtn

S_Set04_8_RoomTemp_RelTempSetpoint_FanSpeed_Occup_01

ROpUn_QMX3.P36_Fcu_FanSpd-TR-SpTRRel,K-PscBtn

S_Set04_8K_RoomTemp_RelTempSetpoint_FanSpeed_Occup_01

ROpUn_QMX3.P36_GenHvac_Single-page

S_Set01_0_RelTempSetpoint_RoomTemp_01

ROpUn_QMX3.P36_Rcg/Rad_SpTRAbs-HCSta-PscBtn

S_Set04_0_AbsTempSetpoint_Occup_01

ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,C-HCSta-PscBtn

S_Set04_1_RelTempSetpoint_Occup_01

ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,K

S_Set04_13K_RelTempSetpoint_01

ROpUn_QMX3.P36_Rcg/Rad_TR-SpTRRel,K-HCSta-PscBtn

S_Set04_4K_RelTempSetpoint_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRAbs-AQual-PscBtn

S_Set04_11_AQ_AbsTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRAbs-HCSta-PscBtn

S_Set04_5_AbsTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,C-AQual-PscBtn

S_Set04_12_AQ_RelTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,C-HCSta-PscBtn

S_Set04_6_RelTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,K-AQual-PscBtn

S_Set04_12K_AQ_RelTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-SpTRRel,K-HCSta-PscBtn

S_Set04_6K_RelTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRAbs-PscBtn

S_Set04_9_RoomTemp_AbsTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRRel,C-PscBtn

S_Set04_10_RoomTemp_RelTempSetpoint_RpdVent_Occup_01

ROpUn_QMX3.P36_Vav/Fpb_RpdVnt-TR-SpTRRel,K-PscBtn

S_Set04_10K_RoomTemp_RelTempSetpoint_RpdVent_Occup_01

Page Layouts

The tables below contain the page layouts for QMX3.P36 room operator units in the library and their use with suitable application functions. Room operator units from the library already include a certain page layout fitting the application. The preconfigured layout can be exchanged for another layout in the hardware and network editor.

Multi Page Layouts

Name

Application

Pages

Page 1

Page 2

Page 3

Page 4

Page 5

M_SetA_1_Scene_
AbsTemp_Setting

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Settings

(not used)

(not used)

M_SetA_3_Scene_
AbsTemp_Setting_
RoomMode

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Settings

Room Mode

(not used)

M_SetA_4_Scene_
RelTemp_Setting_
RoomMode

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Relative temperature set-point in [°C] or [°F]

Actual temperature in [°C] or [°F]

Setting

Room Mode

(not used)

M_SetA_5_Scene_
AbsTemp_Setting_
Occupancy

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Settings

Occupancy

(not used)

M_SetA_20_Scene_
RelTemp_Setting_
RoomMode_DateTime

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Relative temperature set-point in [°C] or [°F]

Actual temperature in [°C] or [°F]

Settings

Room Mode

Date
Time

M_SetB_0_AbsTemp_
FanSpeed_Setting

Fcu01

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Fan Speed

Settings

(not used)

(not used)

M_SetB_1_Scene_
AbsTemp_FanSpeed_
Setting

Fcu01

Scene

 

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Fan Speed

 

Settings

 

(not used)

M_SetB_2_Scene_
AbsTemp_FanSpeed_
Setting_RoomMode

Fcu01

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Fan Speed

Settings

Room Mode

M_SetB_3_Scene_
AbsTemp_RpdVenti_
Setting_RoomMode

Fcu01, Rapid Ventilation

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Rapid Ventilation

Settings

Room Mode

M_SetB_4_RelTemp_
FanSpeed_Setting

Fcu01

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Fan Speed

Settings

(not used)

(not used)

M_SetB_5_Scene_
RelTemp_FanSpeed_
Setting

Fcu01

Scene

 

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Fan Speed

 

Settings

 

(not used)

M_SetB_6_Scene_
RelTemp_FanSpeed_
Setting_RoomMode

Fcu01

Scene

Set­point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Fan Speed

Settings

Room Mode

M_SetB_7_Scene_
RelTemp_RpdVentil_
Setting_RoomMode

Fcu01, Rapid Ventilation

Scene

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Rapid Ventilation

Settings

Room Mode

M_SetB_8_Scene_
AbsTemp_FanSpeed_
Setting_Occupancy

Fcu01

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Fan Speed

Settings

Occupancy

M_SetB_9_Scene_
AbsTemp_RpdVenti_
Setting_Occupancy

Fcu01, Rapid Ventilation

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Rapid Ventilation

Settings

Occupancy

M_SetB_10_Scene_
AbsTemp_RpdVentil_
Setting

Fcu01, Rapid Ventilation

Scene

Set-point absolute temperature in [°C] or [°F]

Plant state (Heating or Cooling)

Rapid Ventilation

Settings

(not used)

M_SetB_11_Scene_
RelTemp_Setting

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Scene

Relative temperature set-point in [°C] or [°F]

Actual temperature in [°C] or [°F]

Settings

 

(not used)

(not used)

M_SetB_12_Scene_
RelTemp_RpdVentil_
Setting

Fcu01, Rapid Ventilation

Scene

Relative temperature set-point in [°C] or [°F]

Actual temperature in [°C] or [°F]

Rapid Ventilation

Settings

(not used)

M_SetB_20_RelTemp_
FanSpeed_Setting_
DateTime

Fcu01

Relative temperature set-point in [°C] or [°F]

Actual temperature in [°C] or [°F]

Fan Speed

Settings

Date
Time

(not used)

M_SetC_0_allPages

-

All existing pages in one template

Information pages for:

  • Favorites
  • Comfort Prolongation
  • Occupancy
  • Windows open
  • Date and Time

Single Page Layouts

Name

Application

Layout

Lines

Line 1

Line 2

Line 3

Line 4

S_Set01_0_RelTemp­Setpoint_RoomTemp

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

(not used)

(not used)

S_Set01_1_AbsTemp­Setpoint_OpMode

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

(not used)

Operating Mode

S_Set01_4_AbsTemp­Setpoint_Scene

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

(not used)

Scene

S_Set01_5_RelTemp­Setpoint_OpMode

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

(not used)

Operating Mode

S_Set01_6_RelTemp­Setpoint_Scene

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

(not used)

Scene

S_Set01_20_DateTime_RelTemp­Setpoint_
RoomTemp

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Date
Time

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

(not used)

S_Set02_0_AbsTemp­Setpoint_FanSpeed

Fcu01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Fan Speed

(not used)

S_Set02_1_AbsTemp­Setpoint_FanSpeed_
OpMode

Fcu01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Fan Speed

Operating Mode

S_Set02_4_AbsTemp­Setpoint_FanSpeed_
Scene

Fcu01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Fan Speed

Scene

S_Set02_5_RelTemp­Setpoint_FanSpeed

Fcu01

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Fan Speed

(not used)

S_Set02_6_RelTemp­Setpoint_FanSpeed_
OpMode

Fcu01

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Fan Speed

Operating Mode

S_Set02_7_RelTemp­Setpoint_FanSpeed_
Scene

Fcu01

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

Fan Speed

Scene

S_Set02_8_ActRoom­Temp_RelTemp­Setpoint_FanSpeed

Fcu01

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

Fan Speed

(not used)

S_Set02_20_DateTime_
RelTemp­Setpoint_RoomTemp_
FanSpeed

Fcu01

Date
Time

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Fan Speed

S_Set03_0_AbsTemp­Setpoint_Prolongation

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

(not used)

Prolongation

S_Set03_1_AbsRoom­Temp_FanSpeed_
Prolongation

Fcu01, Rapid Ventilation

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Fan Speed

Prolongation

S_Set03_2_RelTemp­Setpoint_Prolongation

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

(not used)

Prolongation

S_Set03_3_RelTemp­Setpoint_FanSpeed_
Prolongation

Fcu01, Rapid Ventilation

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Fan Speed

Prolongation

S_Set04_0_AbsTemp­Set­point_Occup

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

(not used)

Occupancy

S_Set04_1_RelTemp­Setpoint_Occup

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

(not used)

Occupancy

S_Set04_2_AbsTemp­Setpoint_FanSpeed_
Occup

Fcu01, Rapid Ventilation

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Fan Speed

Occupancy

S_Set04_3_RelTemp­Setpoint_FanSpeed_
Occup

Fcu01, Rapid Ventilation

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Fan Speed

Occupancy

S_Set04_4_AbsTemp­Setpoint

Rad01, Ccg01, HCcg2Pipe01, HCcg4Pipe01, CcgRad01, Vav01

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

(not used)

(not used)

S_Set04_4_RelTemp­Setpoint_Occup

Rad, Ccg

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Actual temperature in [°C] or [°F]

Occupancy

S_Set04_4K_RelTemp­Setpoint_Occup

Rad, Ccg

Plant state (Heating or Cooling)

Set-point relative temperature in [K] or [°F]

Actual temperature in [°C] or [°F]

Occupancy

S_Set04_5_AbsTemp­Setpoint_RpdVent_
Occup

VAV

Plant state (Heating or Cooling)

Set-point absolute temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_6_RelTemp­Setpoint_RpdVent_
Occup

VAV

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_6K_RelTemp­Setpoint_RpdVent_
Occup

VAV

Plant state (Heating or Cooling)

Set-point relative temperature in [K] or [°F]

Rapid Ventilation

Occupancy

S_Set04_7_RelTemp­Setpoint_FanSpeed_
Occup

FCU

Plant state (Heating or Cooling)

Set-point relative temperature in [°C] or [°F]

Fan Speed

Occupancy

S_Set04_7K_RelTemp­Setpoint_FanSpeed_
Occup

FCU

Plant state (Heating or Cooling)

Set-point relative temperature in [K] or [°F]

Fan Speed

Occupancy

S_Set04_8_RoomTemp_RelTemp­Setpoint_FanSpeed_
Occup

FCU

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

Fan Speed

Occupancy

S_Set04_8K_RoomTemp_RelTemp­Setpoint_FanSpeed_
Occup

FCU

Actual temperature in [°C] or [°F]

Set-point relative temperature in [K] or [°F]

Fan Speed

Occupancy

S_Set04_9_RoomTemp_AbsTemp­Setpoint_RpdVent_
Occup

VAV

Actual temperature in [°C] or [°F]

Set-point absolute temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_10_RoomTemp_RelTemp­Setpoint_RpdVent_
Occup

VAV

Actual temperature in [°C] or [°F]

Set-point relative temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_10K_RoomTemp_RelTemp­Setpoint_RpdVent_
Occup

VAV

Actual temperature in [°C] or [°F]

Set-point relative temperature in [K] or [°F]

Rapid Ventilation

Occupancy

S_Set04_11_AQ_AbsTemp­Setpoint_RpdVent_
Occup

VAV

Room Air Quality

Set-point absolute temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_12_AQ_RelTemp­Setpoint_RpdVent_
Occup

VAV

Room Air Quality

Set-point relative temperature in [°C] or [°F]

Rapid Ventilation

Occupancy

S_Set04_12K_AQ_RelTemp­Setpoint_RpdVent_
Occup

VAV

Room Air Quality

Set-point relative temperature in [K] or [°F]

Rapid Ventilation

Occupancy

S_Set04_13K_RelTemp­Setpoint

Rad, Ccg

(not used)

Set-point relative temperature in [K] or [°F]

(not used)

(not used)

S_Set05_0_Scene

Only Scene, Meeting Room

Scene

Scene names