Weather stations

Third party weather stations can be integrated via KNX S-Mode or through an Analog Input. The following table provides a description of third party devices along with links to the related documentation.

Depending on the building complexity and local requirements, a variety of weather stations is available on the market. You have two options when choosing a sensor:

Wind sensors

Special focus should be given to wind sensors. These are highly product safety relevant: any mismeasurement or sensor inaccuracy can damage hundreds of blinds actuators. Therefore, we recommend using equivalent sensors that achieve high qualitative requirements in terms of performance, measuring precision, and reliability for Total Room Automation. You can either place one central wind sensor by mast mounting (for example integrated in a multi-purpose Clima sensor) or you can place sensors on each facade. In case of critical environmental impacts, such as different wind situations, additional wind sensors should be placed around the facade.

List of third party devices

Single purpose

Device type

Device with product information

Interface

Catalog download

Wind

Thies Wind Transmitter Compact

4.3519.xx.xxx

Thies products wind compact

Analog

Thies Catalog Wind

Thies Download

Wind direction

Thies Wind Direction Transmitter Compact

4.3129.xx.xxx

Thies products wind compact

Analog

Brightness

Thies Brightness Transmitter

7.1414.5x.xxx

Thies products radiation electrical devices

Analog

Thies Catalog Radiation

Thies Download

Brightness
angle-independent

Thies Brightness Transmitter

7.1414.51.xxx

Thies products radiation electrical devices

Analog

Global Radiation

Thies Pyranometer GSM 3.3

7.1415.09.xxx

Thies products radiation electrical devices

Analog

Temperature

Thies Temperature Sensor compact

2.1280.00.000

Thies products temperature electrical sensors

PT100

Thies Catalog Temperature, Pressure, Humidity

Thies Download

Temperature

Thies Temperature Sensor compact

2.1280.00.1xx

Thies products temperature electrical sensors

Analog

Wind speed

Griesser Wind sensor with heating

WSHE

Frequency

Requires a frequency to analog signal converter (see below)

Griesser Sensors, operation and accessories

Converter

Frequency to analog signal converter

WZ111000

Wachendorff Download Signalwandler und Überwachungsmodule

„Bedienungsanleitung WZ111000“

Frequency / Analog

Wachendorff Informationsflyer

Wachendorff Download Signalwandler und Überwachungsmodule

 

Multi-purpose

Device type

Device with product information

Interface

Catalog download

Wind

Brightness

Global radiation

Temperature

Air humidity

Thies Clima Sensor D

4.91xx.00.061

Thies products miscellaneous devices weatherstations

Analog

Thies Catalog Wind or Catalog Temperature, Pressure, Humidity

Thies Download

 

Temperature

Air Humidity"

Thies Hygro-thermo transmitter compact

1.1005.54.xxx

Thies products temperature electrical sensors

Analog

Thies Catalog Temperature, Pressure, Humidity

Thies Download