LGT_PAR1: Lighting parameter 1, lighting control

Block LGT_PAR1 (FB822) includes a set of parameter values. These parameter values are used in the charts for automating lighting control applications.

Functioning

The block can be parameterized and provide parameter values.

Input values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

EnAutoCtl

Enable auto control

BOOL

1

False, True

0

1

LgtCtlAvl

Lighting control available.

BOOL

1

False, True

0

1

EnSwiOnBrgt

Enable switch on brightness

BOOL

1

False, True

0

1

EnSwiOffBrgt

Enable switch off brightness

BOOL

1

False, True

0

1

DlyOffBrgt

Delay off brightness

TIME

5m

T#0d_0h_0m_0s_0ms

 

 

LgtCmdCtlMax

Lighting command max. control value.

REAL

100.0

%

0.0

100.0

LgtCmdCtlMin

Lighting command min. control value.

REAL

1.0

%

0.0

100.0

StepFac

Step factor

REAL

0.01

---

0.0

3.40E38

StepValMax

Maximum step value

REAL

10.0

%

0.0

100.0

StepValMin

Minimum step value.

REAL

1.0

%

0.0

100.0

UpdIvl

Update interval.

TIME

5s

T#0d_0h_0m_0s_0ms

 

 

HysBrgtSwiOn

Switch on hysteresis brightness

REAL

100.0

lx

0.0

3.40E38

HysBrgtCtl

Hysteresis brightness control.

REAL

100.0

lx

0.0

3.40E38

BrgtCtlMin

Minimum brightness control

REAL

250.0

lx

0.0

3.40E38

TiOnBrgt

Brightness switch on time.

TIME

5s

T#0d_0h_0m_0s_0ms

 

 

SwiOnValBrgt

Brightness switch on value.

REAL

100.0

lx

0.0

3.40E38

SwiOnVal

Switch-on value

REAL

50.0

%

 

 

Output values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

EnAutoCtlOut

Enable auto control output

BOOL

1

False, True

0

1

LgtCtlAvlOut

Lighting control available output.

BOOL

1

False, True

0

1

EnSwiOnBrgtOut

Enable switch on brightness output

BOOL

1

False, True

0

1

EnSwiOffBrgtO

Enable switch off brightness output

BOOL

1

False, True

0

1

DlyOffBrgtOut

Delay off brightness output

TIME

T#0D_0H_5M_0S_0MS

T#0d_0h_0m_0s_0ms

 

 

LgtCmdCtlMaxO

Lighting command max. control value.

REAL

100.0

%

0.0

100.0

LgtCmdCtlMinO

Min. control value lighting command output

REAL

1.0

%

0.0

100.0

StepFacOut

Step factor output

REAL

0.01

---

0.0

3.40E38

StepValMaxOut

Maximum step value output

REAL

10.0

%

0.0

100.0

StepValMinOut

Minimum step value output

REAL

1.0

%

0.0

100.0

UpdIvlOut

Update interval output

TIME

T#0D_0H_0M_5S_0MS

 

 

 

HysBrgtSwiOnO

Switch on hysteresis brightness output

REAL

100.0

lx

0.0

3.40E38

HysBrgtCtlOut

Hysteresis brightness control output

REAL

100.0

lx

0.0

3.40E38

BrgtCtlMinOut

Minimum output brightness control

REAL

250.0

lx

0.0

3.40E38

TiOnBrgtOut

Switch on brightness output

TIME

T#0D_0H_0M_5S_0MS

T#0d_0h_0m_0s_0ms

 

 

SwiOnValBrgtO

Switch on brightness output

REAL

100.0

lx

0.0

3.40E38

SwiOnValOut

Switch-on value output

REAL

50.0

%

0.0

100.0

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).