LGT_PAR1: Lighting parameter 1, lighting control
Block LGT_PAR1 (FB822) includes a set of parameter values. These parameter values are used in the charts for automating lighting control applications.
Functioning
The block can be parameterized and provide parameter values.
Input values
Pin | Description | Data type | Standard value | Engineering unit or text group | Min. | Max. |
EnAutoCtl | Enable auto control | BOOL | 1 | False, True | 0 | 1 |
LgtCtlAvl | Lighting control available. | BOOL | 1 | False, True | 0 | 1 |
EnSwiOnBrgt | Enable switch on brightness | BOOL | 1 | False, True | 0 | 1 |
EnSwiOffBrgt | Enable switch off brightness | BOOL | 1 | False, True | 0 | 1 |
DlyOffBrgt | Delay off brightness | TIME | 5m | T#0d_0h_0m_0s_0ms |
|
|
LgtCmdCtlMax | Lighting command max. control value. | REAL | 100.0 | % | 0.0 | 100.0 |
LgtCmdCtlMin | Lighting command min. control value. | REAL | 1.0 | % | 0.0 | 100.0 |
StepFac | Step factor | REAL | 0.01 | --- | 0.0 | 3.40E38 |
StepValMax | Maximum step value | REAL | 10.0 | % | 0.0 | 100.0 |
StepValMin | Minimum step value. | REAL | 1.0 | % | 0.0 | 100.0 |
UpdIvl | Update interval. | TIME | 5s | T#0d_0h_0m_0s_0ms |
|
|
HysBrgtSwiOn | Switch on hysteresis brightness | REAL | 100.0 | lx | 0.0 | 3.40E38 |
HysBrgtCtl | Hysteresis brightness control. | REAL | 100.0 | lx | 0.0 | 3.40E38 |
BrgtCtlMin | Minimum brightness control | REAL | 250.0 | lx | 0.0 | 3.40E38 |
TiOnBrgt | Brightness switch on time. | TIME | 5s | T#0d_0h_0m_0s_0ms |
|
|
SwiOnValBrgt | Brightness switch on value. | REAL | 100.0 | lx | 0.0 | 3.40E38 |
SwiOnVal | Switch-on value | REAL | 50.0 | % |
|
|
Output values
Pin | Description | Data type | Standard value | Engineering unit or text group | Min. | Max. |
EnAutoCtlOut | Enable auto control output | BOOL | 1 | False, True | 0 | 1 |
LgtCtlAvlOut | Lighting control available output. | BOOL | 1 | False, True | 0 | 1 |
EnSwiOnBrgtOut | Enable switch on brightness output | BOOL | 1 | False, True | 0 | 1 |
EnSwiOffBrgtO | Enable switch off brightness output | BOOL | 1 | False, True | 0 | 1 |
DlyOffBrgtOut | Delay off brightness output | TIME | T#0D_0H_5M_0S_0MS | T#0d_0h_0m_0s_0ms |
|
|
LgtCmdCtlMaxO | Lighting command max. control value. | REAL | 100.0 | % | 0.0 | 100.0 |
LgtCmdCtlMinO | Min. control value lighting command output | REAL | 1.0 | % | 0.0 | 100.0 |
StepFacOut | Step factor output | REAL | 0.01 | --- | 0.0 | 3.40E38 |
StepValMaxOut | Maximum step value output | REAL | 10.0 | % | 0.0 | 100.0 |
StepValMinOut | Minimum step value output | REAL | 1.0 | % | 0.0 | 100.0 |
UpdIvlOut | Update interval output | TIME | T#0D_0H_0M_5S_0MS |
|
|
|
HysBrgtSwiOnO | Switch on hysteresis brightness output | REAL | 100.0 | lx | 0.0 | 3.40E38 |
HysBrgtCtlOut | Hysteresis brightness control output | REAL | 100.0 | lx | 0.0 | 3.40E38 |
BrgtCtlMinOut | Minimum output brightness control | REAL | 250.0 | lx | 0.0 | 3.40E38 |
TiOnBrgtOut | Switch on brightness output | TIME | T#0D_0H_0M_5S_0MS | T#0d_0h_0m_0s_0ms |
|
|
SwiOnValBrgtO | Switch on brightness output | REAL | 100.0 | lx | 0.0 | 3.40E38 |
SwiOnValOut | Switch-on value output | REAL | 50.0 | % | 0.0 | 100.0 |
Process response
Standard (see General rules and information).
Troubleshooting
Standard (see General rules and information).