CK_BLS: Consistency check centralized blinds values

Block CK_BLS (FB802) checks four blinds positioning values for consistency. The valid blinds positioning values are pending at the output.

Functioning

The blinds positioning values are outputted by a centralized shading application for the local shading application. These values are transmitted via separate signal paths (required by the technology). The block ensures that individually transmitted values together form a valid value set and can be outputted.

The block compares the new blinds positioning values with valid value sets for consistency based on the update indication [BlsOpUpdInd], [BlsPosNrUpdInd], [BlsHgtUpdInd] and [SlatsAglUpdInd].

The new blinds positioning values are pending at the output is the check is successful.
The existing blinds positioning values are pending at the output is the check is not successful.

The check occurs within time [TiCK].

Valid values:

Value set

Update indication required for

[BlsOpPrVal] = 5

(Go to height)

BlsOpUpdInd
BlsHgtUpdInd

[BlsOpPrVal] = 7

(Go to height & angle)

BlsOpUpdInd
BlsHgtUpdInd
SlatsAglUpdInd

[BlsOpPrVal] = 8

(Go to position)

BlsOpUpdInd
BlsPosNrUpdInd

Input values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

BlsOpPrVal

Blinds operation present value

INT

9

BA Blinds output command

0

9

BlsOpUpdInd

Blinds operation update indication

BOOL

0

False, True

 

 

BlsPosNrPrVal

Blinds position number present value

INT

0

BA Predefined blinds position

0

4

BlsPosNrUpdInd

Blinds position number update indication

BOOL

0

False, True

 

 

BlsHgtPrVal

Blinds height present value.

REAL

0.0

%

0.0

100.0

BlsHgtUpdInd

Blinds height update indication

BOOL

0

False, True

 

 

SlatsAglPrVal

Slats angle present value

REAL

0.0

%

0.0

100.0

SlatsAglUpdInd

Angle of louvers or slats update indication

BOOL

0

False, True

 

 

TiCk

Time window for check

TIME

10s

T#0d_0h_0m_0s_0ms

 

 

BlsOpPrVal

Blinds operation present value

INT

9

BA Blinds output command

0

9

Output values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

BlsOp

Blinds operation

INT

9

BA Blinds output command

0

9

BlsPosNr

Blinds position number

INT

0

BA Predefined blinds position

0

4

BlsHgt

Blinds height

REAL

0.0

%

0.0

100.0

SlatsAgl

Angle of louvers or slats

REAL

0.0

%

0.0

100.0

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).