CK_COV: Check change of value for 2 MS & 2 Real

Block CK_COV (FB885) checks 2 multistate values and 2 real values for a change of value. The results are pending on the output.

Application: Displays in chart {CenGlrThPrt01} for a change to blinds positioning value.

Functioning

The block compares all input values with their value for the last cycle. For change a value, [PlsCovInd] is set to = 1 (one cycle in length).

The input values are switched directly to the outputs.

Input values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

InMs1

Multistate input 1

INT

1

 

0

32767

InMs2

Multistate input 2

INT

1

 

0

32767

InR1

Real input 1

REAL

0.0

%

0.0

100.0

InR2

Real input 2

REAL

0.0

%

0.0

100.0

Output values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

OutMs1

Multistate output 1

INT

1

Off...Stage15, Max

1

32767

OutMs2

Multistate output 2

INT

1

Off...Stage15, Max

1

32767

OutR1

Real output 1

REAL

0.0

%

0.0

100.0

OutR2

Real output 2

REAL

0.0

%

0.0

100.0

PlsCovInd

Pulse for change of value indication

BOOL

0

False, True

 

 

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).