SHD_PAR2: Shading parameter 2, anti-glare protection

Block SHD_PAR2 (FB801) includes a set of parameter values. These parameter values are used in the charts for automating anti-glare applications, e.g. {ShdGlrPrt01}.

Functioning

The block can be parameterized and provide parameter values.

Input values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

BlsPosGlrPrtHi

Blinds position for high anti-glare protection

INT

1

Automatic, Fixed position

1

2

FxpGlrHiOp

Operation for fixed position & high anti-glare protection

INT

8

BA Blinds output command

0

9

FxpGlrHiPosNr

Position number for fixed position & high anti-glare protection

INT

2

BA Predefined blinds position

0

4

FxpGlrHiHgt

Height for fixed position & high anti-glare protection

REAL

0.0

%

0.0

100.0

FxpGlrHiAgl

Angle for fixed position & high anti-glare protection

REAL

0.0

%

0.0

100.0

FxpGlrHldOp

Operation for fixed position & hold anti-glare protection

INT

8

BA Blinds output command

0

9

FxpGlrHldPosNr

Position number for fixed position & hold anti-glare protection

INT

4

BA Predefined blinds position

0

4

FxpGlrHldHgt

Height for fixed position & hold anti-glare protection

REAL

0.0

%

0.0

100.0

FxpGlrHldAgl

Angle for fixed position & hold anti-glare protection

REAL

0.0

%

0.0

100.0

FxpGlrNoneOp

Operation for fixed position & no anti-glare protection

INT

1

BA Blinds output command

0

9

FxpGlrNonePsn

Position number for fixed position & no anti-glare protection

INT

0

BA Predefined blinds position

0

4

FxpGlrNoneHgt

Height for fixed position & no anti-glare protection

REAL

0.0

%

0.0

100.0

FxpGlrNoneAgl

Angle for fixed position & no anti-glare protection

REAL

0.0

%

0.0

100.0

Output values

Pin

Description

Data type

Standard value

Engineering unit or text group

Min.

Max.

PosGlrPrtHi

Position for high anti-glare protection

INT

1

Automatic, Fixed position

1

2

HiOp

Operation for high anti-glare protection

INT

8

BA Blinds output command

0

9

HiPosNr

Position number for high anti-glare protection

INT

2

BA Predefined blinds position

0

4

HiHgt

Height for high anti-glare protection

REAL

0.0

%

0.0

100.0

HiAgl

Angle for high anti-glare protection

REAL

0.0

%

0.0

100.0

HldOp

Operation for hold anti-glare protection

INT

8

BA Blinds output command

0

9

HldPosNr

Holder hold anti-glare protection position number

INT

4

BA Predefined blinds position

0

4

HldHgt

Hold height for anti-glare protection

REAL

0.0

%

0.0

100.0

HldAgl

Hold angle for anti-glare protection

REAL

0.0

%

0.0

100.0

NoneOp

Operation for no anti-glare protection

INT

1

BA Blinds output command

0

9

NonePosNr

Position number for no anti-glare protection

INT

0

BA Predefined blinds position

0

4

NoneHgt

Height for no anti-glare protection

REAL

0.0

%

0.0

100.0

NoneAgl

Angle for no anti-glare protection

REAL

0.0

%

0.0

100.0

 

Process response

Standard (see General rules and information).

Troubleshooting

Standard (see General rules and information).