SHD_PAR2: Shading parameter 2, anti-glare protection
Block SHD_PAR2 (FB801) includes a set of parameter values. These parameter values are used in the charts for automating anti-glare applications, e.g. {ShdGlrPrt01}.
Functioning
The block can be parameterized and provide parameter values.
Input values
Pin | Description | Data type | Standard value | Engineering unit or text group | Min. | Max. |
BlsPosGlrPrtHi | Blinds position for high anti-glare protection | INT | 1 | Automatic, Fixed position | 1 | 2 |
FxpGlrHiOp | Operation for fixed position & high anti-glare protection | INT | 8 | BA Blinds output command | 0 | 9 |
FxpGlrHiPosNr | Position number for fixed position & high anti-glare protection | INT | 2 | BA Predefined blinds position | 0 | 4 |
FxpGlrHiHgt | Height for fixed position & high anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
FxpGlrHiAgl | Angle for fixed position & high anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
FxpGlrHldOp | Operation for fixed position & hold anti-glare protection | INT | 8 | BA Blinds output command | 0 | 9 |
FxpGlrHldPosNr | Position number for fixed position & hold anti-glare protection | INT | 4 | BA Predefined blinds position | 0 | 4 |
FxpGlrHldHgt | Height for fixed position & hold anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
FxpGlrHldAgl | Angle for fixed position & hold anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
FxpGlrNoneOp | Operation for fixed position & no anti-glare protection | INT | 1 | BA Blinds output command | 0 | 9 |
FxpGlrNonePsn | Position number for fixed position & no anti-glare protection | INT | 0 | BA Predefined blinds position | 0 | 4 |
FxpGlrNoneHgt | Height for fixed position & no anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
FxpGlrNoneAgl | Angle for fixed position & no anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
Output values
Pin | Description | Data type | Standard value | Engineering unit or text group | Min. | Max. |
PosGlrPrtHi | Position for high anti-glare protection | INT | 1 | Automatic, Fixed position | 1 | 2 |
HiOp | Operation for high anti-glare protection | INT | 8 | BA Blinds output command | 0 | 9 |
HiPosNr | Position number for high anti-glare protection | INT | 2 | BA Predefined blinds position | 0 | 4 |
HiHgt | Height for high anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
HiAgl | Angle for high anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
HldOp | Operation for hold anti-glare protection | INT | 8 | BA Blinds output command | 0 | 9 |
HldPosNr | Holder hold anti-glare protection position number | INT | 4 | BA Predefined blinds position | 0 | 4 |
HldHgt | Hold height for anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
HldAgl | Hold angle for anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
NoneOp | Operation for no anti-glare protection | INT | 1 | BA Blinds output command | 0 | 9 |
NonePosNr | Position number for no anti-glare protection | INT | 0 | BA Predefined blinds position | 0 | 4 |
NoneHgt | Height for no anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
NoneAgl | Angle for no anti-glare protection | REAL | 0.0 | % | 0.0 | 100.0 |
Process response
Standard (see General rules and information).
Troubleshooting
Standard (see General rules and information).