Units of measure, engineering units

Desigo Room Automation uses the units as defined under the BACnet standard for room applications.

Three identical libraries are supplied with the same functionality, but using different units:

The library (and with it the system of units) is selected as follows:

The table below describes the units that are different in the libraries as well as their conversion Slope, intercept and rounding.

SI

US

Unit

Unit

Slope

Intercept

°C

°F

1.800000

32.00

K

°F

1.800000

0.00

cm

in

0.393701

0.00

m

ft

3.280834

0.00

m/s

ft/min

196.850394

0.00

m2

ft2

10.764263

0.00

m3/h

ft3/min

0.588578

0.00

Pa

inWC

0.004015

0.00

mbar

inHg

0.029530

0.00

m3/h/SqrtPa

ft3/min/inWC

26.813400

0

W/m2

W/ft2

0.092903

0

SI

Canada

Unit

Unit

Slope

Intercept

°C

°C

 

 

K

K

 

 

cm

cm

 

 

m

m

 

 

m/s

m/s

 

 

m2

m2

 

 

m3/h

l/s

0.277778

0.00

Pa

Pa

 

 

mbar

mbar

 

 

m3/h/SqrtPa

l/s/SqrtPa

0.277778

0

W/m2

W/m2

 

 

info

Angle in degrees (blinds) are only used within the application, not in BACnet objects.