Shading presence operation (ShdPscOp11)

Overview

The application function "Shading presence operation 11" (ShdPscOp11) processes the response to one or more presence detectors.

Function

This AF processes presence detector response for one actuator for blinds or awnings based on the room-wide Shading presence mode (ShdPscMod) which is configured in AF ShdPscMod11.

Configuration

Configuration

Description

Object

Type

Default value

Shading switch-off delay presence detector
▶ This delay is added to the detector's internal delay which is usually 1...2 minutes.

ShdDlyOfPscDet

UCnfVal

1800 [s]

Interface

Interface

Description

Type

Ref.

Owned by

ShdPscDetCol

Collection of shading presence detector
▶ Collect all presence sensors which are relevant fort he actual Shd11 application

ColView

-

 

ShdPscDetRs

Result of shading presence detector

0:Absent
1:Present

BCalcVal

-

PscDet

Presence detector

0:Absent
1:Present

BI

Room segment / Device

ShdPscMod

Shading presence mode

1:None
2:Consider present: Automatic
3:Consider present: Hold
4:Consider absent: Automatic
5:Consider present: Automatic / Consider absent: Automatic
6:Consider present: Hold / Consider absent: Automatic

MCalcVal

1)

-

ShdDlyOfPscDet

Shading switch-off delay presence detector
▶ Time after leaving the room until the configured "absent" reaction is carried out (usually switching the blinds to automatic).

UCnfVal

-

1) ShdPscMod is calculated in AF ShdPscMod11 in RShdCoo11 (and can be operated and configured there). Here in AF PscOp11 it is only a copy via grouping and cannot be operated.

 

Engineering and commissioning


Troubleshooting
Verify the function on the chart in CFC: The output PscDet$ indicates the current presence detector state.