Room temperature setpoint determination (SpTR11)

Overview

The application function "Room temperature setpoint determination 11, for HVAC with heating & cooling setpoint for comfort, room temperature setpoint shift" (SpTR11) provides the Comfort heating/cooling setpoints for room temperature controllers.

Function

Input:


Output:


Note: The heating/cooling setpoints for Economy and Protection, as well as the delta heating/cooling setpoints for Pre-comfort are owned by the room temperature controllers and configured there using BACnet Configuration data points.

Configuration

Parameters

Description

Parameter

Default value

Operating command for energy efficiency condition trigger at automatic
▶ How a trigger caused by an automatic function affects the setpoint operation.

1:None
▶ Manual setpoint operation remains.
2:Automatic
▶ Manual setpoint operation gets released.

OpCmdEefAuto

2:Automatic

Operating command for energy efficiency condition trigger at manual
▶ How a trigger caused by a manual operation such as deactivating the presence button affects the setpoint operation.

Enumeration see OpCmdEefAuto

OpCmdEefMan

1:None

Display absolute room temperature setpoint
▶ In case room operator unit is configured for absolute setpoint, the average or the present setpoint can be displayed. See also section Function.

1:Average value
▶ Displays average of SpHCmf and SpCCmf.
2:Present value
▶ Displays present (i.e. either heating or cooling) setpoint of present operating mode. In case PrOpMod is Economy or Protection, the Pre-Comfort value is displayed.

SpTRAbsDspy

1:Average value

Interface

Interface

Description

Type

Ref.

Owned by

SpTR

Room temperature setpoint

APrcVal

-

SpTRShft

Room temperature setpoint shift

APrcVal

-

SpCCmf

Cooling setpoint for comfort (for display in room operator unit)

APrcVal

Heating/cooling control AF

SpHCmf

Heating setpoint for comfort (for display in room operator unit)

APrcVal

DSpCPcf

Delta cooling setpoint for pre-comfort

ACnfVal

DSpHPcf

Delta heating setpoint for pre-comfort

ACnfVal

PrOpMod

Present operating mode

MCalcVal

ROpMod11

CenSsnCmp

Central seasonal compensation

GrpMbr

-