Air volume flow tracking (AirFlTck11)

Overview

The application function "Air volume flow tracking 11" (AirFlTck11) collaborates with VAV supply and extract air terminal boxes to calculate the extract airflow setpoint.

Function

Room pressurization mode
The extract airflow setpoint depends on the setting of PRMode (Room pressurization mode). PRMode can be set for Neutral, Positive, or Negative room pressure.

Transferred air volume flow
AirFlTrn (Transferred air volume flow) represents the amount of air that enters (infiltration) or exits (exfiltration) a pressurized room through cracks or small openings. In a pressurized room, the extract airflow setpoint differs from supply airflow by the value of AirFlTrn.

Example:

AirFlTrn is a positive number regardless of PRMode value.

Configuration

Parameters

Description

Parameter

Default value

Room pressurization mode

1:Neutral
2:Positive pressure
3:Negative pressure

PRMod

1:Neutral

Transferred air volume flow
▶ The amount of air that enters (infiltration) or exits (exfiltration) a pressurized room through cracks or small openings.

AirFlTrn

10 [m3/h]
5.8 [ft3/min]
2.77 [l/s]

Air volume flow unit
▶ Defined by selected engineering unit – do not change.

AirFlUnit

[m3/h]
[ft3/min]
[l/s]

Interface

Interface

Description

Type

Ref.

Owned by

AirFlSuR

Room supply air volume flow

ACalcVal

-

PrSpAirFlExR

Present setpoint for room extract air volume flow

ACalcVal

-

RCtl

Room control

GrpMaster

Room

Engineering and commissioning