Fan powered box room temperature control cooling (FpbTRCtlC11)
Overview
The application function "Fan-powered VAV box room temperature control for cooling 11" (FpbTRCtlC11) is the hub for the sequencing of the room temperature controllers for FPB cooling. It determines the room cooling setpoint and the room cooling demand signals to maintain the room temperature at the cooling setpoint.
The following devices in the room segment(s) are supported:
- Cooling coil
- Chilled ceiling (panels or beams)
- Supply air VAV damper
- Fan
Function
This AF works in collaboration with a room segment HVAC device component AF for cooling. The cooling room temperature PID controller is enabled based on a signal that is read via the grouping function (from equipment in the room segment) indicating whether cooling is available.
Devices for cooling are activated in the following order (default):
Chilled ceiling > Heating/Cooling coil > Cooling coil > Fan > VAV
Cooling setpoint and plant mode
| Plant operation mode | Cooling setpoint |
|---|---|---|
1 | Off | Protection cooling |
2 | Protection | Protection cooling |
3 | Economy | Economy cooling |
4 | Pre-Comfort | Pre-Comfort cooling |
5 | Comfort | Comfort cooling |
6 | Warm-up | Protection cooling |
7 | Cool down | Comfort / Pre-Comfort cooling1 |
8 | Room low temperature protection | Protection cooling |
9 | Not used |
|
10 | Free cooling | Comfort cooling |
11 | Night cooling | Comfort cooling |
12 | Ventilation | Comfort cooling |
13 | Not used |
|
14 | Air volume flow off | Protection cooling |
15 | Smoke extraction positive pressure | Protection cooling |
16 | Smoke extraction negative pressure | Protection cooling |
17 | Purge | Protection cooling |
1) Depends on Next room operating mode (NxROpMod) in HvacPltMod AF.
Feature configuration
Feature selections for "Room HVAC coordination" are accessed via the Application configuration task in the Configuration component.
Feature (AF) | Feature description | Ref. |
|---|---|---|
Trend for present cooling setpoint | None/Active | ☑ |
Configuration
Objects
Description | Object | Type | Default value |
|---|---|---|---|
Cooling setpoint for comfort 0...50 [°C], 32.0...122.0 [°F] | SpCCmf | APrcVal | 24 [°C] |
Delta cooling setpoint for pre-comfort 0...10 [K], 0.0...18.0 [°F] | DSpCPcf | ACnfVal | 1 [K] |
Cooling setpoint for economy 0...50 [°C], 32.0...122.0 [°F] | SpCEco | ACnfVal | 35 [°C] |
Cooling setpoint for protection 0...50 [°C], 32.0...122.0 [°F] | SpCPrt | ACnfVal | 40 [°C] |
Parameters
Description | Parameter | Default value |
|---|---|---|
Fan operation 0:Series | FanOp | 1:Parallel |
Coil valve start position by parallel operation | CoilVlvSttPrl | 10 [%] |
Coil valve end position by parallel operation | CoilVlvEndPrl | 100 [%] |
Fan end speed by parallel operation | FanEndSpdPrl | 50 [%] |
Comfort configuration 1:None | CmfCnf | 4:Radiant & air treatment devices |
Pre-Comfort configuration Enumeration see CmfCnf | PcfCnf | 4:Radiant & air treatment devices |
Economy configuration Enumeration see CmfCnf | EcoCnf | 4:Radiant & air treatment devices |
Protection configuration Enumeration see CmfCnf | PrtCnf | 4:Radiant & air treatment devices |
Cool down configuration Enumeration see CmfCnf | CoolDnCnf | 4:Radiant & air treatment devices |
Free cooling configuration Enumeration see CmfCnf | FreeCCnf | 4:Radiant & air treatment devices |
Coil: Controller mode by comfort 0:Continuous | CoilCmf | 0:Continuous |
Coil: Controller mode by pre-comfort Enumeration see CoilCmf | CoilPcf | 0:Continuous |
Coil: Controller mode by economy Enumeration see CoilCmf | CoilEco | 0:Continuous |
Coil: Controller mode by protection Enumeration see CoilCmf | CoilPrt | 0:Continuous |
Coil: Controller mode by cool down Enumeration see CoilCmf | CoilCoolDn | 0:Continuous |
Radiant devices: Controller mode by comfort Enumeration see CoilCmf | RadDevCmf | 0:Continuous |
Radiant devices: Controller mode by pre-comfort Enumeration see CoilCmf | RadDevPcf | 0:Continuous |
Radiant devices: Controller mode by economy Enumeration see CoilCmf | RadDevEco | 0:Continuous |
Radiant devices: Controller mode by protection Enumeration see CoilCmf | RadDevPrt | 0:Continuous |
Radiant devices: Controller mode by cool down Enumeration see CoilCmf | RadDevCoolDn | 0:Continuous |
Radiant ceiling cooling sequence | RcgCSeq | 1 [1..8 unique] |
Heating/cooling coil cooling sequence | HCclCSeq | 2 [1..8 unique] |
Cooling coil cooling sequence | CclCSeq | 3 [1..8 unique] |
Fan cooling sequence | FanCSeq | 4 [1..8 unique] |
VAV cooling sequence | VavCSeq | 5 [1..8 unique] |

Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
PrSpC | Present cooling setpoint | APrcVal | ● | - |
TrndPrSpC | Trend for present cooling setpoint | FtrSel | ☑ | - |
PrSpCCmf | Present cooling setpoint for comfort | ACalcVal | ● | - |
PrSpCPcf | Present cooling setpoint for pre-comfort | ACalcVal | ● | - |
PrSpCEco | Present cooling setpoint for economy | ACalcVal | ● | - |
PrSpCPrt | Present cooling setpoint for protection | ACalcVal | ● | - |
VavTRCtrC | Room temperature controller cooling for VAV | Controller | ● | - |
FanTRCtrC | Room temperature controller cooling for fan | Controller | ● | - |
CclTRCtrC | Room temperature controller cooling for cooling coil | Controller | ● | - |
HCclTRCtrC | Room temperature controller cooling for heating/cooling coil | Controller | ● | - |
RcgTRCtrC | Room temperature controller cooling for radiant ceiling | Controller | ● | - |
RCtl | Room control | GrpMaster | ◉ | Room |
SpCCmf | Cooling setpoint for comfort | APrcVal | ● | - |
DSpCPcf | Delta cooling setpoint for pre-comfort | ACnfVal | ● | - |
SpCEco | Cooling setpoint for economy | ACnfVal | ● | - |
SpCPrt | Cooling setpoint for protection | ACnfVal | ● | - |