VAV ventilation control (VavVntCtl11)

Overview

The application function "VAV ventilation control 11" (VavVntCtl11) collaborates with VAV supply air terminal boxes for ventilation and/or room air quality control.

Function

Different modes are available for ventilation control; the behavior is selectable by parameter.

Ventilation mode
The ventilation mode can be set per room operating mode to:

1) Air quality sensor required in the room.

 

The table shows factory default settings for min vent and air quality parameters:

Plant mode

Ventilation mode

Sp air quality
[ppm]

AirFlMin
[m3/h]

1 Off

Off

 

 

2 Protection*

Off

1500

50

3 Economy*

Off

1500

50

4 Pre-Comfort*

Dcv

1100

50

5 Comfort*

Min & Dcv

900

50

6 Warm-up

Off

 

 

7 Cool down

Off

 

 

8 Room low temperature protection

Off

 

 

9 <not used>

 

 

 

10 Free cooling

Depends on ROpMod

Depends on ROpMod

Depends on ROpMod

11 Night cooling

Off

 

 

12 Rapid ventilation

s/a Comfort

s/a Comfort

s/a Comfort

13 <not used>

 

 

 

14 Emergency off

Off

 

 

15 Max.supply air vol.flow only (positive pressure)

Off

 

 

16 Max.extract air vol.flow only (negative pressure)

Off

 

 

17 Purge
Max.supply and extract air vol. flow

Off

 

 

*For these modes the parameters can be individually adjusted.

 

NOTICE

notice

Minimum ventilation air flow settings in VavVntCtl11

VAV PID controller is not enabled unless ventilation flow setpoint is above 7% of max air flow setting (hardcoded).

  1. If minimum ventilation is required, set minimum ventilation air flow setting(s) >7% of the largest maximum air flow setpoint.

 

Minimum ventilation setup

Minimum ventilation air flow settings should be >7% of the largest maximum air flow setpoint value (typically cooling flow maximum, VavSuAirFlMaxC located in the segment AF VavSu.xx). The nominal air volume flow parameter (AirFlNom, also located in the segment AF VavSu.xx) should be set equal to this largest maximum air flow setpoint value.

In the following examples, cooling flow maximum (VavSuAirFlMaxC) is assumed to be the largest maximum air flow setpoint.

Example 1
In this example, assume AirFlNom and VavSuAirFlMaxC have both been set to 1000 m3/h, and the minimum ventilation setpoint object (VavSuAflMinVnt, located in the segment AF VavSu.xx) has been set tozero. Setting VavSuAflMinVnt in the segment AF to zero allows the min vent parameter settings in this AF (VAV ventilation control, VavVntCtl11) to vary per the room operating mode (Comfort, Pre-Comfort, Economy, Protection). See table.

Room mode ventilation flow value

Ventilation mode setting

Result

AirFlMinRCmf = 100 m3/h

CmfCnf = Min vent & DCV

In Comfort, ventilation flow will have a low limit of 100 m3/h and may rise with air quality demand (DCV).

AirFlMinRPcf = 80 m3/h

PcfCnf = Min vent

In Pre-Comfort, ventilation flow = 80 m3/h.

AirFlMinREco = 60 m3/h

EcoCnf = Min vent

In Economy, ventilation flow will be zero, because AirFlMinREco was incorrectly set to 60 m3/h which is less than 7% of AirFlNom (AirFlNom was set to 1000 m3/h).

AirFlMinRPrt = 80 m3/h

PrtCnf = Off

In Protection, the mode setting (PrtCnf) has been set to Off. When a ventilation mode setting = Off, ventilation flow for that room mode will be zero regardless of the parameter flow value (in this case, AirFlMinRPrt) or the value of VavSuAflMinVnt.

 

Example 2
In this example, assume AirFlNom and VavSuAirFlMaxC have both been set to 1000 m3/h, and the minimum ventilation setpoint object (VavSuAflMinVnt) located in the segment AF VavSu.xx has been set to 100 m3/h.

Room mode ventilation flow setting

Ventilation mode setting

Result

AirFlMinRCmf = 125 m3/h

CmfCnf = Min vent

In Comfort, ventilation flow will be 125 m3/h.

AirFlMinRPcf = 90 m3/h

PcfCnf = Min vent

In Pre-Comfort, ventilation flow = 100 m3/h (not 90) because VavSuAflMinVnt was set to 100, which is larger than 90; (90 and 100 are each >7% AirFlNom, so they are both valid (usable) values; when valid settings conflict, the larger value wins).

AirFlMinREco = 50 m3/h

EcoCnf = Min vent

In Economy, ventilation flow will = 100 m3/h because VavSuAflMinVnt was set to 100.
Note: it is important to understand that if VavSuAflMinVnt were set to zero as in example 1 above, the minimum ventilation flow for Economy would not = 50 m3/h, even though AirFlMinREco has been set to 50. This is because 50 is not >7% of the maximum flow setpoint (AirFlNom was set to 1000 m3/h). In this case min vent would be zero.

AirFlMinRPrt = 50 m3/h

PrtCnf = Off

In Protection, the mode setting (PrtCnf) has been set to Off. When a ventilation mode setting = Off, ventilation flow for that room mode will be zero regardless of the parameter flow value (in this case, AirFlMinRPrt) or the value of VavSuAflMinVnt.

 

Demand Controlled Ventilation with Proportional Control - Configuration

Typical DCV (Demand control ventilation) uses only the "P" of the PID control loop. (PID: Proportional gain; Integral; Derivative).

DCV also uses outside air to maintain a ppm differential between good/bad indoor air quality.

When indoor air quality is at or above the hi limit ppm setpoint, PID loop output should be 100%. This control behavior can be configured by adjusting properties of the Ventilation controller object (VntCtr, Ventilation controller).

Set VntCtr properties as follows:

Integral:0
Derivative:0
Controller Output for Offset:100

The Controller Output for Offset parameter determines PID output when the measured value is at setpoint. Reference the specifications document and set accordingly.

Examples of Minimum VS Maximum Ventilation at Setpoint

The left graph shows an example of the behavior of the controller at default settings. The graph on the right shows an example the behavior of the controller after the VntCtr properties have been configured using the settings listed previously in the DCV with Proportional Control section.

Minimum Ventilation at Setpoint (default)

Maximum Ventilation at Setpoint

Periodic air flush
Parameters are available to configure periodic cycling of ventilation air flow. Ventilation can be enabled for minimum air flow at regular intervals, for the length of time in TiOnDutyCyc. See figure.

The length of the duty cycle off interval can be configured for each operating mode (DutyCycCmf, DutyCycPcf, DutyCycEco, DutyCycPrt). A duty cycle of 0min (default) means the feature is disabled.

Note
If the room temperature is measured with an extract air temperature sensor, air must flow to ensure the effective room temperature is measured correctly. In this case, periodic air flush can be used to provide air flow at regular intervals.

 

Exception handling
For air quality control, the ventilation mode must be set to Dcv or Min & Dcv, VavSuAvlVnt must be Yes and the air quality sensor must be Valid. If the sensor is failed or absent, then the ventilation mode cannot be Dcv or Min & Dcv; in this case VavSuVntReq is set to Min.

Configuration

Objects

Description

Object

Type

Default value

Setpoint room air quality for comfort

SpAQualRCmf

ACnfVal

900 [ppm]

Setpoint room air quality for pre-comfort

SpAQualRPcf

ACnfVal

1100 [ppm]

Setpoint room air quality for economy

SpAQualREco

ACnfVal

1500 [ppm]

Setpoint room air quality for protection

SpAQualRPrt

ACnfVal

1500 [ppm]

Parameters

Description

Parameter

Default value

Comfort configuration

1:Off
2:Minimum ventilation
3:Demand-controled ventilation
4:Minimum ventilation & Demand-controlled ventilation

CmfCnf

4:Minimum ventilation & Demand-controlled ventilation

Pre-Comfort configuration

Enumeration see CmfCnf

PcfCnf

3:Demand-controled ventilation

Economy configuration

Enumeration see CmfCnf

EcoCnf

2:Minimum ventilation

Protection configuration

Enumeration see CmfCnf

PrtCnf

2:Minimum ventilation

Minimum room air volume flow for comfort
▶ When CmfCnf is set to 4:Minimum ventilation & Demand-controlled ventilation and IAQ sensor configured and Valid, damper during Comfort will equal AirFlMinRCmf or the demand-controlled ventilation position, whichever is larger.
▶ When used, air flow minimum settings should be at least 7% of the largest maximum flow setpoint (for example, cooling flow maximum).

AirFlMinRCmf

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Minimum room air volume flow for pre-comfort
▶ Function see CmfCnf

AirFlMinRPcf

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Minimum room air volume flow for economy
▶ Function see CmfCnf

AirFlMinREco

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Minimum room air volume flow for protection
▶ Function see CmfCnf

AirFlMinRPrt

50 [m3/h]
29.4 [ft3/min]
13.89 [l/s]

Air volume flow unit
▶ Defined by selected engineering unit – do not change.

AirFlUnit

[m3/h]
[ft3/min]
[l/s]

Duty cycling in comfort

DutyCycCmf

0 [min]

Duty cycling in pre-comfort

DutyCycPcf

0 [min]

Duty cycling in economy

DutyCycEco

0 [min]

Duty cycling in protection

DutyCycPrt

0 [min]

Switch-on time duty cycling
▶ If periodic cycling of ventilation air flow is desired, TiOnDutyCyc defines the length of "on" time for the ventilation air flow. Periodic cycling requires duty cycle parameter(s) to be set to non zero value (DutyCycCmf, DutyCycPcf, DutyCycEco, DutyCycPrt).

TiOnDutyCyc

6 [min]

Interface

Interface

Description

Type

Ref.

Owned by

PrSpVnt

Present ventilation setpoint

APrcVal

-

VntCtr

Ventilation controller

Controller

-

RCtl

Room control

GrpMaster

Room

SpAQualRCmf

Setpoint room air quality for comfort

ACnfVal

-

SpAQualRPcf

Setpoint room air quality for pre-comfort

ACnfVal

-

SpAQualREco

Setpoint room air quality for economy

ACnfVal

-

SpAQualRPrt

Setpoint room air quality for protection

ACnfVal

-

Engineering and commissioning

NOTICE

notice

Minimum ventilation air flow settings in VavVntCtl11

VAV PID controller is not enabled unless ventilation flow setpoint is above 7% of max air flow setting (hardcoded).

  1. If minimum ventilation is required, set minimum ventilation air flow setting(s) >7% of the largest maximum air flow setpoint.