HVAC green leaf (HvacGrnLf11)

Overview

The application function "HVAC green leaf 11, energy efficiency" (HvacGrnLf11) determines if manual user operations influence HVAC energy efficiency, and handles return to normal (energy efficient) state after receiving the reset request.

Function

Inputs:
The main inputs for HVAC determining energy efficiency are:


Output:
The AF provides the Energy efficiency indication HVAC (HvacEei) to the room operator unit (via RGrnLf11).
The AF releases manual settings (via internal connection) if a reset request is received from the room operator unit (REeiRst, via RGrnLf11), and the settings are inappropriate for energy efficient HVAC operation.

Configuration

Parameters

Description

Property

Default value

Maximum tolerance of room temperature setpoint shift
▶ Range (plus/minus tolerance value) in which setpoint shift is not determined as energy inefficient.

TolMaxSpTRShft

2 [K]
3.6 [°F]

Temperature difference unit
▶ Defined by selected engineering unit – do not change.

TDiffUnit

[K]
[°F]

Interface

Interface

Description

Type

Ref.

Owned by

RHvacEei

Room energy efficiency indication HVAC

1:Undefined
2:Poor
3:Satisfactory
4:Good
5:Excellent

MCalcVal

-

REeiRst

Reset of room energy efficiency indicator

0:No
1:Yes

BCalcVal

RGrnLf11