Lighting operating strategy (LgtOpStrgy11)
Overview
The application function "Lighting operating strategy 11" (LgtOpStrgy11) controls the lighting operating strategy for automatic mode based on the room operating mode.
Function
The operating strategy (LgtOpStrgy) supports the following values:
- Energy efficiency: In automatic mode the lights are set to reduced consumption of electrical energy.
- Comfort optimization: In automatic mode the lights are set to visual comfort.
The strategy can be configured for each room operating mode.
Output
The response (LgtOpStrgy) is distributed via grouping to the lighting applications (Lgt11) in the room segments.
A BACnet client can also operate the response to a presence detector.
Configuration
Parameters
Description | Parameter | Default value |
|---|---|---|
Operating strategy for comfort 1:Energy efficiency | OpStrgyCmf | 2:Comfort optimization |
Operating strategy for pre-comfort Enumeration see OpStrgyCmf | OpStrgyPcf | 1:Energy efficiency |
Operating strategy for economy Enumeration see OpStrgyCmf | OpStrgyEco | 1:Energy efficiency |
Operating strategy for protection Enumeration see OpStrgyCmf | OpStrgyPrt | 1:Energy efficiency |
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
LgtOpStrgy | Lighting operating strategy 1:Energy efficiency | MPrcVal | ● | - |
RCtl | Room control | GrpMaster | ◉ | Room |
Engineering and commissioning
- The configuration depends on room use and user preferences.