Lighting presence mode (LgtPscMod11)
Overview
The application function "Lighting presence mode 11" (LgtPscMod11) controls lighting respoonse to a presence detector on room operating mode.
Function
Lighting response to a presence detector (LgtPscMod) can be configured for each operating mode.
The configuration supports the following values:
- None: The presence detector is ignored.
- Consider present: The AF reacts to a change from absent to present.
- Consider absent: The AF reacts to a change from present to absent.
- Consider present & absent: The AF reacts to a change from absent to present and vice-versa.
Output
The response (LgtPscMod) is distributed via grouping to the lighting applications (Lgt11) in the room segments.
A BACnet client can also operate response to a presence detector.
Usage
Lighting operating modes | ||
|---|---|---|
LgtOpMod | Description | Typical usage |
None | The presence detectors state does not influence lighting. | No automatic function available |
Consider present | When the first person enters the room, lighting switches on and remains on. | Public places |
Consider absent | When no more persons are in the room, the lighting switches off. | Typical configuration when Room operating mode is NOT Comfort. |
Consider present & absent | When a person enters the room, lighting switches on. When no more persons are in the room, the lighting switches off. | Typical configuration when Room operating mode is Comfort. |
Configuration
Parameters
Description | Parameter | Default value |
|---|---|---|
Presence mode for comfort 1:None | PscModCmf | 4:Consider present & absent |
Presence mode for pre-comfort Enumeration see PscModCmf | PscModPcf | 4:Consider present & absent |
Presence mode for economy Enumeration see PscModCmf | PscModEco | 4:Consider present & absent |
Presence mode for protection Enumeration see PscModCmf | PscModPrt | 4:Consider present & absent |
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
LgtPscMod | Lighting presence mode 1:None | MPrcVal | ● | - |
RCtl | Room control | GrpMaster | ◉ | Room |
Engineering and commissioning
- The AF is required if a presence detector is in the room and used for lighting.
- For configuration, see examples in RLgtCoo11 .
- Note that the comfort trigger and energy efficiency trigger (see RLgtCoo11) also influence lighting output.