Analog inputs

This section describes analog input objects (AI) for specific applications.

For the description of properties see chapter "TX-I/O modules" in the Hardware catalog.

List of specific I/Os

This list contains the specific analog input objects in the library.

Data point

Description

AI_AQualR_Measuring_0-10V

Analog input 0…10 V for

  • Room air quality
  • 0...2000 [ppm]

AI_AtmP_Measuring_0-10V_0-2000mbar

Analog input 0…10 V for

  • Atmospheric pressure
  • 0...2000 [mbar], 0...59.06 [inHg]

AI_Brgt_Measuring_0-10V

Analog input 0…10 V for

  • Brightness
  • 0...2000 [lx]

AI_BrgtFcd_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Brightness on facade
  • 0...150000 [lx]

AI_BrgtOdr_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Outdoor brightness
  • 0...150000 [lx]

AI_BrgtOdrEast_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Outdoor brightness east
  • 0...150000 [lx]

AI_BrgtOdrNorth_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Outdoor brightness north
  • 0...150000 [lx]

AI_BrgtOdrSouth_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Outdoor brightness south
  • 0...150000 [lx]

AI_BrgtOdrWest_Measuring_0-10V_0-150000lx

Analog input 0…10 V for

  • Outdoor brightness west
  • 0...150000 [lx]

AI_FanDiffP_Flow pressure measuring

Analog input P1 for

  • Fan differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_FanDiffP_Measuring_0-10V

Analog input 0…10 V for

  • Fan differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_HuRelOa_Measuring_0-10V_0-100%RH

Analog input 0…10 V for

  • Relative outside humidity
  • 0...100 [%RH]

AI_HuRelR_Measuring_0-10V

Analog input 0…10 V for

  • Relative humidity for room
  • 0...100 [%RH]

AI_Pwr_Measuring_0-10V

Analog input 0…10 V for

  • Power
  • 0.00...1000.00 [kW]

AI_SolRdn_Measuring_0-10V_0-2000W_m2

Analog input 0…10 V for

  • Solar radiation
  • 0...2000 [W/m2], 0...185.81 [W/ft2]

AI_SolRdnFcd_Measuring_0-10V_0-2000W_m2

Analog input 0…10 V for

  • Solar radiation on facade
  • 0...2000 [W/m2], 0...185.81 [W/ft2]

AI_SpShftIn_Measuring_1000-1175Ohm_-3-+3K

Analog input 1000-1175 Ohm for

  • Setpoint shift input value
  • -3.0…3.0 [K], -5.4...5.4 [°F]
  • For DXR2 Automation stations only.

AI_TEx_Measuring_0-10V

Analog input 0…10 V for

  • Extract air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_Ni1000

Analog input Ni 1000 for

  • Extract air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_NTC10K

Analog input NTC 10k for

  • Extract air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_NTC100K

Analog input NTC 100k for

  • Extract air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_PT1K_EU

Analog input PT 1k for

  • Extract air temperature
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_PT1K_NA

Analog input PT 1k for

  • Extract air temperature
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TEx_Measuring_T1_PTC

Analog input PTC T1 for

  • Extract air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_0-10V

Analog input 0…10 V for

  • Mixed air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_Ni1000

Analog input Ni 1000 for

  • Mixed air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_NTC10K

Analog input NTC 10k for

  • Mixed air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_NTC100K

Analog input NTC 100k for

  • Mixed air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_PT1K_EU

Analog input PT 1k for

  • Mixed air temperature
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_PT1K_NA

Analog input PT 1k for

  • Mixed air temperature
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TMx_Measuring_T1_PTC

Analog input PTC T1 for

  • Mixed air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_0-10V

Analog input 0…10 V for

  • Outside air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_Ni1000

Analog input Ni 1000 for

  • Outside air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_NTC10K

Analog input NTC 10k for

  • Outside air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_NTC100K

Analog input NTC 100k for

  • Outside air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_PT1K_EU

Analog input PT 1k for

  • Outside air temperature
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_PT1K_NA

Analog input PT 1k for

  • Outside air temperature
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOa_Measuring_T1_PTC

Analog input PTC T1 for

  • Outside air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_0-10V

Analog input 0…10 V for

  • Outside air temperature local
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_Ni1000

Analog input Ni 1000 for

  • Outside air temperature local
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_NTC10K

Analog input NTC 10k for

  • Outside air temperature local
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_NTC100K

Analog input NTC 100k for

  • Outside air temperature local
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_PT1K_EU

Analog input PT 1k for

  • Outside air temperature local
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_PT1K_NA

Analog input PT 1k for

  • Outside air temperature local
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TOaLoc_Measuring_T1_PTC

Analog input PTC T1 for

  • Outside air temperature local
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_0-10V

Analog input 0…10 V for

  • Primary air temperature for air after-treatment
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_Ni1000

Analog input Ni 1000 for

  • Primary air temperature for air after-treatment
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_NTC10K

Analog input NTC 10k for

  • Primary air temperature for air after-treatment
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_NTC100K

Analog input NTC 100k for

  • Primary air temperature for air after-treatment
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_PT1K_EU

Analog input PT 1k for

  • Primary air temperature for air after-treatment
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_PT1K_NA

Analog input PT 1k for

  • Primary air temperature for air after-treatment
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TPaAftrt_Measuring_T1_PTC

Analog input PTC T1 for

  • Primary air temperature for air after-treatment
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TR_Measuring_0-10V

Analog input 0…10 V for

  • Room temperature
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_Ni1000

Analog input Ni 1000 for

  • Room temperature
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_NTC10K

Analog input NTC 10k for

  • Room temperature
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_NTC100K

Analog input NTC 100k for

  • Room temperature
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_PT1K_EU

Analog input PT 1k for

  • Room temperature
  • Europe
  • 3.85 [Ohm/K]
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_PT1K_NA

Analog input PT 1k for

  • Room temperature
  • North America
  • 3.75 [Ohm/K]
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TR_Measuring_T1_PTC

Analog input PTC T1 for

  • Room temperature
  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_TSu_Measuring_0-10V

Analog input 0…10 V for

  • Supply air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_Ni1000

Analog input Ni 1000 for

  • Supply air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_NTC100K

Analog input NTC 100k for

  • Supply air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_NTC10K

Analog input NTC 10k for

  • Supply air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_PT1K_EU

Analog input PT 1k for

  • Supply air temperature
  • Europe
  • 3.85 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_PT1K_NA

Analog input PT 1k for

  • Supply air temperature
  • North America
  • 3.75 [Ohm/K]
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_TSu_Measuring_T1_PTC

Analog input PTC T1 for

  • Supply air temperature
  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_VavExAirFl_Measuring_0-10V

Analog input 0…10 V for

  • Extract air VAV air volume flow
  • 0...1000 [m3/h], 0...588.6 [ft3/min], 277.78 [l/s]

AI_VavExAirV_Measuring_0-10V

Analog input 0…10 V for

  • Extract air VAV air velocity
  • 0.0...10.0 [m/s], 0.0...1968.5 [ft/min]

AI_VavExDiffP_Flow pressure measuring

Analog input P1 for

  • Extract air VAV differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_VavExDiffP_Measuring_0-10V

Analog input 0…10 V for

  • Extract air VAV differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_VavSuAirFl_Measuring_0-10V

Analog input 0…10 V for

  • Supply air VAV air volume flow
  • 0.0...1000.0 [m3/h], 0...588.6 [ft3/min], 277.78 [l/s]

AI_VavSuAirV_Measuring_0-10V

Analog input 0…10 V for

  • Supply air VAV air velocity
  • 0.0...10.0 [m/s], 0.0...1968.5 [ft/min]

AI_VavSuDiffP_Flow pressure measuring,
AI_VavSuDiffP1_Flow pressure measuring,
AI_VavSuDiffP2_Flow pressure measuring

Analog input P1 for

  • Supply air VAV differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_VavSuDiffP_Measuring_0-10V,
AI_VavSuDiffP1_Measuring_0-10V,
AI_VavSuDiffP2_Measuring_0-10V

Analog input 0…10 V for

  • Supply air VAV differential air pressure
  • 0...500 [Pa], 0...2.008 [inWC]

AI_WdSpd_Measuring_0-10V_0-50m_s

Analog input 0…10 V for

  • Wind speed
  • 0...50 [m/s], 0...9842.5 [ft/min]

AI_WdSpdFst_Measuring_0-10V_0-50m_s

Analog input 0…10 V for

  • First wind speed
  • 0...50 [m/s], 0...9842.5 [ft/min]

AI_WdSpdScd_Measuring_0-10V_0-50m_s

Analog input 0…10 V for

  • Second wind speed
  • 0...50 [m/s], 0...9842.5 [ft/min]

List of generic I/Os

This list contains the generic analog input objects in the library.

Data point

Description

AI_AI_Measuring_0-10V

Analog input 0...10 V

AI_AI_Measuring_0-10V_0-50Pa

Analog input 0...10 V for

  • 0…50 [Pa], 0.201 [inWC]

AI_AI_Measuring_0-10V_0-100%

Analog input 0...10 V for

  • 0...100 [%]

AI_AI_Measuring_0-10V_0-100%RH

Analog input 0...10 V for

  • 0...100 [%RH]

AI_AI_Measuring_0-10V_0-250Pa

Analog input 0...10 V for

  • 0...250 [Pa], 0...1.004 [inWC]

AI_AI_Measuring_0-10V_0-500Pa

Analog input 0...10 V for

  • 0...500 [Pa], 0...2.008 [inWC]

AI_AI_Measuring_0-10V_0-1500lx

Analog input 0...10 V for

  • 0...1500 [lx]

AI_AI_Measuring_0-10V_0-1500Pa

Analog input 0...10 V for

  • 0...1500 [Pa], 0...6.023 [inWC]

AI_AI_Measuring_0-10V_0-2000ppm

Analog input 0…10 V for

  • 0...2000 [ppm]

AI_AI_Measuring_0-10V_0-10000lx

Analog input 0...10 V for

  • 0...10000 [lx]

AI_AI_Measuring_0-10V_0-500Microg_m3

Analog input 0...10 V for

  • 0...500 [µg/m3]

AI_AI_Measuring_0-10V_-3-+3K

Analog input 0…10 V for

  • -3.0…3.0 [K], -5.4...5.4 [°F]

AI_AI_Measuring_2500_Ohm

Analog input 2500 Ohm

AI_AI_Measuring_NI1000

Analog input NI 1000

  • -50.0...80.0 [°C], -58.0...176.0 [°F]

AI_AI_Measuring_NI1000_0-130C

Analog input NI 1000 for

  • 0.0...130.0 [°C], 32.0...266.0 [°F]

AI_AI_Measuring_NI1000_5-40C

Analog input NI 1000 for

  • 5.0...40.0 [°C], 41.0...104.0 [°F]

AI_AI_Measuring_NI1000_5-95C

Analog input NI 1000 for

  • 5.0...95.0 [°C], 41.0...203.0 [°F]

AI_AI_Measuring_NI1000_-40-+50C

Analog input NI 1000 for

  • -40.0...50.0 [°C], -40.0...122.0 [°F]

AI_AI_Measuring_NTC10K

Analog input NTC 10k

AI_AI_Measuring_NTC10K_0-50C

Analog input NTC 10k

  • 0.0...50.0 [°C], 32.0...122.0 [°F]

AI_AI_Measuring_NTC100K

Analog input NTC 100k

AI_AI_Measuring_T1_PTC

Analog input T1 PTC

AI_AI_Measuring_PT1K_EU

Analog input PT 1k for

  • Europe, 3.85 [Ohm/K]

AI_AI_Measuring_PT1K_NA

Analog input PT 1k for

  • North America, 3.75 [Ohm/K]