Analog outputs

This section describes analog output objects (AO) for specific applications.

For the description of properties see chapter "TX-I/O modules" in the Hardware catalog.

List of specific I/Os

This list contains the specific analog output objects in the library.

Data point

Description

AO_CclSpWfl_Positioning

Analog output 0...10 V for

  • Setpoint for water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_CclVlvPos_Positioning

Analog output 0...10 V for

  • Cooling coil valve position
  • 0...100 [%]

AO_CclVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Cooling coil valve position
  • 0...100 [%]

AO_CclVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM)

  • Thermal actuators
  • Cooling coil valve position
  • 0...100 [%]

AO_CclVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Cooling coil valve position
  • 0...100 [%]

AO_DmpOaPos_Positioning

Analog output 0...10 V for

  • Outside air damper position
  • 0...100 [%]

AO_DmpOaPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Outside air damper position
  • 0...100 [%]

AO_FanVarSpd_Positioning

Analog output 0...10 V for

  • Fan speed
  • 0...100 [%]

AO_HCclSpWfl_Positioning

Analog output 0...10 V for

  • Setpoint for water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_HCclVlvPos_Positioning

Analog output 0...10 V for

  • Heating/cooling valve position
  • 0...100 [%]

AO_HCclVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating/cooling valve position
  • 0...100 [%]

AO_HCclVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating/cooling valve position
  • 0...100 [%]

AO_HCclVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating/cooling valve position
  • 0...100 [%]

AO_HCclVlvPosC_Positioning

Analog output 0...10 V for

  • Heating/cooling valve position for cooling
  • 0...100 [%]

AO_HCclVlvPosC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating/cooling valve position for cooling
  • 0...100 [%]

AO_HCclVlvPosC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating/cooling valve position for cooling
  • 0...100 [%]

AO_HCclVlvPosC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating/cooling valve position for cooling
  • 0...100 [%]

AO_HCclVlvPosH_Positioning

Analog output 0...10 V for

  • Heating/cooling valve position for heating
  • 0...100 [%]

AO_HCclVlvPosH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating/cooling valve position for heating
  • 0...100 [%]

AO_HCclVlvPosH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating/cooling valve position for heating
  • 0...100 [%]

AO_HCclVlvPosH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating/cooling valve position for heating
  • 0...100 [%]

AO_HCclVlvShofC_Positioning

Analog output 0...10 V for

  • Heating/cooling coil shutoff valve cooling
  • 0...100 [%]

AO_HCclVlvShofC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating/cooling coil shutoff valve cooling
  • 0...100 [%]

AO_HCclVlvShofC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating/cooling coil shutoff valve cooling
  • 0...100 [%]

AO_HCclVlvShofC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating/cooling coil shutoff valve cooling
  • 0...100 [%]

AO_HCclVlvShofH_Positioning

Analog output 0...10 V for

  • Heating/cooling coil shutoff valve heating
  • 0...100 [%]

AO_HCclVlvShofH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating/cooling coil shutoff valve heating
  • 0...100 [%]

AO_HCclVlvShofH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating/cooling coil shutoff valve heating
  • 0...100 [%]

AO_HCclVlvShofH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating/cooling coil shutoff valve heating
  • 0...100 [%]

AO_HclElPos_Positioning

Analog output 0...10 V for

  • Heating coil electric position
  • 0...100 [%]

AO_HclElPos_Pulsewidth mod.: Constant period

Analog output pulse-width modulation (PWM) with constant pulse period for

  • Heating coil electric position
  • 0...100 [%]

AO_HclSpWfl_Positioning

Analog output 0...10 V for

  • Setpoint for water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_HclVlvPos_Positioning

Analog output 0...10 V for

  • Heating coil valve position
  • 0...100 [%]

AO_HclVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Heating coil valve position
  • 0...100 [%]

AO_HclVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Heating coil valve position
  • 0...100 [%]

AO_HclVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Heating coil valve position
  • 0...100 [%]

AO_HpuVarSpd_Positioning

Analog output 0...10 V for

  • Heat pump variable speed
  • 0...100 [%]

AO_RadElPos_Positioning

Analog output 0...10 V for

  • Radiator electric position
  • 0...100 [%]

AO_RadElPos_Pulsewidth mod.: Constant period

Analog output pulse-width modulation (PWM) with constant pulse period for

  • Radiator electric position
  • 0...100 [%]

AO_RadVlvPos_Positioning

Analog output 0...10 V for

  • Radiator valve position
  • 0...100 [%]

AO_RadVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiator valve position
  • 0...100 [%]

AO_RadVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiator valve position
  • 0...100 [%]

AO_RadVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiator valve position
  • 0...100 [%]

AO_RcgSpWfl_Positioning

Analog output 0...10 V for

  • Setpoint for water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_RcgSpWflC_Positioning

Analog output 0...10 V for

  • Setpoint for water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_RcgVlvPos_Positioning

Analog output 0...10 V for

  • Radiant ceiling valve position
  • 0...100 [%]

AO_RcgVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant ceiling valve position
  • 0...100 [%]

AO_RcgVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant ceiling valve position
  • 0...100 [%]

AO_RcgVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant ceiling valve position
  • 0...100 [%]

AO_RcgVlvPosC_Positioning

Analog output 0...10 V for

  • Radiant ceiling valve position for cooling
  • 0...100 [%]

AO_RcgVlvPosC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant ceiling valve position for cooling
  • 0...100 [%]

AO_RcgVlvPosC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant ceiling valve position for cooling
  • 0...100 [%]

AO_RcgVlvPosC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant ceiling valve position for cooling
  • 0...100 [%]

AO_RcgVlvPosH_Positioning

Analog output 0...10 V for

  • Radiant ceiling valve position for heating
  • 0...100 [%]

AO_RcgVlvPosH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant ceiling valve position for heating
  • 0...100 [%]

AO_RcgVlvPosH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant ceiling valve position for heating
  • 0...100 [%]

AO_RcgVlvPosH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant ceiling valve position for heating
  • 0...100 [%]

AO_RcgVlvShofC_Positioning

Analog output 0...10 V for

  • Radiant ceiling shutoff valve cooling
  • 0...100 [%]

AO_RcgVlvShofC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant ceiling shutoff valve cooling
  • 0...100 [%]

AO_RcgVlvShofC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant ceiling shutoff valve cooling
  • 0...100 [%]

AO_RcgVlvShofC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant ceiling shutoff valve cooling
  • 0...100 [%]

AO_RcgVlvShofH_Positioning

Analog output 0...10 V for

  • Radiant ceiling shutoff valve heating
  • 0...100 [%]

AO_RcgVlvShofH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant ceiling shutoff valve heating
  • 0...100 [%]

AO_RcgVlvShofH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant ceiling shutoff valve heating
  • 0...100 [%]

AO_RcgVlvShofH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant ceiling shutoff valve heating
  • 0...100 [%]

AO_RfrVlvPos_Positioning

Analog output 0...10 V for

  • Radiant floor valve position
  • 0...100 [%]

AO_RfrVlvPos_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant floor valve position
  • 0...100 [%]

AO_RfrVlvPos_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant floor valve position
  • 0...100 [%]

AO_RfrVlvPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant floor valve position
  • 0...100 [%]

AO_RfrVlvPosC_Positioning

Analog output 0...10 V for

  • Radiant floor valve position for cooling
  • 0...100 [%]

AO_RfrVlvPosC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant floor valve position for cooling
  • 0...100 [%]

AO_RfrVlvPosC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant floor valve position for cooling
  • 0...100 [%]

AO_RfrVlvPosC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant floor valve position for cooling
  • 0...100 [%]

AO_RfrVlvPosH_Positioning

Analog output 0...10 V for

  • Radiant floor valve position for heating
  • 0...100 [%]

AO_RfrVlvPosH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant floor valve position for heating
  • 0...100 [%]

AO_RfrVlvPosH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant floor valve position for heating
  • 0...100 [%]

AO_RfrVlvPosH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant floor valve position for heating
  • 0...100 [%]

AO_RfrVlvShofC_Positioning

Analog output 0...10 V for

  • Radiant floor shutoff valve cooling
  • 0...100 [%]

AO_RfrVlvShofC_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant floor shutoff valve cooling
  • 0...100 [%]

AO_RfrVlvShofC_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant floor shutoff valve cooling
  • 0...100 [%]

AO_RfrVlvShofC_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant floor shutoff valve cooling
  • 0...100 [%]

AO_RfrVlvShofH_Positioning

Analog output 0...10 V for

  • Radiant floor shutoff valve heating
  • 0...100 [%]

AO_RfrVlvShofH_Pulsewidth mod.: Spring return

Analog output pulse-width modulation (PWM) for

  • Actuators with spring return
  • Radiant floor shutoff valve heating
  • 0...100 [%]

AO_RfrVlvShofH_Pulsewidth modulation: Thermal

Analog output pulse-width modulation (PWM) for

  • Thermal actuators
  • Radiant floor shutoff valve heating
  • 0...100 [%]

AO_RfrVlvShofH_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Radiant floor shutoff valve heating
  • 0...100 [%]

AO_VavExPos_Positioning

Analog output 0...10 V for

  • Extract air VAV position
  • 0...100 [%]

AO_VavExPos_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Extract air VAV position
  • 0...100 [%]

AO_VavExSpAirFl_Positioning

Analog output 0...10 V for

  • Extract air VAV setpoint for air volume flow
  • 0...1000 [m3/h], 0...588.6 [ft3/min], 277.78 [l/s]

AO_VavSuPos_Positioning,
AO_VavSuPos1_Positioning,
AO_VavSuPos2_Positioning

Analog output 0...10 V for

  • Supply air VAV position
  • 0...100 [%]

AO_VavSuPos_Three points control,
AO_VavSuPos1_Three points control,
AO_VavSuPos2_Three points control

Analog output 3-position actuator for

  • Triac modules
  • Supply air VAV position
  • 0...100 [%]

AO_VavSuSpAirFl_Positioning

Analog output 0...10 V for

  • Supply air VAV setpoint for air volume flow
  • 0...1000 [m3/h], 0...588.6 [ft3/min], 277.78 [l/s]

List of generic I/Os

This list contains the generic analog output objects in the library.

Data point

Description

AO_AO_Positioning

Analog output 0...10 V for

  • 0...100 [%]

AO_AO_Positioning_0-10V

Analog output 0...10 V

AO_AO_Positioning_0-10V_0-100%

Analog output 0...10 V for

  • 0...100 [%]

AO_AO_Positioning_0-10V_0-10000l_h

Analog output 0...10 V for

  • Water volume flow
  • 0...10000 [l/h], 0.000...44.030 [gus/min],
    0.0000...2.7800 [l/s], 0.000...36.660 [ggb/min]

AO_AO_Positioning_0-10V_0-1000m3_h

Analog output 0...10 V for

  • Air volume flow
  • 0...1000 [m3/h], 0...588.6 [ft3/min], 277.78 [l/s]

AO_AO_Pulsewidth mod.: Constant period_PWM_Const

Analog output PWM with constant pulse period

  • For triac modules
  • 0...100 [%]
  • Typically for electromechanic actuators

AO_AO_Pulsewidth modulation: Thermal_PWM_0-100

Analog output PWM with variable pulse period

  • For triac modules
  • 0...100 [%]
  • Typically for thermal actuators, without undercool- and overheat functionality

AO_AO_Pulsewidth modulation: Thermal_PWM_5-50

Analog output PWM with variable pulse period

  • For triac modules
  • 5...50 [%]
  • Typically for thermal actuators, with undercool- and overheat functionality
    • 5 [%] = actuator pre-heated but fully closed
    • 50 [%] = actuator fully open

AO_AO_Three points control_3pos_Relay

Analog output 3-position actuator for

  • Relay modules

AO_AO_Three points control_3pos_Triac

Analog output 3-position actuator for

  • Triac modules