Lighting life cycle (LgtLifeCyc11)

Overview

The application function "Lighting life cycle 11, lifetime phase, operating hours, maintenance" (LgtLifeCyc11) calculates the Operating hours state of the lamp connected to the lighting output (Burn-in phase, Operation phase, Lifetime expired).

If configured, the following functions are supported:

 

Function Operating hours state

The BACnet object for each lighting output stores the following values:


The AF sets the Operating hours state based on operating hours:

Function Maintenance factor

The AF considers the Maintenance factor (MntnFac) based on the operating hours and expected operating hours. It provides the necessary information to the other involved application functions.

The function is disabled if (MntnFac = 1) or (expected operating hours = 0).

Function Adaptation of illuminance

The AF adapts the power of the lighting output

It provides the necessary information to the other involved application functions.

The function is disabled if ImncAda = 1.

Configuration

Parameters

Description

Parameter

Default value

Operating phase maximum value

OpMaxVal

100 [%]

Operating phase minimum value

OpMinVal

0.5 [%]

Burn-in minimum value

BrninMinVal

100 [%]

Maintenance factor

MntnFac

0.67

Adaptation of illuminance

ImncAda

1

Interface

None (the AF writes directly to the lighting output).

Note:
The lighting output object forms the basis for service and maintenance information.

Operating hours are saved as a property of the BACnet object for each lighting output. The value is saved for each save cycle on the room automation station, e.g. approximately every 15 minutes. The operating hours counter can be reset online, after changing the lamp. The management station directly accesses the BACnet object to visualize service and maintenance information.

Engineering and commissioning

Disable functionality
Burn-in functionality and lifetime supervision can be disabled by setting burn-in operating hours and/or expected operating hours to 0.


Burn-in
Newly installed fluorescent lamps must be burned in to achieve their maximum brightness and life cycle:

Refer to manufacturer data for more detailed information.

The burn-in function ensures that new fluorescent lights are not dimmed during the required burn-in period, either by a control algorithm or manual dimming. Only states Off or BrninMinVal are permitted. BrninMinVal must be configured.

As soon as the hours of operation counter reaches the required number of hours for burn-in, dimming is permitted between limits OpMinVal and OpMaxVal. They must be configured.

Note: S-Mode devices do not support Burn-in.


Operation phase
The operation phase depends on type of light. Whereas halogen bulbs have an average service life of approx. 2,000 hours; LEDs have up to 50,000 hours. This period is referred to as expected operating hours. Refer to manufacturer data for more detailed information.


Operating hours reset
The operating hours must be reset online.

The operating hours are stored with the room automation station's store cycle.


Maintenance factor
The maintenance factor is normally provided by a lighting designer.
It considers

A normal office environement has a value of 0.67.