Heating/cooling state determination (HCStaDtr11)

Overview

The application function "Heating/cooling state determination 11" (HCStaDtr11) determines whether HVAC control is currently heating or cooling or neither, and supplies this information in a BACnet object.
In addition it ensures a minimum switching delay (changeover delay) between heating and cooling.

Function

Input:
The AF compares the room temperature to current setpoints, and checks whether a PID controller actively controls a device.


Output:
The heating/cooling state (HCSta) is supplied for use by the following AFs: RThLd11, ROpUn11 (as a BACnet object) and for SpTR11 (as an internal connection). In addition it provides a release heating and a release cooling signal (as an internal connection) to enable the heating and cooling room temperature control sequences.


Configuration:
The switching points can be shifted and a time delay can be configured to smooth switching.

Configuration

Objects

Description

Object

Default value

Shift of switch-on point for cooling state

ShftOnPtCSta

0 [K]
0.0 [°F]

Shift of switch-on point for heating state

ShftOnPtHSta

0 [K]
0.0 [°F]

Switch-on delay for heating/cooling changeover

DlyOnHCChovr

2 [min]

Temperature difference unit
▶ Defined by selected engineering unit – do not change.

TDiffUnit

[K]
[°F]

Interface

Interface

Description

Type

Ref.

Owned by

HCSta

Heating/cooling state

1:Neither
2:Heating
3:Cooling

MCalcVal

-

Engineering and commissioning

The Switch-on delay for heating/cooling changeover (DlyOnHCChovr) must be configured in other places as well:

In the event of differing values the higher value wins.