Rapid ventilation operation (RpdVntOp11)
Overview
The application function "Rapid ventilation operation 11" (RpdVntOp11) sends a request for AF HvacPltModxx to start/stop the function "rapid ventilation" used to improve the room air quality.
The request is either entered manually on a room operator unit, or is generated automatically by a trigger signal (if configured).
Function
Request to start rapid ventilation
- By room occupant, using a room operator unit
- The room operator unit writes to data point RpdVnt
- By the application, based on CmfCndTrg/EefCndTrg and supplied by AF ROpMod11
The response can be configured for each trigger signal. - Upon Comfort Condition Trigger (CmfCndTrg), activated by automatic
- Upon Comfort Condition Trigger (CmfCndTrg), activated manually by room occupant
- Upon Energy Efficiency Condition Trigger (EefCndTrg), activated by automatic
- Upon Energy Efficiency Condition Trigger (EefCndTrg), activated manually by room occupant
Request to stop rapid ventilation
- By room occupant, using a room operator unit
- The room operator unit writes to data point RpdVnt.
- By the application
- Rapid ventilation timer (TiRnRpdVnt) has elapsed.
- Conditions for manual operation (see below) no longer apply (this stops the timer).
Conditions which prevent rapid ventilation
- Present priority of PltOpMod is 1..12
- Manual operation is locked (ManOpCnd = Locked), supplied by AF ROpMod11.
Configuration
Parameters
Description | Parameter | Default value |
|---|---|---|
Rapid ventilation runtime | TiRnRpdVnt | 60 [min] |
Operating command for energy efficiency condition trigger at automatic 1:None | OpCmdEefAuto | 1:None |
Operating command for energy efficiency condition trigger at manual Enumeration see OpCmdEefAuto | OpCmdEefMan | 1:None |
Operating command for comfort condition trigger at automatic Enumeration see OpCmdEefAuto | OpCmdCmfAuto | 1:None |
Operating command for comfort condition trigger at manual Enumeration see OpCmdEefAuto | OpCmdCmfMan | 1:None |
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
RpdVnt | Rapid ventilation 0:Off | BPrcVal | ● | - |