Orientation light (LgtOrnt11)

Overview

The application function "Orientation light 11" (LgtOrnt11) calculates the state of an orientation light depending on the configured functionality and provides it via grouping to the related orientation light outputs.

Function

The AF supports the following indication functions (IndFnct) based on the room operating mode and/or brightness:

Configuration

Parameters

Description

Parameter

Default value

Indication function
▶ Sources to be considered for state of orientation light.

1:None
2:Room operating mode
3:Brightness
4:Room operating mode & brightness

IndFnct

1:None

Configuration switch-on indication
▶ Room operating modes where the orientation light is switched on.

1:Protection
2:Protection & Economy
3:Protection & Economy & Pre-Comfort
4:Protection & Economy & Pre-Comfort & Comfort

IndOnCnf

4:Protection & Economy & Pre-Comfort

Switch-on point
▶ Configuration for brightness dependent state of orientation light.

SwiOnPt

100 [lx]

Hysteresis for brightness
▶ Configuration for brightness dependent state of orientation light.

HysBrgt

50 [lx]

Interface

Interface

Description

Type

Ref.

Owned by

LgtOrnt

Orientation light

1:Off
2:On

MPrcVal

-

RCtl

Room control

GrpMaster

Room