Fan coil unit ventilation control (FcuVntCtl11)

Overview

The application function "Fan coil unit ventilation control 11" (FcuVntCtl11) collaborates with FCU fans for ventilation and/or room air quality control.

Function

Different modes are available for ventilation control; the behavior is selectable by parameter.

Ventilation mode
The ventilation mode can be set per room operating mode to:

1) Air quality sensor required in the room.

 

The table shows factory default settings for min vent and air quality parameters:

Plant mode

Ventilation mode

Sp air quality
[ppm]

Outside air damper min position [%]

1 Off

Off

 

 

2 Protection*

Off

1500

20

3 Economy*

Off

1500

30

4 Pre-Comfort*

Dcv

1100

40

5 Comfort*

Min & Dcv

900

50

6 Warm-up

Off

 

 

7 Cool down

Off

 

 

8 Room low temperature protection (frost)

Off

 

 

9 Condensate overflow

Off

 

 

10 Free cooling

Depends on ROpMod

Depends on ROpMod

Depends on ROpMod

11 Night cooling

Off

 

 

12 Ventilation

s/a Comfort

s/a Comfort

s/a Comfort

13 Equipment temperature protection

Off

 

 

14 Emergency off

Off

 

 

Not used

 

 

 

Not used

 

 

 

Not used

 

 

 

*For these modes the parameters can be individually adjusted.

 

Periodic fan kick
Parameters are available to configure periodic cycling of the fan on and off. The fan can be enabled to run at the lowest speed at regular intervals, for the length of time in TiOnDutyCyc. See figure.

The length of the duty cycle off interval can be configured for each operating mode (DutyCycCmf, DutyCycPcf, DutyCycEco, DutyCycPrt). A duty cycle of 0min (default) means the feature is disabled.

Note
If the room temperature is measured with an extract air temperature sensor, the fan must be switched on to ensure the effective room temperature is measured correctly. In this case, periodic fan kick can be used to periodically cycle the fan.

 

Exception handling
For air quality control, the ventilation mode must be set to Dcv or Min & Dcv, FanAvlVent must be Yes and the air quality sensor must be Valid. If the sensor is failed or absent, then the ventilation mode cannot be Dcv or Min & Dcv; in this case FanVntReq is set to Min.

Configuration

Objects

Description

Object

Type

Default value

Setpoint room air quality for comfort

SpAQualRCmf

ACnfVal

900 [ppm]

Setpoint room air quality for pre-comfort

SpAQualRPcf

ACnfVal

1100 [ppm]

Setpoint room air quality for economy

SpAQualREco

ACnfVal

1500 [ppm]

Setpoint room air quality for protection

SpAQualRPrt

ACnfVal

1500 [ppm]

Parameters

Description

Parameter

Default value

Comfort configuration

1:Off
2:Minimum ventilation
3:Demand-controled ventilation
4:Minimum ventilation & Demand-controlled ventilation

CmfCnf

4:Minimum ventilation & Demand-controlled ventilation

Pre-Comfort configuration

Enumeration see CmfCnf

PcfCnf

3:Demand-controled ventilation

Economy configuration

Enumeration see CmfCnf

EcoCnf

2:Minimum ventilation

Protection configuration

Enumeration see CmfCnf

PrtCnf

2:Minimum ventilation

Minimum position outside air damper for comfort

DmpOaPosMinCmf

50 [%]

Minimum position outside air damper for pre-comfort

DmpOaPosMinPcf

40 [%]

Minimum position outside air damper for economy

DmpOaPosMinEco

30 [%]

Minimum position outside air damper for protection

DmpOaPosMinPrt

20 [%]

Duty cycling in comfort

DutyCycCmf

0 [min]

Duty cycling in pre-comfort

DutyCycPcf

0 [min]

Duty cycling in economy

DutyCycEco

0 [min]

Duty cycling in protection

DutyCycPrt

0 [min]

Switch-on time duty cycling
▶ If periodic cycling of ventilation air flow is desired, TiOnDutyCyc defines the length of "on" time for the ventilation air flow. Periodic cycling requires duty cycle parameter(s) to be set to non zero value (DutyCycCmf, DutyCycPcf, DutyCycEco, DutyCycPrt).

TiOnDutyCyc

6 [min]

Interface

Interface

Description

Type

Ref.

Owned by

PrSpVnt

Present ventilation setpoint

APrcVal

-

DmpOaVntCtr

Ventilation controller for outside air damper

Controller

-

FanVntCtr

Ventilation controller for fan

Controller

-

RCtl

Room control

GrpMaster

Room

SpAQualRCmf

Setpoint room air quality for comfort

ACnfVal

-

SpAQualRPcf

Setpoint room air quality for pre-comfort

ACnfVal

-

SpAQualREco

Setpoint room air quality for economy

ACnfVal

-

SpAQualRPrt

Setpoint room air quality for protection

ACnfVal

-

Engineering and commissioning