DRA-specific

Occupancy sensor

DRA/ABT

KNX/ETS

Remark

Application Block

Direction

DPT ID

Format

DPT name

PRD
Presence detector

Input

1.018 1)

B1

DPT_Occupancy

Workaround for Desigo V5.x: use mapping via GPDI.

Output

1.018 1)

B1

DPT_Occupancy

Workaround for Desigo V5.x: use mapping via GPDO.

1) Not supported in Desigo V5.x

Time

DRA controller can transmit time information to the KNX device but cannot receive time information from KNX device.

DRA/ABT

KNX/ETS

Application Block

Direction

DPT ID

Format

DPT name

SCLO
System clock

Output

10.001 1)

N3N5r2N6r2N6

DPT_TimeOfDay

1) Not supported in Desigo 5.x

Date

DRA controller can transmit date information to the KNX device but cannot receive date information from KNX device.

DRA/ABT

KNX/ETS

Application Block

Direction

DPT ID

Format

DPT name

SCLO
System clock

Output

11.00112)

r3N5r4N4r1U7

DPT_Date

1) Not supported in Desigo 5.x

Combined Date and Time

DRA controller can transmit date and time information to the KNX device but cannot receive date and time information from KNX device.

DRA/ABT

KNX/ETS

Application Block

Direction

DPT ID

Format

DPT name

SCLO System clock

Output

19.001 1)

U8[r4U4][r3U5][U3U5][r2U6][r2U6]B16

DPT_DateTime

1) Not supported in Desigo 5.x

Scene Number

DRA/ABT

KNX/ETS

Remark

Application Block

Direction

DPT ID

Format

DPT name

-

Input

17.001 1)

r2U6

DPT_SceneNumber

Wokaround: Use DPT 18.001 with disabled control feature, application block SCS.

1) Not supported

Scene Control

DRA/ABT

KNX/ETS

Application Block

Direction

DPT ID

Format

DPT name

SCS

Input

18.001

B1r1U6

DPT_SceneControl

Scene Info

DRA/ABT

KNX/ETS

Application Block

Direction

DPT ID

Format

DPT name

SCS

Output

26.001

r1b1U6

DPT_SceneInfo

User presence sensor

DRA/ABT

KNX/ETS

Remark

Application Block

Direction

DPT ID

Format

DPT name

UPS
User presence sensor

Input

1.018

B1 1)

DPT_Occupancy

Workaround for Desigo V5.x: use mapping via GPDI.

Output

1.018

B1 1)

DPT_Occupancy

Workaround for Desigo V5.x: use mapping via GPDO.

1) Not supported in Desigo V5.x

Window/Door sensor

DRA/ABT

KNX/ETS

Remark

Application Block

Direction

DPT ID

Format

DPT name

WOS
Window switch

Input

1.019

B1 1)

DPT_Window_Door

Workaround for Desigo V5.x: use mapping via GPDI.

Output

1.019

B1 1)

DPT_Window_Door

Workaround for Desigo V5.x: use mapping via GPDO.