DXP2 and DXR2 IP product description

DXP2.. and DXR2.. are compact, programmable room automation stations for HVAC, lighting and shading applications of which DXP2 are high temperature rated automation stations.

Every DXP2.. and DXR2.. room automation station has a fixed I/O mix and preloaded application types. The assortment of preloaded application types depends on the I/O mix of the room automation station.

Product description

DXR2.E09-1, Compact room automation station

  • 1 binary input and 2 universal inputs
  • 3 relays and 3 analog outputs
  • BACnet/IP communications
  • AC 230 V power supply

Order number: S55376-C110

Download data sheet: CM1N9204

DXR2.E09T-1, Compact room automation station

  • 1 binary input and 2 universal inputs
  • 4 triacs, 1 relay and 1 analog output
  • BACnet/IP communications
  • AC 230 V power supply

Order number: S55376-C111

Download data sheet: CM1N9204

DXR2.E10-1, Compact room automation station

  • 1 binary input and 2 universal inputs
  • 4 triacs and 3 relays
  • BACnet/IP communications
  • AC 230 V power supply

Order number: S55376-C109

Download data sheet: CM1N9204

DXR2.E10PL-1, Actuating room automation station
DXR2.E10PLX-1, Actuating room automation station

  • 1 binary input, 2 universal inputs and 1 pressure sensor
  • 4 triacs and 1 analog output
  • 30 respectively 60 data points for used physical I/Os and
    KNX PL-Link data points
  • BACnet/IP communications
  • AC 24 V power supply
  • Embedded damper actuator: 10 Nm

Order numbers:
DXR2.E10PL-102B (USA and Canada): S55376-C145
DXR2.E10PLX-102B (USA and Canada): S55376-C146

Download data sheet: A6V11259958

DXR2.E12P-1, Compact room automation station
DXR2.E12PX-1, Compact room automation station

  • 1 binary input, 2 universal inputs and 1 pressure sensor
  • 6 triacs and 2 analog outputs
  • 30 respectively 60 data points for used physical I/Os and
    KNX PL-Link data points
  • BACnet/IP communications
  • AC 24 V power supply

Order numbers:
DXR2.E12P-102A (worldwide, without USA and Canada): S55376-C108
DXR2.E12P-102B (USA and Canada): S55376-C126
DXR2.E12PX-102A (worldwide, without USA and Canada): S55376-C143
DXR2.E12PX-102B (USA and Canada): S55374-C252

Download data sheet: CM1N9205

DXR2.E17C-1, Compact room automation station
DXR2.E17CX-1, Compact room automation station

  • 3 binary inputs, 4 universal inputs, and 2 resistive inputs – vertical sash
  • 4 triacs and 4 analog outputs
  • 4 analog input membrane pressure modules
  • 1 face area module
  • 30 respectively 60 data points for used physical I/Os and
    KNX PL-Link data points
  • BACnet/IP communications
  • AC 24 V power supply

Order numbers:
DXR2.E17C-103A (worldwide, without USA and Canada): S55376-C134
DXR2.E17C-103B (USA and Canada): S55376-C136
DXR2.E17CX-103A (worldwide, without USA and Canada): S55376-C150
DXR2.E17CX-103B (USA and Canada): S55376-C149

Download data sheet: A6V10959860

DXP2.E18-1andDXR2.E18-1, Compact room automation station

  • 2 binary inputs and 4 universal inputs
  • 8 triacs and 4 analog outputs
  • BACnet/IP communications
  • AC 24 V power supply

Order numbers:
DXP2.E18-110BR: S55375-C106
DXR2.E18-101A (worldwide, without USA and Canada):: S55376-C107
DXR2.E18-101B (USA and Canada): S55376-C125
DXR2.E18-102A (worldwide, without USA and Canada):: S55376-C128

Download data sheet: CM1N9205

Additional information

On-board I/O functions

CM110569

DRA installation guide

CM111043

Product properties

DXP2 and DXR2 IP properties

Subsystem-specific extension properties

KNX PL-Link (FldBusMgmt - subsystem-specific extension)

Power supply data

DXR2.

Power supply

KNX PL-Link Power supply [mA]

Field power supply

DC 24 V (W)

AC 24 V (VA)

E09-1

AC 230 V

50

-

4 1)

E09T-1

AC 230 V

50

-

4 1)

E10-1

AC 230 V

50

-

4 1)

E10PL-1, E10PLX-1

AC 24 V

50

-

6

E12P-1, E12PX-1

AC 24 V

50

-

6

E17C-1, E17CX-1

AC24 V

50

2.4

6

E18-1

AC24 V

50

2.4

6

1) Max. 4 A for the common load of the Triacs and field supply. See data sheets for details.

NOTICE

notice

Equipment damage due to parallel operation of internal and external KNX power supply

Operating internal and external KNX power supply in parallel may lead to severe damage of the automation station.

  1. If an external power supply is used, make sure the internal KNX power supply is turned off.

NOTICE

notice

Communications fail due to insufficient KNX power supply

Communications of the KNX rail fail if the power consumption of the connected devices with KNX PL-Link and KNX S-Mode exceeds the power supplied by the internal or external power supply.

  1. Make sure that for devices with KNX S-Mode the correct value for power consumption is set in the Hardware and network editor > Inspector window > Properties > General tab.
  2. Make sure the power supplied by the internal or external power supply is larger than the power consumed by the connected devices with KNX Pl-Link and KNX S-Mode.

Inputs and outputs

DXR2.

Inputs

Outputs

ΔP

Digital Input

Universal Input 1)

Resistive Input, Vertical Sash

Triac high side

2)

Triac low side

3)

Triac output (Total VA)

Analog output (0..10 V)

Relay (3 step fan)

Relay (1 step fan)

E09-1

 

1

2

 

 

 

 

3

3

 

E09T-1

 

1

2

 

 

4

4

1

 

1

E10-1

 

1

2

 

 

4

4

 

3

 

E10PL-1, E10PLX-1

1

1

2

 

4

 

48

1

 

 

E12P-1, E12PX-1

1

1

2

 

6

 

48

2

 

 

E17C-1, E17CX-1

 

3

4

2

4

 

48

4

 

 

E18-1

 

2

4

 

8

 

48

4

 

 

1) Configurable: Ni Pt NTC Res 0..10V DI

2) Max. 6 VA per Triac output

3) Max. 4 A for the common load of the Triacs and field supply. See data sheets for details.

Supported devices

The following device types can be combined with DXR2.E.. room automation stations: