Supply chain extract air volume flow deviation (SplyAflDvnEx11)

Overview

The application function "Supply chain extract air volume flow deviation evaluation 11" (SplyAflDvnEx11) helps to optimize the central AHU fan speed by calculating the air flow deviation of the extract VAV dampers.

Function

The deviation signals of the extract VAV controllers from the room segments are collected.

Air flow deviation is calculated as: ((setpoint flow – measured flow) / setpoint flow)) x 100 [%]

The 10 highest deviations are evaluated and the average is used for fan speed optimization.

For monitoring, the number of deviations between 5...20% are counted.

Configuration

None

Interface

Interface

Description

Type

Ref.

Owned by

AirFlDvnExMax

Maximum of extract air volume flow deviation

ACalcVal

-

NumAirFlDvnEx

Number of extract air volume flow deviation

ACalcVal

-

SplyAirMst

Manager for supply chain air

GrpMaster

SplyAir11

Engineering and commissioning